HEATING TECHNIQUE Centrometal d.o.o. - Glavna 12, 40306 Macinec, Croatia, tel: +385 40 372 600, fax: +385 40 372 611

TECHNICAL INSTRUCTIONS For installation, setup and control of the solar control unit Cm-SOL

READY

Cm-SOL TU-SOL-12/2018-v2.03-ENG

Content Thank you for purchasing the product of Centrometal d.o.o. Please read these technical manuals carefully so that you can use and adjust this control unit as easily as possible. Once you have read the manuals, place them in an appropriate place where you can easily find them if you need further information on the operation and use of control unit. Please make sure that the contol unit is discontinued after the end of use to reduce the pollution of the environment.

CONTENT INTRODUCTION

3

TECHNICAL CHARACTERISTICS

4

BASIC PARTS

5

CONTROL UNIT INSTALLATION

7

BATTERY REPLACEMENT

8

CONTROL UNIT DESCRIPTION

9

CONTROL UNIT ACTUATION

10

MAIN DISPLAY / SYMBOLS

11

SYMBOLS OF THE SYSTEM FUNCTION

14

MAIN MENU

17

1. TANK

18

2. COLLECTOR

21

3. OPERATION

24

4. HYSTORY

34

5. DISPLAY

34

6. SAVE/LOAD

36

7. INFO

37

MENUS FOR SYSTEM CONFIGURATION 8. INSTALLATION

2

40 40

8.1. SYSTEM COMPONENTS

41

8.2. COLLECTOR

49

8.3. TANK

53

8.4. DHW HEATING

64

8.5. RECIRCULATION

66

8.6. LEGIONELLA PROTECTION

68

8.7. ENERGY MEASUREMENT

70

8.8. MANUAL TEST

72

8.9. SAVE/LOAD

73

8.10. INFO

74

8.11. INTERNET SUPERVISION

77

8.12. COUNTER RESET

78

ERROR LIST

79

WARNING LIST

82

INFORMATION LIST

83

ELECTRICAL CONNECTION

84

EXAMPLE OF SELECTING THE SOLAR SYSTEM COMPONENTS

86

COMMISSIONING LIST

90

Technical instructions Cm-SOL

Introduction

INTRODUCTION Solar control unit is intended for heating the DHW tank, accumulation tank (with or without built-in DHW tank) or swimming pool through solar collectors and / or boilers and / or el. heaters. The control unit can control heating up to 4 different tanks / swimming pool that can be heated up to 2 separate hot water solar collector fields and up to 2 types of conventional source (boilers) or el. heater. Pumps to collector can be operated with PWM or analog signal. In addition to the temperature sensors, also on the control unit it is possible to connect the flow meter and the pressure switch in the solar system. With standard tank heating control over temperature difference, control unit has protective functions such as collector cooling (over tank), collector freezing options, tank cooling (over collector or recirculation), legionella protection (disinfection function) and protection of outlets (pumps and valves ) of blocking due to long-term non using time. Also, it is possible to include the functions of examination of the priority tank filling, pumps pulse start, as well as annual holiday option (all protective functions are switched on at once), one-time heating of the tank, one-time extension of tank heating or tank disinfection ( legionella protection ). For the functions like heating of the tank with conventional source ( boiler ) or el. heater, recirculation, impulse start of the solar collector and disinfection of the tank it is possible to set schedual (timers) (two tables, for each day of the week, up to 3 times). All functions are controlled through a touch screen color screen that simplifies the use of control. As an additional equipment, a Cm WiFi-box can be connected via which it is possible to connect control unit to the local WiFi network for remote control and monitoring of the system.

Technical instructions Cm-SOL

3

Technical characteristics

TECHNICAL CHARACTERISTICS Technical characteristics CM-SOL Input 10x multifunctional inputs (each of which can be PT1000 or NTC5K or flow meter or pressure switch) 1x power supply +5V

Output

8x semi-conductor (triac) 1x potential-free relay with NO and NC

Output power

Triacs (8x) 1A/240V Relay (1x) 5A/30VDC/250VAC

Power supply Max. Power Electricity consumption Cross section conductor IP protection Environment temperature Display Control unit mass Housing material Control unit dimensions

195-265V/50Hz 6,3A/240VAC 3W 1-2,5 mm2 IP20 po EN -10 do 40°C touchscreen display 715 g Flame resistant ABS (UL94V-0) (WxHxD) 200x40x200

Sensor technical characteristics Sensor type Min. conductor cross section Max. conductor length

Pt1000, NTc5k 0,5-2,5 mm2 50 m

CE Declaration of conformity The product complies with the relevant directives and is labelled with the CE mark. The Declaration of conformity is available at request, please contact the manufacturer.

4

Technical instructions Cm-SOL

Basic parts

BASIC PARTS INPUT: - 10x multifunctional inputs for sensors (PT1000 or NTC5k sensor of the tank, boilers, solar collectors and outdoor sensor, flow meter or pressure switch) - 1x +5V power supply OUTPUT: - 8x standard (230V) - 2x PWM (for modulation pump) - 2x 0-10V analog (for modulation pump) - 1x relay output (with quiet or operational contact) - 2x CAL (for alarm moduler) - 1x USB connector for software loading - 1x UTP connector for connection of the additional equipment (WiFi box...) - 1x Main switch DELIVERY in the cardboard box: 1x solar control unit 1x Pt1000 (silicone cable for solar collector) 4x Pt1000 (2x tank, 1x boiler, 1x return) 3x dowel+screw 1x technical manual

Upper control unit lid Touch screen control unit display

Screw for upper lid (for service )

Screw for upper lid (for service) Main switch UTP connector (for additional equipment)

Status bar with LED diodes

Screw for lower lid Screw for lower lid Lower control unit lid

Cable input (for power supply sensors, pumps....) valves...)

Technical instructions Cm-SOL

5

Basic parts

BASIC PARTS STATUS BAR - LED diodes

YELLOW – active relay output RED – Active error GREEN – active heating with a conventional source GREEN – active heating with a solar collector RED – control unit power supply is switched on

Control unit INPUT / OUTPUT

Power supply 230V (F/N) Relay output USB konektor

Resistor for 1-4 triac (3,15A) Resistor for 5-8 triac (3,15A) Wall mounting position

Wall mounting position EARTHING (EARTH) EARTHING (EARTH) 10x multifunctional input for sensors (T1-T10) ) (PT1000 or NTC5k sensors for tank, boiler, solar collector and outdoor sensor, flow meter and pressure switch)

Cable holder 8x semi conductor output (pumps, valves) (O1-O8) 2x alarm output (CAL1 common) (CAL) 2x output 0-10V (pumps) (0-10V)

Power supply +5V (+5V)

6

2x PWM output (pumps) (PWM)

Technical instructions Cm-SOL

Control unit installation

CONTROL UNIT INSTALLATION Solar controler is installed on a wall or flat hard surface in a closed dry area. First, 3 holes in diameter 6mm x 35 - 40mm should be drilled at the mounting site according to the bottom sketch. Three dowels are inserted into the holes and in the upper dowel need to be screwed the screw with a distance of approx. 4mm from the wall.

mm 0,6 17

152 mm

~4 mm

m

6m

155 mm

From the control unit remove the lower lid, hang the control unit on the upper screw, insert the screws at the mounting positions of the control unit and tighten the screws in the wall dowels.

hang

tighten tighten

Technical instructions Cm-SOL

7

Battery replacement

BATTERY REPLACEMENT If it is necessary to replace the battery in the solar control unit, remove the upper control unit lid (on which the display is located). After releasing the two side screws for the upper lid (each side of the control for one), slowly pull the upper lid of the control towards you and completely remove it. Upper control unit lid Screw for upper lid

Screw for upper lid

On the back of the display, in the corner of the PCB board, there is placed a battery CR 1220. After replacing the battery, the upper lid with the display must be carefully restored to the control unit (pay attention to the connector of the PCB board and motherboard) and tighten the side screws.

Battery CR1220

8

Technical instructions Cm-SOL

Control unit description

CONTROL UNIT DESCRIPTION CmSOL control unit can control solar heating up to 4 separate tanks with 1 or 2 solar collector fields and heating the first tank using conventional sources - an el. heater and up to two boilers. Control unit has 10 inputs and 8 outputs. Types of solar collectors can be chosen between flat plate and vaccum tube solar collectors. Types of tanks can be selected between DHW tank, accumulation tank, accumulation tank with built-in DHW tank and swimming pool. Hydraulic connection of the multiple tanks can be selected via pumps, 3-way zone valve and 2-way zone valve. It is possible to control the pump for heating the first tank with the next one(heating the DHW tank with the accumulation tank). The first tank can be heated by an el. heater (via contactor) and with up to 2 conventional heat sources (it is possible to choose between wood boilers, pellets, oil / gas, el. boiler or heat pumps). The control unit can control the recirculation pump with impulse operation at the set schedule time. By entering the correct flow through the solar collectors and by installing the solar collector backflow sensor, sollar controller calculate total gain energy from solar collectors. If the flow meter is installed, the calculation of the energy will be more accurate.

E= 543 (kWh)

In addition to the upper mentioned, the control unit also has protective functions: solar collector cooling function (via tank), tank cooling function (over solar collector or recirculation), disinfection function (legionela protection) and function pump/valve protection function for blocking protection. On the control unit you can determine the priority of solar heating of a single tank, switch on a tank heating priority test, switch on and off certain tank from the heating, switch on one-time heating with conventional sources, switch on party option for one-time heating extension and switch on the holiday option with which are automatically switch on all protective control unit functions to allow the overheating / freezing of the collector to be minimized. To monitor the operation of the solar system, it is possible to install a WiFi box and through the web portal monitor the individual temperatures and operation of individual pumps and valves. Through the web portal it is also possible to change the set temperatures of the tank and solar collector.

Technical instructions Cm-SOL

9

Control unit activation

CONTROL UNIT ACTIVATION After the main switch is switched on, the menu for selecting the desired language and the software version will appear. Different languages can be selected. To select the language you need to press on the display the flag of the preferred language.

Online operation monitoring and regulation control (additional equipment: Cm WiFi-box)

Software version

Page listing Language selection

If in the main menu under MENU (DISPLAY), option LANGUAGE SELECTION is set under OFF an initial message will appear (see the image below) and it will be displayed as long as it is set in the menu INITIAL MESSAGE TIME or until the button ''OK'' is pressed.

Software version

Button ’’OK’’

Countdown of the initial message duration

When switching on the main switch the display must not be pressed (finger ...). If the display switches on when the main switch is pressed (Firmware update is displayed on the screen), the control unit enters the software loading mode, which can only be used by authorized service persons. If this occurs, switch off the main switch and turn it back on again without any pressure on the display to make the control unit ready for operation.

10

Technical instructions Cm-SOL

Symbols

MAIN DISPLAY / SYMBOLS

1

2

3 4 5

6

BUF E= 543 (kWh)

7

8

Main display symbols

1 coll. field / vacuum tube coll. / 1 tank DHW / 1 ACCU tank / 3 –way zone valve / el. heater / boiler1 / mixing/reheating / flow meter / backflow sensor / outdoor temperature sensor / recirculation / internet control

1 - Display of the selected configuration 2 - Display of the system functions (switch off/on/active) 3 - WiFi Connection Status Display (additional equipment) 4 - Display of the current time and date

5 - Button 'main menu' 6 - Button ‘'shortcuts'’ 7 - Display the total gain of solar energy 8 - Display of outdoor temp (additional equipment)

A few examples of the main display with selected configurations of the solar

E= 543 (kWh)

1coll.field / flat plate coll. / 1 tank. DHW / backflow sensor / outdoor temperature sensor

BUF

E= 543 (kWh)

2 coll. fields / vaccum tube coll. / 1 tank. DHW / 1 accu tank / pump hydr.connection / reheating boiler oil/gas / recirculation DHW / flow meter / backflow sensor

Technical instructions Cm-SOL

E= 543 (kWh)

1coll.field / flat plate coll. / 4 tank. DHW / hydr. connection 2 –way zone / reheating boiler oil/gas / recirculation DHW / flow meter / backflow sensor

E= 543 (kWh)

1 coll. fields / flat plate coll. / 1 accu with DHW / swimming pool / hydr.connection 3 –way zone / reheating wood boiler / recir. DHW / flow meter / backflow sensor / outdoor temp. sensor

11

Symbols

SYMBOLS

27

26 25 24 23 22 21

20

1 2 3 4 5 6

BUF E= 543 (kWh)

7 8

9 10 11

12 13 14

Main display symbols 1 - Mark of the collector field according to the configuration (1(1/2)) 2 - Collector field 1 (vaccum tube coll. (vaccum tube/flat plate)) 3 - Tank hydraulic connection (zone 3-way (pump/ zone 2way/zone 3-way)) 4 - Mark of the tank according to the configuration (2 (1/2/3/4)) 5 - Mark of the tank priority (2 (1/2/3/4)) 6 - Collector pump (collector field 1) 7 - Flow meter (additional equipment) 8 - Collector backflow sensor 9 - Accu tank (second) 10 - Lower heat exchanger of the accumulation tank 11 - Lower temperature of the accumulation tank 12 - DHW tank (first) 13 - Lower heat exchanger of the DHW tank

15 16

17 18 19

14 - Lower temp of the DHW tank 15 - El. heater (additional equipment) 16 - Upper heat exchanger of the DHW tank 17 - Boiler pump 18 - Boiler (Pellets (Pellets/wood/gas-oil/El. boiler/HP)) 19 - Boiler temperature 20 - Recirculation 21 - Upper temperature of the DHW tank 22 - Mixing pump /reheating of the DHW tank 23 - System function - inactive (darkgreen) 24 - System function – switch on, at this moment inactive (lightgreen) 25 - System function – at this moment active (yellow) 26 - Upper temperature of the accu. tank 27 - Collectors field 1 temperature

Solar collectors 1 collector field flat plate solar collector

1 collector field vacuum tube solar collector

2 collector field vacuum tube solar collector

Tanks Tank DHW 1 Heat exchanger 2 temperatures

12

Tank DHW 2 heat exchanger 2 temperatures

Accumulation tank 1 heat exchanger 2 temperature

Accumulation tank with DHW tank 1 heat exchanger 2 temperatures

Swimming pool

Technical instructions Cm-SOL

Symbols

Hydraulic connection of the tank Hydraulic connection of the tank: Pumps

Hydraulic connection of the tank: 3-way zone valve

Hydraulic connection of the tank: 2-way zone valve

3-way zone valve: Open in L

3-way zone valve: Open in I

2-way zone valve: Open

2-way zone valve: Closed

Mixing / reheating Mixing / reheating Reheating – Pump between the accumulation tank and DHW tank for reheating of the DHW tank

Mixing / reheating REMARK: El. Heater and boiler/boilers can be configured only to 1. tank in the configuration! El. heater (in 1. tank) installed – switch on - not working schedule - table 1/2

El. heater (in 1. tank) installed – switch off schedule - off

Boiler: Pellets/chiped wood

Boiler: wood

Boiler: gas/oil

El. heater (in 1. tank) installed – switch on - working schedule - in table 1/2

Boiler: Heat pump

Boiler: El . boiler

Tank reheating: example 1 wood boiler and 1 oil/gas boiler - control unit controls only the boiler pumps, do not switch off/on the boilers!

Recirculation REMARK: Recirculation can be configured only to 1. tank in the configuration! DHW recirculation

WiFi supervision REMARK: additional equipment

Energy meter / backflow sensor REMARK: energy meter is the additional equipment Energy meter (upper symbol) Backflow meter (lower symbol)

Technical instructions Cm-SOL

Cm Wifi-box Is not connector to a router/server Cm Wifi-box Is connector to a router/server

13

Symbols

SYMBOLS OF THE SYSTEM FUNCTION

Symbols of the system function on the main display C - Cooling of the collector (2.2.Collector cooling) T - Cooling of the tank (1.7.Tank cooling) I - Pulse start of the collector/swimming pool pump (2.1.2.Pump pulse start) P - Priority test (1.6.priority test) G - Protection of the pumps/valves (3.8. Protection of the pumps/valves) R - Recirculation (3.6.Recirculation) O - One-time heating of the DHW (3.2.DHW one-time) Z - Party function (3.4.Party function) H - Holiday option (3.5.GO options) L - Tank desinfection (3.7.Legionella protection) F - Collector frost protection (2.3.frost protection) M - Manual test (3.9.Manual test) E - Reheating delay (3.3.Reheating delay)

3

2

1

1 - When none of the functions are included, the letter boxes on the main display are dark green. 2 - When a single function of the system is on, but not active, the letter box of that function on the main display is light green. 3 - When a single function of the system is on, and active, the letter box of that function on the main display is yellow.

14

Technical instructions Cm-SOL

Parameter setting

PARAMETER SETTING

A

B

C

D

E

F

There are several parameter menus for setting parameters: A- the menu is used to set parameters that have numeric values (°C, time...) example: setting of the DHW tank temperature B - the menu is used to set the parameters which need to be selected (marked) to be switched on, multiple elements can be tagged simultaneously REMARK: some of the included elements exclude others (may not be included at the same time) example:switch on the tank... C - the menu is used to set the parameters which need to be selected (marked) but only one parameter can be selected (marked) example: test priority switched off... D - the menu is used for settings the parameters which have more then one setting parameters (adjusting with the arrows) example: setting of the time and date E - the menu is used when entering file names, usernames and passwords (letters and characters) example: entering the name of the user file during the recording... F - the menu is used when setting the schedule (timers) example: setting the schedule of the pulse pump start

Technical instructions Cm-SOL

15

Parameters setting

TYPES OF PARAMETERS SETTING (EXAMPLES)

1

3

4

2

5 6

1 - setting parameters 2 -the window of the value you set 3 - set value 4 - value unit 5 - the confirmation button 6 - resets the current value to the factory set value 7- button info (shows the factory, min. and max. value)

7 1

5

6 1 - setting parameters 2 - the window of the value you set 3 - set value (only one can be set) 4 - confirmation button 5 - information on the factory value 6 - BACK button to return to the previous screen

2 3 4

1 1 - setting parameters 2 - elements that can be switched on / off 3 - marked (switched on) element 4 - confirmation button 5 - unmarked (switch off ) element

2 3

5

4

1 2 3

5

4 6

1 - setting table 2 - the day of the week for which the schedule is valid 3 - start time of switching time (green) 4 - end of switching time (red) 5 - if it is marked all day by pressing the name at the day, it is possible to copy all the switching times of that day. 6 - marking the name of the day can be pasted before copied day

IMPORTANT: After changing parameter values press the ''CONFIRMATION'' button to save a new value. If you do not want to save a new value, press the button ''BACK''.

16

Technical instructions Cm-SOL

Main Menu

MAIN MENU The main menu is used to select the desired menus. To select a particular menu, press the appropriate icon on the display. To switch between "Main Menu" and "Home screen", use the "MAIN MENU" button.

Time Date Main menu: Main menu / Home display

Shortcust: inactive

Total gain energy from solar collectors Outdoor temperature (if outdoor sensor is installed, additional equipment)

BUTTONS Button ''MAIN MENU'' options: main menu / home display

Button ''SHORTCUTS'' options: home screen / set shortcuts

Key ''OK''

Key ''START''/''STOP''

Button ’’CONFIRMATION’’

Navigation Keys: ’’LIJEVO’’, ’’DESNO’’, ’’DOLJE’’, ’’GORE’’

Key ’’BACK''

Key ’’BRISANJE’’

Key ''BACK SCREEN''

Key ’’TVORNIČKE POSTAVKE’’

Key ''NEXT SCREEN''

Key ’’INFORMACIJE’’

Key ’’COPIE’’

Key ’’ZALIJEPI’’

Technical instructions Cm-SOL

17

User menu, tank

THE NUMBERS OF MENU AND MENUS ARE CHANGING ACCORDING TO THE SELECTED CONFIGURATION (here are shown only fix numbers (which are always the same), and other changeable numbers are marked with x, menu depth where the parameter is located).

USER MENU (MAIN MENU) 1. TANK

The menu 1. Tank contains menus associated with configured tanks. Depending on the configuration, here are displayed menus for 1 to max 4 tanks. example: configuration 2 tanks, function mixing-heating

1.x DHW temperature Setting of desired DHW (domestic hot water) temperature. Conventional energy sources (el. heater, boiler1 and boiler2) heat the DHW tank to the desired DHW temperature. NOTE: DHW temperature applies only to the conventional sources. Solar collectors heat tank up to tank temperature TMAX tank. Factory settings DHW temperature

Setting of

min./max. unit. 55

10 / 85

°C

1.x. T MAX tank 1 Setting maximum tank temperature 1. Solar collectors heat tank 1 to temp. [T MAX tank 1] after which the heating of the tank 1 stops and the heat is transferred to the next tank by priority (if available). If the collector cooling function is activated, the temperature in the tank can increase to max. 90 ° C (or 95°C if the TMAX Tank 1 is set at 90°C). 1.x. T MAX tank 2 Set maximum tank temperature 2. Solar Collectors Heat Tank 2 to Temp. [T MAX Tank 2] after which the the heating of the tank 2 stops and the heat transfer to the next container by priority (if available). If the active cooling function of the collector is also activated, the temperature in the tank can increase to max. 90°C (or 95°C if the TMAX tank is set to 90 ° C. Factory settings

min./max. unit.

T MAX tank 1

70

30 / 90

°C

T MAX tank 2

70

30 / 90

°C

T MAX tank3

70

30 / 90

°C

T MAX tank 4

70

30 / 90

°C

If the last tank in configuration is swimming pool, the max. swimming pool temperature can be adjusted in the following range: Factory settings T MAX tank X

18

min./max. unit. 28

15 / 40

°C

Technical instructions Cm-SOL

User menu, tank 1.x. Enabled tanks In this menu, you can switch on/off the individual tank in operation of the system. SWITCH ON - the tank is included in the system. SWITCH OFF - the tank is switched off from the system (no pump or valve is used, nor does it heat up). NOTE: If all tanks are switched off on the control unit, a warning will appear! (solar collectors do not fill any of the tank fast boiling in the collector).

Example:configuration 2 tanks

Factory settings

selection

Tank 1

Switch on

ON/OFF

Tank 2

Switch on

ON/OFF

Tank 3

Switch on

ON/OFF

Tank 4

Switch on

ON/OFF

1.x. Tank priority Selection of the priority for solar tank filling. Tank 1 must always be the first priority, the other tanks can rotate at the priority of the charge. The priority of each tank is indicated in the upper left corner of the tank (green number), below the row number of the tank (black number). Factory settings

Example:configuration 3 tanks

selection

2 tank

12

12

3 tank

123

123 / 132

4 tank

1234

1234/1243/1324/1342/1423/1432

1.x. Priority test If there are more than one tank in the configuration, the tank priority test may be switch on to periodically examine whether the collector temperature is high enough to refill the priority tank.

P P P

After the priority tank is filled (or [T MAX tank1] or [Tcoll
Factory settings Test priority

selection OFF

OFF/ON

1.7. Filling priority Priority test -> Switch on Continuous filling time of the next tank in order (non-priority tank). Factory settings Filling priority

Technical instructions Cm-SOL

min./max. unit. 15

0 / 720

min

19

User menu, tank 1.x. STAND BY PRIORITY Test priority -> Switch on The collector pump stand by time during which the temperature rise of the collector is tested in order to return collector heating to the priority tank. If the temperature increase in the set stand by time is greater than or equal to [3°C / x min], the stand by time is extended for the next interval, which again looks at the increase in the temperature of the collector and the possibility of filling the priority tank. If the temperature rise in the set stand by time is less than [3°C / x min], filling the current tank continues Factory settings Stand by priority

min./max. unit. 3

0 / 60

min

1.x. Tank cooling Cooling the tank, ie lowering the water temperature in tanks to prepare the tank for accepting the new solar energy the next day, can be done over the collector or through recirculation (if it is installed in the system and connected to the controller). NOTE: Cooling of the tank always start from the lowest priority to the tank with the highest priority. Tanks must have upper tank sensor. Collectors - Cooling the tank via the collector (and pipes to the collector).

T T T TIP: If you want to cool the tanks to leave more space for solar energy for the next day, it is recommended to enable the Tank Cooling function together with Collector Cooling function and lower the [TMAX tank] down (ca. 50°C). When the tanks are filled up to [TMAX tank] the collectors wil reach the cooling point faster (adjust according to the number of collectors, not to pass TMAX coll), the temperature in the tanks will start to rise up to 90°C, but after that will start tank cooling which will try to cool tanks down to [TMAX tank-dTcoll/tank] (ca. 50-4= 46°C).

NOTE: It is recommended to cool the tank with flat plate collectors (not vaccum tube) because of less insulation on flat plate collectors. Cooling takes place when the temperature in the collectors is lower than the temperature in the tank down [Tcoll. + dTcoll. / tank. T MAX is tank.1] (only runs on the first tank). Cooling of the tank stops when the temperature of the upper sensor drops below the diference collector / tank [Ttank_upper
OFF

Off/Collectors/Recirculation/Call-Rec

1.X. Mixing-reheating If in the mixing-heating of the tank is switch on the mixing-reheating pump can be switched on or off. If the function is switched on, when the temperature of the first tank (upper sensor) is lower for the differential setting than the second tank (upper sensor), the mixing / reheating pump is switched on to heat the first tank (this function is usually used when the first tank is DHW tank and the second ACCU , when the excess energy is stored in the ACCU during the day, and in the evening, after the consumption, the DHW tank may additionally be heated). example: configuration 2 tanks, hyd. connection: - Zones 3-Way, Mixing / Reheating

NOTE: need to be switch on in the Installation menu.

selection

Factory settings Mixing-reheating.

20

OFF

ON/OFF

Technical instructions Cm-SOL

User menu, sollar collector

2. COLLECTOR

In menu 2.Collectors, there are menus associated with configured collector fields. Depending on the configuration, menus for 1 to max. 2 collector fields are displayed here example: configurated 2 collector fields 2.1. Collector 1 Menu 2.1, Collector 1 contains menus for setting the parameters for the 1st Collector field.

2.1.1. T MAX COLLECTOR1 Settin of maximum collector temperature 1. The solar collector field 1 pump runs to the temperature in the collectors [T MAX collector 1] after which it goes off (to protect the armature from excessive temperature due to steam in the collectors and the inability to operate the pump until the temperature in the collectors drops below the set max. collector). When the temperature in the collectors drops below [T MAX Collector1 4°C], the Collector Field 1 pump again starts working if other conditions are met. NOTE: [T MAX collector] it is necessary to adjust to the point of solar fluid boiling in the solar system and always be lower than the boiling point. Factory settings T MAX collector 1

I

Technical instructions Cm-SOL

I

I

min./max. unit. 140

30 / 150

°C

2.1.2.Pulse collector start In the menu 2.1.2. Pulse collector start contains the menus for adjusting the parameters for the pulse start pump (kick) of the collector field 1. If the collector sensor is not mounted in the collector (but it is set somewhere on the flow pipe) or has more than one collector in the same field, it is recommended to switch on the impulse collector start which, if the pump collector pauses, occasionally starts collector pump at a specified time to obtain a more accurate current temperature solar fluid on the collector sensor. NOTE: excessive and long-lasting pump operation can be tank unnecessarily cooled down the tank. Pump working time and stop depends on the size and location of the collector field and the collector sensor.

21

User menu, solar collector 2.1.2.1. Pulse collector start In this menu, the pulse start function can be on or off. All pre-set times as well as switching times remains. selection

Factory settings Pulse coll. start

OFF

ON/OFF.

2.1.2.2. Pump work time Setting of the working time of the pump at pulse start. NOTE: Time has to be adapted to the size and location of the collector field and collector sensor to obtain the correct collector temperature.

Factory settings Operation pump time

min./max. unit. 10

0 / 3600 sec

2.1.2.3. Pump pause time Setting of the pause time of the pump in the pulse start. NOTE: Time has to be adapted to the size and location of the collector field and collector sensor to obtain the correct collector temperature.

Factory settings Pump pause time

min./max. unit. 15

0 / 1440 min

2.1.2.4.Schedule In this menu there are menus related to adjusting the schedule for the pulse start of the pump (kick) of the collector field 1. The schedule can be switched off or one of two tables can be set with the set intervals of the active and inactive function

2.1.2.4.1.Schedule In this menu, you can switch on / off the schedule and select one of the two tables that will operate on the pulse start pumps. NOTE: If the pulse collector start is switched on, and the switch-off time is off, the pulse start will run non-stop (24/7) at start / stop times. In such a case, the pulse start will also work overnight and there is a possibility of cooling the tank over the collector. selection

Factory settings Switching time

Table1

OFF/Table1/Table2

2.1.2.4.2.Table 1 In this menu, you can set 3 time intervals (3 start and 3 stop) for each day of the week in which the pump will operate according to the set pulse start. Factory setting: Pulse start pump is active from 08:00 to 17:00 every day of the week. From 17:00 h the first day until 08:00 h the next day the pulse start does not operate. Factory settings Table 1

22

selection

08:00-17:00 mon/tue/wed/thu/fri/sat/sun

Technical instructions Cm-SOL

User menu, sollar collector 2.1.2.4.3.Table 2 In this menu, you can set 3 time intervals (3 start and 3 stop) for each day of the week in which the pump will operate according to the set pulse start. Factory setting: Pulse start pump is active from 08:00 to 17:00 every day of the week. From 17.00 h the first day until 08.00 h next day pulse start is not operational. selection

Factory settings Table 2

08:00-17:00 mon/tue/wed/thu/fri/sat/sun

2.x. Collector 2 In Menu 2.2, Collector 2 contains menus for setting parameters for the 2nd Collector field. The menus are identical to that of Collector 1 (for details, see descriptions for 2.1.Collector 1).

C C C

2.x.Collector cooling In this menu, the collector cooling function (over the tank) can be switched on or off (tanks must have upper sensor). With this function we want to delay boiling of the solar fluid in collectors, by raising the temperature in the tanks to the maximum temperature [T MAX tank= 90°C]. The collector cooling function starts if the temperature in the collectors reaches [T MAX collector - d TCooling_collector] and if all tanks are full, to [T MAX tank(set)]. [Tcoll. > T MAX coll. - dTCooling_collector.] Collector cooling stops if the coil collector crosses [T MAX collector] or when the temperature drops in the collectors below [Tcoll
F F F

selection OFF

ON/OFF

2.x. Frost protection In this menu, you can switch the collector freezing function on or off. Use this function when in the solar water system is water (instead of solar fluid) and if the outer temperatures do not drop below zero. In the solar system it is always recommended to use a mixture of glycol and water (solar antifreeze with water). The frost collector protection function causes the circulation of water through the collectors to prevent the freezing with help of heat energy from the tank. The frost protection drops when the temperature in the collectors falls to the set temperature under PIN code (factory setting + 4°C). The frost protection starts when the temperature in the collectors rises by + 2°C of the set temperature [Tstart] and when the temperature in the tank lower drops down to + 3°C (to prevent freezing of the tank). Frost protection starts from the least priority tank to a tank of higher priority. NOTE: Only use this function when only water is in the collectors. It is never recommended to fill the solar system with water only (without glycol)! By switching on the frost protection function, it is possible to coll the tanks. Possible significant energy consumption of conventional sources in heating tank due to "heating" the collector! Factory settings Frost protection

Technical instructions Cm-SOL

selection OFF

ON/OFF

23

User menu, operation

3. OPERATION

In the menu 3. Operation you can find the menus connected with the solar system functions, manual test, and if present, the internet supervision. 3.1. DHW heating In this menu you can find the menus connected with the parameter setting of the configurated DHW heating (tank). Under the PIN for the DHW heating it is possible to configure one electric heater and maximum 2 conventional sources (under PIN it is possible to select for screen display following: wood boiler, pellet boiler, oil/gas boiler, heat pump and electric boiler). It is possible to switch on/off (needs to be configurated in the installation menu) the reheating delay. Example: configuration of 1 electric heater and 1 conventional source 3.x.x. Electric heater In this menu you can find the menus connected with the electric heater parameter settings in the first tank. NOTE: needs to be switched on in the installation menu. The electric heater is connected on the controller's exit always through a contactor. For electric heater work OBLIGATORY define switch ON schedule.

3.x.x.1.Electric heater In this menu it is possible to switch on/off the electric heater operation for the reheating of the tank. In case the electric heater is switched off, schedule off, the symbol of the electric heater in the tank is crossed. In case the electric heater is switched on, schedule table 1/2 and not active, the symbol of the electric heater has a grey colour. In case the electric heater is switched on, in schedule table 1/2 and active, the symbol of the electric heater in the tank has a red colour and blinks. Factory settings Electric heater

24

selection OFF

ON/OFF

Technical instructions Cm-SOL

User menu, operation 3.x.x.2 Schedule In this menu you can find the menus connected with the schedule (switching time ) for the electric heater operation. The schedule can be switched off or one of two tables can be selected with the set time intervals of the active and inactive function. NOTE: Considering that the electric heater for the tank reheating consumpts an expensive energy – electricity – it is necessary after the electric heater switches on, to define the schedule, with which we define the time of the desired tank reheating by the electric heater. 3.x.x.2.1.Schedule In this menu it is possible to switch on/off the switching time and to select one of two tables according to which the electric heater will be switched on and active when needed (for example, first table can be used for the everyday use of the electric heater, the other over holidays). NOTE: If the electric heater is switched on and the Schedule (switching time) turned off, the electric heater will NOT operate. For the electric heater operation it is obligatory to select one of the two tables and set the switching time (in some countries night/second electricity tariff is much cheaper than the daily one). selection

Factory settings Schedule

OFF

OFF/ Table 1/ Table 2

3.x.x.2.2.Table 1 In this menu it is possible to set 3 time intervals (3 start (green field) and 3 stop (red field)) for each day in the week in which the reheating by the electric heater will be able to operate according to the set temperatures. Factory setting: the conventional source is enabled from 06:00 until 22:00 each day in the week. From 22:00 first day until 06:00 next day the reheating by the conventional source cannot operate. Factory settings Table 1

selection

06:00-22:00 mon/tue/wed/thu/fri/sat/sun

3.x.x.2.3.Table 2 In this menu it is possible to set 3 time intervals (3 start (green field) i 3 stop (red field)) for each day in the week in which the electric heater will be able to operate according to the set temperatures. Factory setting: the electric heater is enabled for operation from 06.00 to 22.00 hours each day in the week. From 22.00 hours first day until 06.00 hours next day the electric heater cannot operate. Factory settings Table

Technical instructions Cm-SOL

selection

06:00-22:00 mon/tue/wed/thu/fri/sat/sun

25

User menu, operation 3.x.x. Boiler 1 In this menu you can find the menus connected with the parameter settings for the reheating by a conventional source 1 of the first tank. NOTE: it is necessary to switch it on in the installation menu. 3.x.x.1. Boiler 1 In this menu the reheating of the conventional source 1 can be switched on or off (ie the operation of the pump between the conventional source 1 and tank 1 ). Factory settings Boiler 1

selection OFF

ON/OFF

3.x.x.2.Schedule In this menu you can find the menus connected for the schedule setting for the reheating operation through the conventional source 1. NOTE: In case the schedule is not switched on when we would like the reheating by help of the conventional source to operate and when not, the conventional source pump will operate according to the set temperatures the entire time, 24/7.The recommendation is to switch on and set the schedule in order to optimize the energy consumption according to the real needs for hot water. 3.x.x.2.1.Schedule In this menu it is possible to switch on/ off the schedule and to select one or two tables according to which the tank reheating by the conventional source 1 will operate. NOTE: If the conventional source iz switched on, and the schedule is switched off, the reheating of the tank by the conventional source will be done according to the set temperature the entire time, 24/7. selection

Factory settings Schedule

OFF

OFF/Table1/Table2

3.x.x.2.2.Table 1 In this menu it is possible to set 3 time intervals ( 3 start ( green field ) and 3 stop (red field)) for each day in the week in which the reheating by the conventional source will be able to operate according to the set temperatures. Factory setting: the conventional source is enabled from 06:00 until 22:00 each day in the week. From 22:00 first day until 06:00 next day the reheating by the conventional source cannot operate. Factory settings Table1

selection

06:00-22:00 mon/tue/wed/thu/fri/sat/sun

3.x.x.2.3.Table 2 In this menu it is possible to set 3 time intervals (3 start (green field) and 3 stop (red field)) for each day in the week in which the reheating by the conventional source will be able to operate according to the set temperatures. Factory setting: the conventional source is enabled from 06:00 to 22:00 hours each day in the week. From 22:00 first day until 06:00 next day the reheating by the conventional source cannot operate. Factory settings Table 1

selection

06:00-22:00 mon/tue/wed/thu/fri/sat/sun

3.x.x. Boiler 2 The menus for the setting of the conventional source 2. All menus are the same as for the conventional source 1 and will not be separately described.

26

Technical instructions Cm-SOL

User menu, operation

E E E

3.1.3. Heating delay For the appearance of this menu the reheating with at least one of the conventional sources must be defined and in the installation menu the heating delay must be switched on and configurated. If the function is switched on and the solar collector pump is active (it means that the tank is reheated by solar energy) this function decreases the actuation temperature of the reheating by the conventional source (it delays the start of the reheating by the conventional source) for the value set under PIN in the menu Temperature decrease. If the solar collector pump is active, the delay of the reheating start: [Ttank_up1 <=TDHW-dTboiler_tank-Ttemp. decrease] If the solar collector pump is not active and needs to reheat the tank, the delay of the reheating is not taken into consideration: [Ttank_up1 <=TDHW – dTboiler_tank] NOTE: It is needed to swith it on in the installation menu. selection

Factory settings Heating delay

OFF

Factory settings

In the installation menu:

Temp. decrease

ON/OFF

min./max. jed. 0

0 / 90

°C

3.x. DHW one – time By selecting the conventional source from this menu (one or more of them together if existing) the DHW is reheated one-time until the set temeperature (either in the set time or outside of it). After the end of reheating option DHW one – time is automatically switched off . NOTE: Conventional sources must be switched on (in their menus) by which the DHW reheating would like to be done. Example: configurated 1 electric heater and 1 conventional source

O O O

selection

Factory settings DHW one – time

OFF

Electric heater/boiler 1/boiler 2

3.x. Party function Party function enables the DHW heating by switched on conventional sources a certain selected time (independent on schedual). After the end completion of the selected time Party function, the options switches off automatically.

Z Z Z

3.x.1. Party function By switching on this option the DHW is reheated until the set DHW tank temperature by switching on the conventional sources a certain time, which is selected in the menu Duration. After the expiration of the selected time the Party function automatically switches off. Factory settings Party function

Technical instructions Cm-SOL

selection OFF

ON/OFF

27

User menu, operation 3.x.2. Duration In this menu is defined how long from the moment of the Party function actuation the DHW reheating will last according to the set temperature. After the expiry of the selected time the Party function automatically switches off. Factory settings Duration

selection unit. 1

1 / 3 / 6 / 12 h

3.x. Holiday option The holiday option includes system safety functions to postpone as long as possible the appearance of steam in the solar collectors and to prevent the pump and valves blockage due to very little or none water consumption. By the actuation of the Holiday option the tank and collector cooling function is activated aswell the pump/valve safety function and frost protection of the water in the collectors. If it is not wished to activate all before mentioned functions at once, the Holiday option must be switched off and the individual wished safety functions need to be activated manualy.

H H H

Factory settings Holiday option

unit. OFF

ON/OFF

3.x. Recirculation In this menu you can find the menus connected with the setting of the DHW recirculation operation parameters. In this menus you can set the time of work and pause of the recirculation pump and define the time interval in which the operation and inactivity time of the pump will be active. NOTE: It is necessary to switch it on in the installation menu.

R R R

3.x.1. Recirculation In this menu the recirculation function can be switched on or off. All preset times aswell the schedule remain as adjusted. unit.

Factory settings Recirculation

OFF

ON/OFF

3.x.2.Pump working time Adjusting the pump working time when the recirculation is active. NOTE: The time must be adjusted to the recirculation system. The recommendation is to set the recirculation pump work as short as possible in order to cooldown the DHW tank as less as possible. Factory settings Pump working

min./max. jed. 5

1 / 1440 min

3.x.3. Pump pause time Adjusting the pump pause time when the recirculation is active. NOTE: Time must be adjusted to the recirculation system. The recommendation is to set the recirculation pump pause as long as possible in order to avoid to cooldown the DHW tank. Factory settings Pump pause time

28

min./max. jed. 15

0 / 1440 min

Technical instructions Cm-SOL

User menu, operation 3.x.4. Schedule In this menu you can find the menus connected with the schedule setting for the recirculation. The schedule time can be switched off or one or two tables selected with the set time intervals of the active and inactive function.

3.x.4.1. Schedule In this menu it is possible to switch on/off the schedule and select one or two tables according to which the DHW recirculation will operate. NOTE: If the recirculation is switched on, and the schedule is switched off, the recirculation will operate according to the set time non – stop (24/7), ie the recirculation pump will operate also in the time when it is not needed and will unnecessarily cooldown the DHW tank. Factory settings Schedule

selection ON

OFF/Table1/Table2

3.x.4.2. Table 1 In this menu it is possible to set 3 time intervals [3 start (green field) and 3 stop (red field)) for each day in the week in which the pump will work according to the set work/pause time. Factory settings: the recirculation is enabled from 06:00 until 22:00 hours each day in the week. From 22:00 hours first day until 06:00 hours next day the recirculation does not operate. Factory settings Table 1

selection

06:00-22:00 mon/tue/wed/thu/fri/sat/sun

3.x.4.3. Table 2 In this menu it is possible to set 3 time intervals [3 start (green field) and 3 stop (red field)) for each day in the week in which the pump will work according to the set work/pause time. Factory settings: the recirculation is enabled from 06:00 until 22:00 hours each day in the week. From 22:00 hours first day until 06:00 hours next day the recirculation does not operate. Factory settings Table 2

selection

06:00-22:00 mon/tue/wed/thu/fri/sat/sun

3.x. Legionella protection In this menu you can find the menus connected with the tank disinfection function settings ie the legionella protection.

L L L Technical instructions Cm-SOL

29

User menu, operation 3.x.1. Legionella protection In this menu the legionella protection function can be switch on or off. All preset times aswell the schedule and temperatures remain as adjusted. selection

Factory settings Legionella protection

OFF

ON./OFF.

3.x.2. Protection temperature The Legionella bacteria lives and develops itself in the areas with weak or none circulation at the temperature between 20°C and 55 °C. On higher temperatures the bacteria dies slowly, while above 70°C the bacteria instantly dies. In order to have an efficient bacteria appearance protection, the tanks and piping must be kept a certain time above 65°C to have an efficient disinfection. Factory settings Protection temp.

min./max. jed. 70

60 / 90

°C

3.x.3. Schedule In this menu you can find the menus connected with the setting of the switching time for the legionella protection. The schedule can be switched off or one or two tables can be selected with the preset time intervals of the active and inactive function. 3.x.2.1. Schedule In this menu it is possible to switch on/off the schedule and to select one or two tables according to which the legionella protection will be switched on. NOTE: If the schedule is switched off the legionella protection will not operate until one of the tables with the set time is selected. Factory settings Schedule

selection Table 1

OFF/Table1/Table2

3.x.3.2. Table 1 In this menu it is possible to set 3 time intervals (3 start (green field) and 3 stop (red field)) for each day in the week on which the legionella protection will be switched on. Factory settings: Legionella protection is active one day in the in the week (on Monday) from 02:00 until 03:00 hours. Factory settings Table 1

02:00-03:00

selection pon

3.x.3.3. Table 2 In this menu it is possible to set 3 time intervals (3 start (green field) and 3 stop (red field)) for each day in the week in which the legionella protection will be switched on. Factory settings: Legionella protection is active one day in the in the week (on Monday) from 02:00 until 03:00 hours. Factory settings Table 2

30

02:00-03:00

selection pon

Technical instructions Cm-SOL

User menu, operation 3.x.4. Choose source (source selection) In this menu it is possible to select the conventional source with which we would like to disinfect the tank according to the schedule and set temperature. The selected source must be able to reach the set temperature at the choosen time (in the menu only the configurated conventional sources are listed). Factory settings

selection

Choose source Electric heater Electric heater/Boiler1/Boiler 2

primjer: konfigurirano 3 konvencionalna izvora 3.x.5. Skip legionella time In this menu it is possible to switch on or off the skip legionella time function for the Legionella protection. If the function is switched on, and in the time interval between two activation terms of the tank protection, the set temperature and the desinfection time duration is reached, when the next activation term for the protection arrives, the controller skips it and waits for the next term. Factory settings Skip legionella time

selection OFF

ON/OFF

3.x.6. Disinfection duration Setting of time in which the water temperature on the upper sensor in the tank must be above the set protection temperature in order to consider that the disinfection was successfully performed. Factory settings Disinfection duration

min./max. jed. 15

1 / 1440 min

3.x.7. Legionella recirculation In this menu it is possible to switch on and off the recirculation operation when the Legionella protection is active in order to disinfect the piping (the condition is that the recirculation is configurated in the system). When the conventional source starts up, also the recirculation pump switches on, and operates for as long as the disinfection time is set. NOTE: The recirculation must exist and it is needed to switch it on in the installation menu. Factory settings Legionella recirc.

selection OFF

ON./OFF

3.x. Pump/valve protection The pump/valve protection follows the activity of the individual output (pump or valve) as due to a long – term inactivity the pump/valve would not block. By setting the off inaction time (in the installation menu) it is possible to determine the maximum inaction time of the output, after which the controller activates the output for 60 seconds. selection

Factory settings Pump/valve protection

OFF

ON/OFF

G G G Technical instructions Cm-SOL

31

User menu, operation 3.x. Manual test Depending on the configurated system components and its outputs, during the manual test it is possible to test all turned on outputs. NOTE: Number and type of menu depends on the turned on exits in the installation menu. If there are PWM outputs, in manual tests you can set wanted speed of each PWM output (factory on 100%).

Example: configurated 2 tanks with PWM pumps, 1 conventional source, 1 electric heater, recirculation pump and mixing pump

M M M 3.x.1. Manual test pump S1 By pressing the button START the output is turned on (in this case the tank 1 pumps) and by pressing the key STOP the output is turned off (in this case the tank 1 pump). With the button RETURN it returns the previous screen. When the Manual test is switched on, the marking of the Manual test (M) function lights yellow.

1 solar flat collector field / vacuum tube collector / 1 DHW tank / 1 buffer tank / pumps / electric heater / boiler 1 / mixing/reheating / flow meter / return sensor / outer temperature sensor / recirculation

Depending on the selected output, with the buttons START and STOP the individual outputs are manualy switched on or off.

3.x. Internet supervision If the CM – WiFi BOX is embedded, the controller automatically recognizes the device and under the user and PIN the menu Internet supervision appears. In this menu it is possible to switch on/off the supervision or the supervision and control via the WiFi network, enter the name of the WiFi network and the password, make the time synchronization , select the time zone and do the manual reset of the connection. The user can adjust and commission the WiFi Box by him/herself.

3.x.1. Internet supervision In this menu it is possible to switch on and off the Internet supervision and to choose only Supervision (it is not possible to change the parameters) or Supervision and control (possible to change the parameters). Factory settings Internet supervision

32

selection

Sup.+control. OFF/Supervision/Sup.+control

Technical instructions Cm-SOL

User menu, operation 3.x.2. WiFi network name In this menu the name of the WiFi network is entered on which the WiFi Box is connected. It is possible to enter 31 signs, with big/small letters, numbers and signs. REMARK: It is obligatory to enter the correct network name by respecting the big and small letters and other signs.

3.x.2. WiFi password In this menu WiFi password to which Cm WiFi-box will connect must be entered. Possible is to enter 31 characters, with upper and lower case, numbers and symbols. NOTE: Insert correct network password paying attention to the upper and lower case, numbers and symbols. 3.x.4. Time synchronization In this menu the controller time synchronization is enabled with the server. Factory settings Time synchr.

selection ON

ON/OFF

3.x.5. Time zone In this menu it is possible to change the time zone where the boiler is installed. min./max. jed.

Factory settings Time Zone

1h

-12 / 14

h

3.x.6. Connection reset In this menu it is possible to manualy reset the Internet connection. If the sending of data to the web server is blocked, it is possible to manualy reset connection.

Cm WiFi – box requires an active DHCP access point server (for instance router, access point) as the the manual adjusting of the network parameters is not possible. For additional information please contact the local network administrator.

For detailed adjustment of the Cm WiFi – box please look into the technical manual for the Cm WiFi – box delivered together with the device.

Technical instructions Cm-SOL

33

User menu, history

4. HISTORY

4. History In the menu 4. History you can find information about the history of error and warnings. After the 50th written item the oldest one will be erased when a new one appears. The history of errors/warnings/ cannot be erased.

1

3

2

You can find the list of all codes and error names at the end of this instructions.

3

1

2

3 3

4.1. Errors In this menu it is possible to view/browse history of errors (E) in the system – time of emergence, code and the name of the emerged error. 1 - error code 2 - error name 3 - error date and time of emergence

4.2. Warnings In this menu it is possible to browse the warnings (W) and information (IW) in the system – time of emergence, code and name of warning/information. 1 -warning/information code 2 - warning/information name 3 - warning/information date and time of emergence You can find the list of all codes and warning/information names at the end of this instructions. By pressing the error/warning/information it is possible to read the cause and the possibility how to remove the error or warning.

5. DISPLAY

5. Display In the menu 5. Display it is possible to set the functions connected with the screensaver, language selection, initial message time, date and time and the volume and type of sound 5.1. Screensaver Time after which the screensaver appears to avoid a display damage due to a long – time presence of the same image. By pressing the display or by appearance of an „Error „ or „ Warning „ the screen saver switches off until the end of the next recorded time or until the error/warning is confirmed. Factory settings Screensaver

34

min./max. unit. 600

10 / 43200 sec

Technical instructions Cm-SOL

User menu, history 5.2. Language selection In this menu it is enabled or disabled to display the initial screen with the language selection when pressing the main switch. In case you select „Switched off„ , after pressing the main switch the controller will turn on with the previous set language and after a certain time of „initial message time „ the main screen will appear. NOTE: It is obligatory after the language selection to switch off the „ Language selection „to enable the controller to start up automatically after the arrival of electricity. If the „Language selection„ is not switched off, after the electricity arrival the controller/regulation will wait for someone to select the desired language in order that the main screen and possible errors appear. Factory settings Language selection

selection ON

ON/OFF

5.3. Initial message time Setting of initial message duration which appear after switching on the main switch. Time is running only if the „ Language selection „ is set on „ OFF„ . Factory settings Language selection

min./max. unit. 5

0 / 20

sec

5.4. Date and time: Current date and time settings. NOTE: If the date and time is not correct, the schedule time will not work properly. If the clock starts to be late or it resets on 00:00 and the date on 01.01.2000 it is necessary to replace the battery in the controller display (CR1220) (see chapter battery replacement).

5.5. Sound volume: Setting one out of 3 sound volumes by pressing the display or a complete volume switch off. Factory settings Sound volume

selection 2

OFF/1...3

5.6. Sound type: Selecting on out of 10 possible sound types which are heard when pressing the display. Factory settings Sound type

Technical instructions Cm-SOL

selection Type 3

Type 1...Type 10

35

User menu, save/load

6. SAVE/ LOAD

6. Save/Load In this menu you can find the menus connected with the saving and loading of changed settings. 6.1. Save Saving of current user's files (settings). It is possible to save it under a new name or under the existing one. The file names can contain big and small letters, numbers and signs until the max. length of 24 signs. The selection of big/small letters/signs is done by pressing the button with the arrow (on the keyboard the upper right corner).

6.2. Load Loading of saved user's files (settings).

6.3. Load service Loading of files saved under PIN (serviceman files). 6.4. Delete Deletion of previous saved files. The serviceman files is possible to delete only under PIN.

36

Technical instructions Cm-SOL

User menu, info

7. INFO

7. Info In this menu you can find the menus connected with the system info and software. 7.1. Statistics In this menu you can find the menus connected for the display of the solar system statistical data.

7.1.1. Numerical display Here is displayed the statistics of work of a single output (in minutes of operation) and the total collected energy (in kWh/MWh) are shown.

7.1.2. Display graphs The menus connected with the display of graphical statistical data. Graphs connected with the collected energy (in 12 months) and the temperature diagrams (24 h and 48 h).

7.1.2.1. Energy graphs Menus connected with the display of the graph of collected energy. If the columns do not fit into the visible chart surface/area , by help of the multiplier it is possible to reduce or increase the chart surface. The collected energy can be viewed per month within a year. 7.1.2.1.1. Multiplier If the columns of the collected energy do not fit into the visible chart surface, by help of the multiplier it is possible to reduce or increase the chart area ( x1,x2,x3,x5,x10) (multiplication of the axes with the energy). 7.1.2.1.2. 12 months energy As the solar energy is collected the chart is drawn automatically in the month in which we are currently present. On the display it is always possible to see the collected solar energy in the interval of one year in periods of one month.

Technical instructions Cm-SOL

37

User menu, info 7.1.2.2. Temperatures Menus connected with the display of the graph obtained temperatures from the configurated sensors. 7.1.2.2.1. 24h temperatures The temperature diagram from the configurated sensors in a time span of 24 hours. 7.1.2.2.2. 48h temperatures The temperature diagram from the configurated sensors in a time span of 48 hours. 7.2. Software version Software version and WiFi box identification number: - current software version loaded in the controller - if connected, WiFi ID (identification number)

7.3. Current configuration Selected system configuration. 1. K x - number of boilers (0, 1, 2) 2. C x - number of collector fields (1, 2) 3. S x - number of tanks (1, 2, 3, 4) 4. B x - number of swimming pools (0, 1) 5. H x - hydraulic connection (1(pump), 2 (2 way zone valve), 3 (3 way zone valve)) Example: configurated: 1 boiler, 1 collector circuit, 2 tanks, 1 swimming pool, hydraulic connection – 2 way zone valve 7.4. Current file Current selected file under which the controller is operating.It is possible to select the file which is saved under the basic menu (user) or a file saved under PIN ( serviceman ).

8.9.5. Last change of glycol Depending on the solar system operation and the recommendation of the glycol manufacturer, the glycol in the solar system must be regularly replaced (due to often glycol overheating (steam in the collectors) glycol ages faster and thickens which lowers the solar collector efficiency and finaly can lead to solar colletor stoppage).The recommendation is to replace glycol every 2 years. After the glycol replacement in the solar installation you need to reset the counter in the menu 8.12.2. Reset glycol counter, by help of which a new time counting of 2 years will start and after which a warning appears for the replacement of glycol in the solar system. NOTE: The warning for the glycol replacement appears after the expiry of 2 years from the last reset of the glycol counter. After the appearance of the warning the solar system continuous normally with the operation, only the warning is active that long until the counter is annulled. The annulment of the counter warning for the glycol replacement can be found in the installation menu -> 8.12.2 Reset glycol counter.

38

Technical instructions Cm-SOL

Installation

SETTING OF PARAMETERS UNDER PIN (SYSTEM CONFIGURATION)

Technical instructions Cm-SOL

39

Installation

MENUS FOR THE SYSTEM CONFIGURATION 8. INSTALLATION

By pressing the key 8. Installation you enter the menus designed for the solar system configuration. To enter the menu it is needed to write the PIN (0000) (which cannot be changed), to prevent the entering into this menu accidently.

In the menu 8. Installation the individual system components are set (it is not intended for everyday use). Menus: 1. System components - selection of existing components in the system and output configuration 2. Solar collector - parameter setting of selected solar collector fields 3. Tank – parameter setting of selected tanks 4. Tank reheating - parameter setting of selected conventional sources for the tank reheating 5. Recirculation - recirculation parameter setting in case of its existence 6. Legionella protection - parameter settings for the tank disinfection ie legionella protection 7. Energy measuring - parameter setting connected with the solar fluid and the flow through the solar collectors 8. Manual test - testing of the operation of every individual component connected with the controller 9. Save/Load - saving/deleting/loading the controller settings and returning the controller to factory settings 10. Information - Browsing the error history , software version and the records of the enterings into the installation menu 11. Internet supervision - WiFi network parameter settings for the controller connection with the Internet 12. Reset counters - the return of the energy and glycol counter to zero ( 0 )

THE NUMBERS OF MENU AND MENUS ARE CHANGING ACCORDING TO THE SELECTED CONFIGURATION (here are shown only fix numbers (which are always the same), and other changeable numbers are marked with x, menu depth where the parameter is located).

40

Technical instructions Cm-SOL

Installation, system components

8.1. SYSTEM COMPONENTS

8.1. System components In the menu 8.1. System components you can find the menus connected with the selection of the existing components in the system and the configuration of the individual controller outputs.

8.1.1. Collectors In this menu you can find the menus connected with the selection of the number of the solar collector fields and the type of the installed solar collectors.

one field

two fields

8.1.1.1. Collector fields In this menu it is necessary to select the number of the solar collector fields (the solar collector field is a set of collectors connected in one system with one solar collector pump).Two solar collector fields are usually installed as one on the east part and one on the west part of the roof and each field is separately connected with the tank with its solar collector pump. Factory settings Collector fields

One field

selection One field / Two fields

8.1.1.2. Field type In this menu it is necessary to select the type of used collectors in the solar collector field. It is always possible to select only one type of collectors, whether one or two solar collector fields were selected. The selection of the solar collectors only serves for the graphical display of the solar collectors on the screen. Factory settings

Field type

Vacuum tube collector

Vacuum tube

selection Vacuum tube/Flat plate

flat plate collector

Technical instructions Cm-SOL

41

Installation, system components 8.1.2. Tanks In this menu you can find the menus connected with the selection of the number and type of installed tanks and the selection of their connection (with collectors and mutually). It is possible to configure up to 4 tanks. It is possible to select one of three hydraulic connection. It is possible to select mutual reheating of the first 2 tanks (reheating of the DHW tank with the buffer tank).

8.1.2.1. Tank 1 , type In this menu it is necessary to select the type of the installed tank (1 – 4). Tank 1 must always exist. The types of tanks can be DHW tank, buffer tank (BUF), buffer tank with DHW tank (BUF with DHW) or pool (Pool). Only with the Tank 1 it is possible to configure reheating with conventional sources and the recirculation of DHW. If conventional sources are configured (boiler 1,2 or electric heater), the installation of the upper sensor in the Tank 1 is obligatory. If the upper sensor in the Tank 1 is not installed, the conventional sources cannot be included into the tank reheating. The solar collector pump operates according to the temperature difference of the lower tank sensor and the solar collector sensor. If the pool is configured as a tank, the pool sensor is configured as the upper tank sensor and the solar collector pump operates according to the temeperature difference between the upper tank sensor (pool) and solar collector sensor. The pool must always be configurated only as the last tank (it is not possible to choose it between two tanks), as the tank 1, 2 or 3. The controller can control manage each tank with two sensors – upper and lower (except the pool where only the upper sensor is used) or only with one, lower sensor, but in this case some of the controller functions are disabled. The upper sensor serves for the tank safety and protection functions DHW tank (maximum temperature), for the tank mixing/reheating function and for 2 heat exchangers the tank reheating with conventional sources. 2 temperatures The lower sensor serves for the solar collector tank reheating.

DHW tank 1 heat exchanger 2 temperatures

Each configured tank has on itself in the upper left corner the ordinaly number marking (black number) and below the tank ordinaly number the priority marking of the tank in the configuration (green number). DHW

DHW Factory settings

Buffer tank with embedded DHW tank 1 heat exchanger 2 temperatures

Buffer tank 1 heat exchanger 2 temperatures

BUF

BUF with DHW POOL 1 temperature

Pool

42

Tank 1, type

selection DHW

Doesn't exist/DHW/BUF/BUF with DHW/Pool

Tank 2, type

doesn't exist Doesn't exist/DHW/BUF/BUF with DHW/Pool

Tank 2, type

doesn't exist Doesn't exist/DHW/BUF/BUF with DHW/Pool

Tank 2, type

doesn't exist Doesn't exist/DHW/BUF/BUF with DHW/Pool

8.1.2.2. Tank 2 type In this menu it is necessary to select the installed tank type 2.For details please see description Tank type 1. 8.1.2.3. Tank 3 type In this menu it is necessary to select the installed tank type 3.For details please see description Tank type 1. 8.1.2.4. Tank 4 type In this menu it is necessary to select the installed tank type 4.For details please see description Tank type 1.

Technical instructions Cm-SOL

Installation, system components 8.1.2.5. Hydraulic tank connection In this menu it is necessary to select the hydraulic connection mode of the tanks with the solar collectors. In all schemes the tanks are connected serial with DHW – the tanks are always loaded according to the selected loading priority (first the first one, subsequently the second …). Depending on the installed configuration it is necessary to select one of three offered connection modes: Pump: each configured tank has its own solar collector pump. 2 way zone: each configurated tank has its 2 way valve (valve with spring ! ) + common solar collector pump. 3 way zone: the solar collector flow overlaps the 3 way zone valve (valve with spring !) depending on the given priority (2 tanks 1 valve, 3 tanks 2 valves , 4 tanks 3 valves ). The 3 way zone valve must always be installed with the zero position towards the primary tank (when the valve gets contact it overlaps onto the secondary tank, when the contact stops the spring returns).

Factory settings

Example: configurated 2 tanks, hydraulic connection: - pump

Example: configurated 2 tanks, hydraulic connection: 2 way zone valve

Hydr. tank connection.

selection Pump

Pump/3 way zone valve/2 way zone valve

Example: configurated 2 tanks, hydraulic connection: 3 way zone valve

8.1.2.6. Mixing – reheating If there is a need for the reheating of for example the primary DHW tank with the secondary buffer tank (when both tanks are reheated by solar energy, and the DHW is cooled down, it is possible to reheat the DHW tank by help of the buffer tank (if energy exists in the tank)), the controller can manage the pump between the buffer tank and the upper heat exchanger in the DHW tank on the basis of the temperature difference between the upper buffer tank temperature and the upper DHW tank temperature and the set difference. selection

Factory settings Mixing–reheating

Not exist

Not exist/Exist

Example: configurated 2 tanks, hydraulic connection: - 3 way zone valve, mixing /reheating

Technical instructions Cm-SOL

43

Installation, system components 8.1.3. DHW heating In this menu you can find the menus connected with the selection of the installed conventional sources for the heating of the primary Tank 1. It is possible to reheat only the Tank 1 with the installed upper temperature sensor. Electric heater switching on is possible only over an additional contactor. The controller optionally (and in current conditions) switches on/off the pump between the tank 1 and the boiler. (In order to switch the conventional source it is obligatory to install the upper Tank 1 sensor. After the configuration, the conventional source must be set in the menu 8.4. Tank (DHW) heating). 8.1.3.1. Installed electric heater If the electric heater is installed in the Tank 1, in this menu it must be marked in order to be existing in the configuration. When the electric heater is configured, it is possible to switch it on/off from the operation and it is needed to select the Schedule during which the electric heater operation is permitted. NOTE: the connection of the electric heater with the controller only over a contactor! Factory settings Installed el. heater

selection Not exist

Not exist/Exist

8.1.3.2. Boiler type 1 If a conventional source exists connected with Tank 1, in this menu you need to select the type of the conventional source to be used for the heating of the Tank 1. The selection of the Boiler 1 type serves only for the graphical display of the first conventional source on the screen. selection

Factory settings Boiler type 1

Not exist

Not exist/Wood/Pellets_Wood chip/ Gas_oil/Heat pump/Electric boiler

8.1.3.3. Boiler type 2 If a second conventional source exists connected to the Tank 1 in this menu it is necessary to select the type of the second conventional source to be used for the reheating of the Tank 1. The selection of the Boiler 2 type serves only for the graphical display of the second conventional source on the screen. selection

Factory settings Boiler type 2

Boiler type: Pellets/Wood chip

Boiler type: Wood

Boiler type: Gas/Oil

Not exist Not exist/Wood/Pellets_Wood chip/Gas_oil/ Heat pump/Electric boiler

Boiler type: Heat pump

Boiler type: Electric boiler

8.1.4. Recirculation installed If the system has a recirculation installed to the Tank 1, in this menu it needs to be marked in the configuration. When the recirculation is configurated, it is possible to switch it on/off, it is needed to select the operation interval of the pump start/stop and it is possible to select the Schedule during which the recirculation operation is permitted. selection

Factory settings Recirculation installed

44

Not exist

Not exist./Exist

Technical instructions Cm-SOL

Installation, system components 8.1.5. Flowmeter If a flowmeter is installed in the system in this menu it needs to be marked to be existing in the configuration. If the flowmeter is switched on, it is needed to enter its characteristics in the following menus (the constant and volume per pulse and the sensor address). selection

Factory settings Flowmeter

Not exist

Not exist/Exist

8.1.6. Back flow temperature (collector) If the back flow temperature sensor is installed in the system in this menu it is necessary to select the address and sensor type. The sensor serves for a more accurate measuring of the collected energy from the solar collectors (with solar collector sensor and correct entered or measured fluid flow through the collectors). If the back flow temperature sensor is not installed, the controller takes as the back flow temperature the lower tank temperature. NOTE: The measuring of energy is done over the temperature in the solar collector sensor, the temperature in the back flow sensor (or lower tank sensor) and entered flow (or flow value from the installed flow meter). The calculation of the collected energy from the solar collectors depends a lot on the accuracy of the measured temperatures and the entered/measured fluid flow through the solar collectors. In case of 2 solar collector fields the back flow sensor is installed on the return of the first field while for the measuring of energy of the second field the lower tank temperature is taken into consideration.

E= 543 (kWh)

built in and configured back flow sensor

Example: configurated 1 tank, 1 flat plate collector, return/back flow sensor, outdoor/outer temperature sensor

8.1.6.1. Sensor address It is necessary to set (choose) adress (input) of the connected back flow sensor (it is possible to connect on one free out of 10 addresses). selection

Factory settings Sensor address

Isključeno OFF./T1/.../T10

... 8.1.6.2. Sensor type If the sensor type NTC is installed here it is necessary to change the sensor type from PT1000 to NTC. selection

Factory settings Sensor type

Technical instructions Cm-SOL

PT1000

PT1000/NTC

45

Installation, system components 8.1.7. Outdoor sensor If in the system is installed outdoor temp. sensor in this menu it is necessary to select the address and sensor type. The outdoor temperature sensor shows the information on the main screen about the current outdoor temperature (additional equipment).

Installed and configured outdoor temperature sensor E= 543 (kWh)

Example: configurated 1 tank, 1 flat collector, back flow sensor, outdoor temperature sensor 8.1.7.1. Sensor address It is necessary to set (choose) address (input) of the connected outdoor temperature sensor (it is possible to connect on one free out of 10 addresses). selection

Factory settings Sensor address

OFF

OFF./T1/.../T10

... 8.1.7.2. Sensor type If the sensor type NTC is installed here it is necessary to change the sensor type from PT1000 to NTC. Factory settings Sensor type

46

selection PT1000

PT1000/NTC

Technical instructions Cm-SOL

Installation, system components 8.1.8. Pumps / Outputs In this menu function of the output that is used must be defined (max. 8 outputs) and used output standby time can be defined after which function of pump and valve protection is activated due to longterm inactivity.

8.1.8.1. Output functions In this menu function of the output that is used must be defined (max. 8 standard outputs). 2 PWM and 2 analog outputs). 8.1.8.1.1. Output 1 function In this menu function of the output that is used must be defined (one of the 22 functions - pump of collector, tank, boiler, recirculation, pool, mixing/reheating, electric heater, zone 2 way or zone 3 way valve). 8.1.8.1.2. Output function 2 8.1.8.1.3. Output function 3 8.1.8.1.4. Output function 4 8.1.8.1.5. Output function 5 8.1.8.1.6. Output function 6 8.1.8.1.7. Output function 7 8.1.8.1.8. Output function 8

selection

Factory settings Output 1 function Output 2 function Output 3 function Output 4 function Output 5 function Output 6 function Output 7 function Output 8 function

see 8.1.8.1.x. Output 1 function

Disabled

Disabled/Pump collector1/Pump collector2/ Pump tank1/Pump tank2/Pump tank3/ Pump tank4/Pump boiler1/Pump boiler2/ Electric heater/Recirculation pump/Pool pump/ Exchanger pump/Pump MRh/ 3 way valve1/3 way valve2/3 way valve3/3 way valve4/ Valve1/Valve2/Valve3/Valve4

8.1.8.1.9./10. PWM 1/2 functio In this menu functions of outputs for PWM pumps must be defined (one of 6 functions - collector pumps, tank pumps to the collector. NOTE: Power to the pump is recommended to take from external power supply, solar controller just controls the pump. 8.1.8.1.11./12. Analog Out 1/2 In this menu functions of outputs for analog steered pumps (0-10V) must be defined. NOTE: Power to the pump is recommended to take from external power supply, solar controller just controls the pump. selection

Factory settings Function PWM 1 Function PWM 2 Function output 1 Function output 2

Technical instructions Cm-SOL

Disabled

Disabled/Pump collector1/Pump collector2/ Pump tank1/Pump tank2/Pump tank3/ Pump tank4/

47

Installation, system components 8.1.8.2. Pumps/Valves protection In this menu pump/valve protection can be enabled. Also, standby time can be set after which pump/valve protection will be activated to prevent blocking due to the longterm inactivity.

8.1.8.2.1. Pumps/Valves protection Pumps/valves protection function monitors activity of each output (pump or valve) to prevent blocking of the pump or valve due to longterm inactivity. selection

Factory settings Pump/valve protect.

OFF

ON/OFF

8.1.8.2.2. Off time By setting the Off time, maximum inactivity time of each output is set after which controller activates output for 60 second. Factory settings Off time

min./max. 48

1 / 720

h

8.1.9. Pressure control In case of installation of the pressure switch it must be enabled in this menu. When this pressure switch is connected and enabled, position (address) where is connected must be set (address of the sensor T under Collector). When the pressure in the solar system is to low, when pressure switch gives signal to the controller (system pressure on which pressure switch gives signal depends on the type and setting of the pressure switch) and low system pressure warning is displayed on the controller screen. selection

Factory settings Pressure control

Not exist

Not exist/Exist

"Option is not implemented!" - If you choose components of solar system that controller can not run, warning will appear on the main screen, after which a different configuration must be selected ie. other components of the solar system must be selected. - see available schemes of components that controller can run at the en of these manual.

48

Technical instructions Cm-SOL

Installation, collector

8.2. COLLECTOR 8.2. Collector In this menu are settings for the work of the collector (one or two fields (if they exist)) and it’s protection functions.

example: configured 2 collector fields, pressure control

8.2.1. Collector 1 In this menu settings for work of the collector 1 are set (maximum allowed collector temperature, enabling temperature of the collector 1 for start of the collector pump, puls start of the collector 1 pump and collector sensor address).

8.2.1.1. T MAX collector 1 Setting of the maximum temperature of the collector 1. Pump of the solar collector field 1 works to the temperature in collectors [T MAX collector 1] after which stops (to protect the fittings from to high temperature, steam in the collectors and inability to operate the pump until temperature in the collectors is lower then set max. temp. of the collectors. When temperature in the collectors falls below [T MAX collector 1 - 4°C] pump of collector field 1 starts to work again if other conditions are met. NOTE: [T MAX collector] must be set according to the boiling point of the solar fluid in the solar system and always must be lower than the boiling point. min./max. unit.

Factory settings T MAX collector 1

140

30 / 150

°C

8.2.1.2. T enable coll.1 Setting of the minimum temperature of the collector 1 at which circulation trough collector 1 starts (working of the collector pump). Factory settings T enable coll.1

I Technical instructions Cm-SOL

I

I

min./max. unit. 10

0 / 90

°C

8.2.1.3.Pulse collector start In this menu are additional menus for setting the parameters for the pulse start of the pump (kick) of the collector field 1 If collector sensor isn’t installed into collector (but somewhere on the flow tube) or there are more collectors in the same field, it’s recommended to enable pulse start which in case of the inactivity of the collector pump, periodically starts it for some time to have better temperature reading of the solar fluid on the collector sensor. NOTE: to often and to long work of the collector pump can unnecessarily cool down the tank! Work and pause time of the pump depends on the size and location of the collector field and collector sensor.

49

Installation, collector 8.2.1.3.1. Pulse start collector 1 In this menu pulse start of collector can be enabled or disabled. All preset times and also schedules are valid. selection

Factory settings Pulse start coll.1

OFF

ON/OFF

8.2.1.3.2.Pump work time Setting of the pump working time in pulse start. NOTE: Working time must be adjusted according size and location of collector field and collector sensor to have accurate reading from the collector sensor to start heating the tank as soon as possible. Factory settings Pump working time

min./max. unit. 10

0 / 3600 sec

8.2.1.3.3.Pump pause time Setting of the pump pause time (not working) in pulse start. NOTE: Pause time must be adjusted according size and location of the collector field and collector sensor to have accurate reading from the collector sensor to start heating the tank as soon as possible.

Factory settings Pump pause time

min./max. unit. 15

0 / 1440 min

8.2.1.3.4.Schedule In this menu are additional menus for setting the schedule for working of the pump in puls start (kick) for the collector field 1. Schedule can be disabled or selected one of two tables with set time intervals with enabled and disabled function of the pump.

8.2.1.3.4.1.Schedule In this menu schedule can be enabled/disabled and one of the two tables can be selected according to which puls start of the pump will work. NOTE: If the puls start of the pump is enabled and Schedule is set to Off, puls start of the pump will work all the time (24/7) according to the set work/pause time. In this case puls start of the pump will work also during the night and there is possibility to cool the tank trough the collector down. Factory settings Schedule

selection Table 1

OFF/Table1/Table2

8.2.1.3.4.2.Table 1 In this menu it is possible to set 3 time intervals (3 start (green field) and 3 stop (red field) for each day in the week in which pump will work according the set pulse start. Factory setting: Impulse start of the pump is active from 08:00 to the 17:00 every day in the week. From 17:00 of the first day to 08:00 next day puls start of the pump is not working. Factory settings Table 1

50

selection 08:00-17:00 mon/tue/wed/thu/fri/sat/sun

Technical instructions Cm-SOL

Installation, collector 8.2.1.3.4.2.Table 2 In this menu it is possible to set 3 time intervals (3 start (green field) and 3 stop (red field) for each day in the week in which pump will work according the set pulse start. Factory setting: Impulse start of the pump is active from 08:00 to the 17:00 every day in the week. From 17:00 of the first day to 08:00 next day puls start of the pump is not working. selection

Factory settings Table 2

08:00-17:00 mon/tue/wed/thu/fri/sat/sun

8.2.1.4. Collector 1 sensor address It is necessary to set (choose) address (input) of the connected collector sensor (it is possible to connect on one free out of 10 addresses, regulation recommends input T1) Factory settings

selection

Coll.1 sensor address Not exist Not exist./T1/.../T10

8.2.x. Collector 2 In this menu settings for working of the collector 2 are set (maximum allowed collector temperature, enabling temperature of the collector 2 for start of the collector pump, puls start of the collector 2 pump and collector sensor address). Menus are equivalent to the menus for Collector 1 - for details see description 8.2.1. Collector 1.

8.2.x.Collector cooling In this menu collector cooling can be enabled or disabled (through the tank) and set the difference for collector cooling start. With the collector cooling function, boiling of the solar fluid in the collector wants to be delayed by increasing tanks temperature to the maximum temperature [T MAX tank = 90°C]. Collector cooling starts if the temperature in the collectors reaches the [TMAX collector -dTcooling (collector)] and if all tanks are full with energy to the [TMAX tank (set)]. [Tcoll.>TMAX coll. -dTcooling (collector)] Collector cooling stops if Tcollector exceedes [TMAX collector] or temperature in the collectors falls below [Tcoll.
Technical instructions Cm-SOL

51

Installation, collector 8.2.x.1.Collector cooling In this menu collector cooling can be enabled or disabled (through the tank). Factory settings Collector cooling

C C C

selection OFF

OFF/ON

8.2.x.2. Cooling difference Setting of the difference when collector cooling starts [TMAX collector dTcooling (collector)] (factory 140-20=120°C) min./max. unit.

Factory settings Cooling difference

20

1 / 50

°C

8.2.4. Antifreeze protection In this menu collector antifreeze function can be set and temperature (of the collector) for start of this function can be set.

F F F

This function is used when in solar system is water and if outside temperature don’t fall below 0°C. In solar system always is recommendation to use mixture of the glycol and water (solar antifreeze and water). With this function enabled, circulation through the collector is started to try to prevent freezing of the collector with the heat of the tank. Antifreeze protection starts when temperature in the collectors falls to the set temperature [Tstart] (factory +4°C). Antifreeze function stops when temperature in collectors raised for +2°C from set temperature [Tstart] and when lower temperature in the tank fals to the +3°C (to prevent freezing of the tank). Freezing protection start from tank with lowest priority to the tank with highest priority. NOTE: Only use this function when only water is in the collectors. It is never recommended to fill the solar system with water only (without glycol)! By switching on the frost protection function, it is possible to coll the tanks. Possible significant energy consumption of conventional sources in heating tank due to "heating" the collector!

8.2.x.1. Antifreeze protection In this menu collector antifreeze protection can be enabled or disabled. selection

Factory settings Antifreeze protection

OFF

OFF/ON

8.2.x.2. T start Setting of the temperature (in the collector) to start the antifreeze protection. min./max. unit.

Factory settings T start

4

0 / 10

°C

8.2.x. Pressure sensor adress In case there is pressure sensor installed, here must be set the connecting address (input) to which this sensor is connected (possible to connect to one of 10 addresses (inputs)). Factory settings Pressure sensor add. Not exist

52

selection Not exist./T1/.../T10

Technical instructions Cm-SOL

Installation, tank

8.3. TANK

exapmle: configurated 3 tanks (DHW, BUF, Pool), priotrity test, mixing/heating function

8.3. Tank In this menu are additonal menus for setting the parammeters for the tanks (depending of the set configuration and tank type, from 1 to maximum 4 tanks).

8.3.1. Temperature DHW Setting the desired DHW temperature (domestic hot water), tank on upper sensor. Conventional heating sources (el. heater, boiler1, boiler2) heats the tank to the set DHW temperature. NOTE: DHW temperature is related only to the conventional heating sources. Solar collectors are heating tanks to the temperature [TMAX tank]. Factory settings Temperature DHW

min./max. unit. 55

10 / 85

°C

8.3.2.1 T MAX tank 1 Setting the max temperature of the tank1. Solar collectors are heating tank 1 to the temperature [T MAX tank 1] after which solar heating of the tank 1 stops and switches to the next tank according the priority (if exists). If the collector cooling function is enabled and activated, tank temperature can rise up to max. 90°C (or 95°C if TMAX tank is set to 90°C). min./max. unit.

Factory settings T MAX tank 1

70

30 / 90

°C

If the pool is set as the last tank in the configuration, max. temperature of the pool can be set in following range: T MAX tank X

28

15 / 40

°C

8.3.2.2. TDcoll-tank (difference) Setting the desired difference between temperature of the collector and temperature of the tank (lower sensor) for start and stop of the collector pump. START pump coll. -> [Tcollector > TDcoll-tank + THcoll-tank]. STOP pump coll. -> [Tcollector < TDcoll-tank]. Factory settings TDcoll-tank

Technical instructions Cm-SOL

min./max. unit. 4

1 / 10

°C

53

Installation, tank 8.3.2.3. THcoll-tank (histeresys) Setting the desired histeresys of the temperature between collector and tank (lower sensor) for start of the collector pump. START pump coll. -> [Tcollector > TDcoll-tank + THcoll-tank]. STOP pump coll. -> [Tcollector < TDcoll-tank]. Factory settings

min./max.

THcoll-tank

2

1 / 10

°C

8.3.2.4. Sensor tank 1 upper Sensor tank 1 upper is used: - stop of the collector pump when set maximum temperature in the tank is reached, - protection function of tank cooling through the collector, - for additional heating of the tank with the conventional heating sources (boilers and el. heater), - One time DHW function - Party function - Mixing/heating function - Holiday option - Legionella protection In this menu sensor address and type must be set.

E= 543 (kWh)

installed and set sensor tank 1 up

example: configurated 1 tank (with 2 sensors), 1 flat plate collector, back flow sensor, outdoor sensor

8.3.2.4.1. Sensor upper It is necessary to set (choose) address (input) of the connected sensor upper (it is possible to connect sensor upper (it is possible to connect an one free of 10 addresses, controller recommends input T2). selection

Factory settings Sensor upper

Not exist

Not exist/T1/.../T10

8.3.2.4.2. Sensor type If NTC sensor is installed, here must be changed from PT1000 to the NTC. Factory settings Sensor type

54

selection PT1000

PT1000/NTC

Technical instructions Cm-SOL

Installation, tank 8.3.2.5. Sensor tank 1 lower Sensor tank 1 lower is used: - work of the collector pump. - in case that back flow sensor isn’t installed, for energy meassurement (meassurement is less precise than with back flow sensor). - in case that sensor tank 1 upper isn’t installed, it takes over it’s functions except additonal heating function with conventional heating sources. - at function of Collector cooling through the tank, - at Collector antifreeze function, - at Holiday option. In this menu sensor address and type must be set.

E= 543 (kWh)

example: configurated 1 tank (with 2 sensors), 1 flat plate collector, return flow sensor, outdoor sensor

installed and set sensor tank 1 lower

8.3.2.5.1. Sensor lower It is necessary to set (choose) address (input) of the connected sensor upper (it is possible to connect sensor upper (it is possible to connect an one free of 10 addresses, controller recommends input T3). selection

Factory settings Sensor lower

Not exist

Not exist/T1/.../T10

8.3.2.5.2. Sensor type If NTC sensor is installed, here must be changed from PT1000 to the NTC. selection

Factory settings Sensor type

PT1000

PT1000/NTC

8.3.x.1 T MAX tank 2 Setting the max temperature of the tank2. Solar collectors are heating tank 2 to the temperature [T MAX tank 2] after which solar heating of the tank 2 stops and switches to the next tank according the priority (if exists). If the collector cooling function is enabled and activated, tank temperature can rise up to max. 90°C (or 95°C if TMAX tank is set to 90°C) min./max. unit.

Facotry settings T MAX tank 2

70

30 / 90

°C

If the pool is set as the last tank in the configuration, max. temperature of the pool can be set in following range: T MAX tank X

Technical instructions Cm-SOL

28

15 / 40

°C

55

Installation, tank 8.3.x.2. TDcoll-tank (difference) Setting the desired difference between temperature of the collector and temperature of the tank (lower sensor) for start and stop of the collector pump. START pump coll. -> [Tcollector > TDcoll-tank + THcoll-tank]. STOP pump coll. -> [Tcollector < TDcoll-tank]. Factory settings

min./max. unit.

TDcoll-tank

4

1 / 10

°C

8.3.x.3. THcoll-tank (histeresys) Setting the desired histeresys of the temperature between collector and tank (lower sensor) for start of the collector pump. START pump coll. -> [Tcollector > TDcoll-tank + THcoll-tank]. STOP pump coll. -> [Tcollector < TDcoll-tank]. min./max. unit.

Factory settings THcoll-tank

2

1 / 10

°C

8.3.x.4. Sensor tank 2 upper Sensor tank 2 is used: - stop of the collector pump when set maximum temperature in the tank is reached, - protection function of tank cooling through the collector, - Mixing/heating function, - Holiday option. In this menu sensor address and type must be set.

Installed and set sensor tank 2 up

example: configurated 2 tank (both with 2 sensors), 1 vacuum tube collector, zone 3-way valve 8.3.x.4.1. Sensor upper It is necessary to set (choose) address (input) of the connected sensor upper 2 (it is possible to connect sensor upper (it is possible to connect an one free of 10 addresses, controller recommends input T4). Factory settings Sensor upper

selection Not exist

Not exist/T1/.../T10

8.3.3.4.2. Sensor type If NTC sensor is installed, here must be changed from PT1000 to the NTC. Factory settings Sensor type

56

selection PT1000

PT1000/NTC

Technical instructions Cm-SOL

Installation, tank 8.3.x.5. Sensor tank 2 lower Sensor tank 2 lower is used: - work of the collector pump. - in case that back flow sensor isn’t installed, for energy meassurement (measurement is less precise than with back flow sensor). - in case that sensor tank 2 upper isn’t installed, it takes over it’s functions - at function of Collector cooling through the tank, - at Collector antifreeze function, - at Holiday option. In this menu sensor address and type must be set.

installed and set sensor tank 2 lower

example: configurate 2 tank (both with 2 sensors), 1 vacuum tube collector, zone 3-way valve 8.3.3.5.1. Sensor lower It is necessary to set (choose) address (input) of the connected sensor tank 2 lower (it is possible to connect sensor upper (it is possible to connect an one free of 10 addresses, controller recommends input T5). Factory settings Sensor lower

selection Not exist

Not exist/T1/.../T10

8.3.x.5.2. Sensor type If NTC sensor is installed, here must be changed from PT1000 to the NTC. selection

Factory settings Sensor type

PT1000

PT1000/NTC

8.3.x. Tank 3 In case Tank 3 is set as DHW or BUF or BUF with DHW, menus must be set in the same way like for Tank 2 - see menus under 8.3.2. Tank 2.

8.3.x. Tank 4 In case Tank 4 is set as DHW or BUF or BUF with DHW, menus must be set in the same way like for Tank 2 - see menus under 8.3.x. Tank 2.

Technical instructions Cm-SOL

57

Installation, tank

EXAMPLE - Configuration of TANKS as SWIMMING POOL

If Tank 1, 2 or 3 is set as POOL, menus must be set the same like for Tank 3 in the description below. (example: Pool set as tank 3). IMPORTANT: in the pool must be installed and set only Sensor tank upper! NOTE: pool sensor ALWAYS must be NTC5K because of the much better precision in temperature reading (reading to 1 decimal place) than PT1000. 8.3.x.1 T MAX tank 3 Setting the maximum temperature of the tank 3. Solar collectors heats tank 3 to the temp. [T MAX tank 3] after which stops heating of this tank. If the collector cooling function is enabled and active, temperature in the tank can reach up to max. 90°C NOTE: Pool must be always set as the LAST tank! Factory settings T MAX tank 3

min./max. unit. 28

15 / 40

°C

8.3.x.2. TDcoll-tank (difference) Setting the desired difference between temperature of the collector and temperature of the tank (pool - upper sensor) for start of the collector pump. START coll. pump -> [Tcollector > TDcoll-tank + THcoll-tank] STOP coll. pump -> [Tcollector < TDcoll-tank]. min./max. unit.

Factory settings TDcoll-tank

4

1 / 10

°C

8.3.x.3. THcoll-tank (hysteresis) Setting the desired hysteresis temperature between collectors and the tank (pool - upper sensor) for start of the collector pump. START coll pump -> [Tcollector > TDcoll-tank + THcoll-tank] STOP coll. pump -> [Tcollector < TDcoll-tank]. min./max. unit.

Factory settings THcoll-tank

2

1 / 10

°C

8.3.x.4. Sensor tank 3 upper Sensor tank 3 upper (pool) is used: - work of the collector pump including the stop of the collector pump when in the tank (pool) set maximum temp. is reached, - in case that back flow sensor isn’t installed, for energy meassurement (meassurement is less precise than with back flow sensor). - at function of Collector cooling through tank, - at Collector antifreeze function, - in protection function of the tank cooling through the collector - at Holiday option. In this menu sensor address and type must be set.

58

Technical instructions Cm-SOL

Installation, tank

installed and set sensor tank 3 up

example: configurated 3 tank (2 with 2 sensors, 3. tank = pool), 1 vacuum tube collector, back flow sensor, zone 3-way valve

8.3.x.4.1. Sensor upper It is necessary to set (choose) address (input) of the connected sensor upper 3 (it is possible to connect sensor upper (it is possible to connect an one free of 10 addresses, controller recommends input T6). Factory settings

selection

Sensor upper

Not exist

Not exist/T1/.../T10

8.3.x.4.2. Sensor type Because of the much better precision in temperature reading (reading to 1 decimal place) pool sensor ALWAYS must be NTC5K (not in the delivery). If NTC sensor is installed, here must be changed from PT1000 to the NTC. selection

Factory settings Sensor type

PT1000

PT1000/NTC

8.3.x. Enabled tanks In this menu tanks can be enabled/disabled in the work of the system. ENABLED - tank is enabled (included) in work of the system DISABLED - tank is disabled (removed) from the work of the system (to this tank pumps, valves and additional heating doesn’t work). selection

Factory settings

example: set 3 tanks

Tank 1

Enabled

Enabled/Disabled

Tank 2

Enabled

Enabled/Disabled

Tank 3

Enabled

Enabled/Disabled

Tank 4

Enabled

Enabled/Disabled

8.3.x. Tank priority Setting the priority for the solar filling of the tanks. Tank 1 always must be first in priority, other can be rotated according the filling priority. Priority of each tank is marked on the upper left corner of the tank (green number), below tank order number (black number). selection

Factory settings

example: set 3 tanks

Technical instructions Cm-SOL

2 tanks

12

12

3 tanks

123

123 / 132

4 tanks

1234

1234/1243/1324/1342/1423/1432

59

Installation, tank 8.3.x. Priority test If there is more than 1 tank in the configuration, priority test can be enabled to periodicaly test the collector temperature if it has enough high temperature to start filling the prioritiy tank again.

P P P

After priority tank is filled (or [T MAX tank1] or [Tcoll. < Ttank1 + TDcolltank]), solar heating is switched to the next tank according the priority. By enabling Prioritiy test function, next tank by priority will be filled for some time (set under Priority filling) after which it will stop for some time (set under Priority pause) to check if the collectors can fill priority tank or they will continue to fill current tank. If the collector temperature increase in the set pause time is higher or equall [3°C/x min.] pause time is extended until increase of the collector temp. is higher ie. until is possible to fill priority tank again. If the increase of the collector temp. in set time is lower than [3°C/x min.] filling the current tank continues. By enabling Priority test function in menu 1. Tank, menus Priority filling and Priority pause are shown.

Factory settings Priority test

selection OFF

OFF/ON

8.3.8. Priority filling Priority test -> ON Time for continuous filling of the next tank (not priority tank).

Factory settings Filling priority

min./max. unit. 15

0 / 720

min

8.3.9. Priority pause Priority test -> ON Pause time for the collector pump in which is tested rise of the collector temperature to switch back to heat priority tank. If the temperature rise in the set pause time is higher or equal [3°C/x min.], time of the pause is extended for next interval, in which rise of the collector temperature is tested and possibility to start to heat priority tank. If the temperature rise in set pause time is less than [3°C/x min], current tank continues to be filled.

Factory settings Priority pause

60

min./max. unit. 3

0 / 60

min

Technical instructions Cm-SOL

Installation, tank 8.3.x. Tank cooling Tank cooling ie. decrease the water temperature in the tanks to prepare them to accept new solar energy next day can be done through collectors or through recirculation (if it’s installed into the system and connected to the controller). NOTE: tank cooling always starts from the tank with the lowest priority to the tank with highest priority. Through collector - cooling the tank through the collector (and pipes to the collector)

T T T

NOTE: it’s recommended that cooling is done through flat collectors (not vacuum tube collectors) due to lower insulation of the flat plate collectors. Tank cooling is done when collector temperature is lower than temperature in tank lower [Tcoll + dTcoll/tank < T MAX tank X]. Tank cooling start only when all tanks are filled to the [T MAX tank] and start from lowest priotiry tank. Tank cooling stops when temperature of the upper tank sensor is lower than the difference collector/tank [Ttank_up < TMAX tank -dTcoll/tank]. Through recirculation - cooling of the first tank through recirculation (cooling only first, priority tank, only if recirculation is connected). Tank cooling starts only when all tanks are filled to the [T MAX tank] and when [Ttank 1_up > T MAX tank 1] (only in first tank). First tank cooling stops when temperature of the upper sensor falls for 5°C from [T MAX tank 1]. [Ttank 1_up < T MAX tank 1 - 5°C]. Factory settings Tank cooling

selection Disabled

Disabled/Through coll./Recirculation

8.3.x. Mixing-heating When temperature of the first (priority) tank (upper sensor) is lower for min. set difference than second tank (upper sensor) mixing-heating pump starts to heat first tank. This function is mostly used when first tank is DHW and second is BUF, when excess of energy (solar) is stored in the BUF tank during the day so in the evening, after DHW consumption, the DHW tank can additionaly be heated with energy from BUF, without using conventional heating source. In this menu is possible to enable/disable function of additional heating of the first tank with the second tank and set the difference between first two tanks.

example: configurated 2 tanks, hid. connection: - Zone 3-way valve, Mixing/heating

8.3.x.1. Mixing-heating In this menu mixing-heating function can be enabled or disabled. Factory settings Mixing-heating

Technical instructions Cm-SOL

selection OFF

OFF/ON

61

Installation, tank 8.3.x.2. TDif Tank2->Tank1 (difference) Setting the temperature difference between second and first tank (upper sensors) for start and stop of the mixing/heating pump. Factory settings Tdif Tank2->Tank1

min./max. unit. 4

1 / 10

°C

8.3.x. Pulse start pool This menu is shown only if pool is set in the configuration. In this menu are additional menus for setting the pulse start of the pool pump (kick). If pool sensor can’t be installed into place where it can read correct temperature, it’s recommended to enable pulse start of the pump (when pump is still) which occasionaly starts the pump for set time, to read correct tempearature of the pool sensor.

I

I

I

NOTE: to offten and to long work of the pool pump power supply consumption can be increrased and pool can be cooled! Work and pause time of the pool pump depends of the location of the pool sensor.

8.3.x.1. Pulse start pool In this menu pulse start of the pool can be enabled or disabled. All set times and schedule are valid. Factory settings

setting

Pulse start pool

OFF/ON

OFF

8.3.x.2. Pump pause time Setting the pause time of the pool pump in pulse start. NOTE: Time must be set according to the position of the pool sensor to have correct pool temperature and start with the pool heating as soon as possible. Factory settings Pump pause time

min./max. unit. 15

0 / 1440 min

8.3.x.3. Pump working time Setting the working time of the pump in pulse start. NOTE: Time must be set according to the position of the pool sensor to have correct pool temperature and start with the pool heating as soon as possible. Factory settings Pump working time

min./max. unit. 60

0 / 3600 sec

8.3.12.4.Schedule In this menu are additional menus for setting the schedule for pulse start (kick) of the pool pump. Schedule can be switch off or one of two tables with adjusted on/off intervals can be set.

62

Technical instructions Cm-SOL

Installation, tank 8.3.x.4.1.Schedule In this menu Schedule can be enabled/disabled and set one of two tables according to which pool pump Pulse start will work. NOTE: If Pulse start is on and Schedule is off, pulse start will work all the the time (24/7) according the work/pause time. In this case, power supply consumption can be increased (pool pump) and pool cooling can occur. Factory settings Schedule

selection Table 1

OFF/Table 1/Table 2

8.3.x.4.2.Table 1 In this menu 3 time intervals (3 starts (green fields) and 3 stops (red fields)) can be set for each day of the week according to pool pump will work in pulse start. Factory setting: pulse start is active from 08:00 h to 17:00 h every day of the week. From 17:00 h of the first day to 08:00 h next day pulse start doesn’t work. Factory settings Table 1

selection 08:00-17:00 mon/tue/wed/thu/fri/sat/sun

8.3.x.4.3.Table 2 In this menu 3 time intervals (3 starts (green fields) and 3 stops (red fields)) can be set for each day of the week according to pool pump will work in pulse start. Factory setting: pulse start is active from 08:00 h to 17:00 h every day of the week. From 17:00 h of the first day to 08:00 h next day pulse start doesn’t work. Factory settings Table 2

Technical instructions Cm-SOL

selection 08:00-17:00 mon/tue/wed/thu/fri/sat/sun

63

Installation, tank heating

8.x. DHW heating 8.x. DHW heating In this menu are additional menus for setting the heating with the conventional heating sources connected to tank 1.

example: configurated 1 electric heater and 2 conventional heating sources

8.x.x. Electric heater In this menu are additional menus for setting the heating with the electric heater. 8.x.x.1. Electric heater In this menu electric heater can be switch ON or OFF selection

Factory settings Electric heater

OFF

OFF/ON

8.x.x. Boiler 1 In this menu are addtional settings for heating with conventional source 1.

8.x.x.1. Boiler 1 In this menu for heating with conventional heating source 1 can be enabled or disabled (ie. work of pump between conventional heat source and tank 1). selection

Factory settings Boiler 1

OFF

OFF/ON

8.x.x.2. T MAX Boiler 1 Setting of the maximum temperature of the conventional heating source 1. If the temperature in conventional heating source is higher than set, pump to the tank will not start. Factory settings T MAX Boiler 1

min./max. unit. 90

30 / 90

°C

8.4.2.3. TD boiler1-tank1 (difference) Setting of the temperature difference between conventional heating source 1 and first tank (upper sensor) for start and stop of the pump between boiler 1 and tank 1. Some of the conditions: pump start: [Tboiler1=>Ttank1+TDboiler1-tank+5] pump stop: [Tboiler1=
min./max. unit. 10

3 / 20

°C

8.x.x.4. TH boiler1-tank1 (hysteresis) Setting the temperature hysteresis between conventional heating source 1 and fist tank (upper sensor) for start of the pump between boiler 1 and tank 1. Some of the conditions: pump start: [Ttank1upper
64

min./max. unit. 10

3 / 20

°C

Technical instructions Cm-SOL

Installation, tank heating 8.4.2.5. T enable boiler 1 Setting the minimum temperature of the conventional heating source for starting the pump between conventional heating source 1 and tank 1 (normaly needed when condensation of the boiler needs to be prevented.) Factory setting

T enable boiler 1

min./max. Val.

60

0 / 90

°C

8.4.2.6.Schedule In this menu are additional menus for setting the schedule for working of the conventional heating source 1. NOTE: In case schedule is not set, convetional heating source pump will work according set temperatures always, 24/7. Recommendation is to set schedule according to the real need for DHW to optimize fuel consumption.

8.4.2.6.1.Schedule In this menu schedule can be enabled/disabled and one of two tables can be selected according to which heating with convetional heating source will work. NOTE: If the convetional heating source is enabled and schedule is disabled, tank heating with convetional heating source will be active always, 24/7, according the set temperatures. Factory setting Schedule

setting OFF

OFF/Table 1/ Table 2

8.4.2.6.2.Table 1 In this menu 3 time intervals can be set (3 starts ((green fields) and 3 stops (red fields) for each day of the week in which heating with coventional heating source will work according the set temperatures. Factory setting: conventioanl heating source is enabled from 06:00 h to 22:00 h every day of the week. From 22:00 h of the first day to 06:00 h next day heating with conventional heating source is disabled. Factory setting Table 1

setting 06:00-22:00 mon/tue/wed/thu/fri/sat/sun

8.4.2.6.3.Table 2 In this menu 3 time intervals can be set (3 starts ((green fields) and 3 stops (red fields) for each day of the week in which heating with coventional heating source will work according the set temperatures. Factory setting: conventioanl heating source is enabled from 06:00 h to 22:00 h every day of the week. From 22:00 h of the first day to 06:00 h next day heating with conventional heating source is disabled. Factory setting Table 2

setting 06:00-22:00 mon/tue/wed/thu/fri/sat/sun

8.4.2.7. Sensor address It’s necessary to select address of the connected sensor of the convetional heating source 1 (possible to connect to one od 10 free address, regulation autmatically recommends input according the set configuration). Factory setting Sensor address

Technical instructions Cm-SOL

setting

Not exist

Not exist/T1/.../T10

65

Installation, tank heating, recirculation 8.x.x.8. Sensor type If NTC sensor is installed, here it must be changed from PT1000 to NTC type. selection

Factory settings Sensor type

PT1000

PT1000/NTC

8.x.x. Boiler 2 Menus for conventional heating source 2 settings. All menus are similar to menus for conventional heating source 1 and will not be separately explained here (for details, see 8.4.2. Boiler 1).

8.x.x. Heating delay For this menu to appear, minimun one of the conventional heating source must be set. If the function is enabled and collector pump is active (tank is filled with solar energy) this function lowers the temperature of activation of the conventional heating source function (delays start of the conventional heating source function) by value that is set under Lowering temperature menu. If collector pump is active, delay start of the heating: [Ttank_upper1 <= TDHW -dTboiler_tank - Tlowering temperature].

E E E

If collector pump isn’t active a tank needs to be heated, delay isn’t considered: [Ttank_upper1 <= TDHW -dTboiler_tank]. 8.x.x.1. Heating delay In this menu heating delay can be enabled or disabled. selection

Factory settings Heating delay

OFF

OFF/ON

8.x.x.2. Lowering temperature Setting the temperature for which start of the heating with convenctional heating source will be delayed when collector pump is working. Factory settings Lowering temperature

min./max. unit. 0

0 / 90

°C

8.5. RECIRCULATION 8.x. Recirculation In this menu are additional menus for setting the recirculation of DHW. In this menus work and pause time of the DHW recirculation pump can be set and also set the time interval when work and pause will be active.

R R R

8.x.1. Recirculation In this menu recirculation function can be enabled or disabled. All set times and schedules remains valid. Factory settings Recirculation

66

unit.

OFF

OFF/ON

Technical instructions Cm-SOL

Installation, recirculation 8.x.2.Pump working time Setting the recirculation pump working time when recirculation is active. NOTE: Time must be set according the recirculation system. Recommendation is to set the working time as short as possible to minimize cooling down the tank. min./max. unit.

Factory settings Pump working time

5

1 / 1440 min

8.x.3. Pump pause time Setting the recirculation pump pause time when circulation is active. NOTE: Time must be set according the recirculation system. Recommendation is to set the pause time as long as possible to minimize cooling down the tank. Factory settings Pump pause time

min./max. unit. 15

0 / 1440 min

8.x.4. Schedule In this menu are additional menus for set the recirculation schedule. Schedule can be enabled/disabled or select one of the two tables with set time intervals for enabled and disabled function.

8.x.4.1. Schedule In this menu schedule can be enabled/disabled and selected one of two tables according to which DHW recirculation will work. NOTE: In case recirculation is enabled and shedule is disabled, recirculation will always work according set times, 24/7, ie. recirculation pump will work when is not needed and will cool down DHW tank and increase fuel comsumption of the conventional heating source. Factory settings Schedule

selection OFF

OFF/Table 1/Table 2

8.x.4.2. Table 1 In this menu 3 time intervals can be set (3 start (green fields) and 3 stop (red fields)) for each day of the week in which recirculation pump will work according the set work/pause times. Factory setting: recirculation is enabled from 06:00 h to 22:00 h every day of the week. From 22:00 h of the first day to the 06:00 next day recirculation is disabled. Factory settings Table 1

selection 06:00-22:00 mon/tue/wed/thu/fri/sat/sun

8.x.4.3. Table 2 In this menu 3 time intervals can be set (3 start (green fields) and 3 stop (red fields)) for each day of the week in which recirculation pump will work according the set work/pause times. Factory setting: recirculation is enabled from 06:00 h to 22:00 h every day of the week. From 22:00 h of the first day to the 06:00 next day recirculation is disabled. Factory settings Table 2

Technical instructions Cm-SOL

selection 06:00-22:00 mon/tue/wed/thu/fri/sat/sun

67

Installation, legionella

8.x. LEGIONELLA PROTECTION 8.x. Legionella protection In this menu are additional menus for setting the tank disinfection ie. legionella protection.

L L L

8.x.1. Legionella protection In this menu legionella protection function can be enabled or disabled. All set times, schedule and temperatures are remaining as they were set. selection

Facotry settings Legionella protection

OFF

OFF/ON

8.x.2. Protection temperature Legionella bacteria lives and develops in places with poor or without circulation in water temperature between 20°C and 55°C. In higher temperature bacteria is slowly dying and over 70°C dies instantly. For efficient protection from the bacteria, temperature in tanks and pipelines must be for some time over 65°C for efficient disinfection. Set protection temperature is measures upper tank 1 sensor.

Factory settings Protection temp.

min./max. unit. 70

60 / 90

°C

8.x.3. Schedule In this menu are additional menus for setting the schedule for legionella protection. Schedule can be disabled or select one of the two tables with set time intervals for enabled and disabled function.

8.x.3.1. Schedule In this menu schedule can be enabled/disabled and select one of two tables according to which Legionella protection will work. NOTE: in case Schedule is disabled Legionella protection will NOT work until one of two tables with set time intervals is selected. If DHW tank has larger volume or conventional heating source is weak, depending of the tank heating speed, it’s necessary to adjust legionella protection time. selection

Factory settings Schedule

Table 1

OFF/Table 1/Table 2

8.x.3.2. Table 1 In this menu 3 time intervals can be set (3 starts (green fields) and 3 stops (3 red fields)) for each day of the week when Legionella protection will work. Factory setting: Legionella protection is active one day of the week (Monday) from 02:00 to 03:00 h. selection

Factory settings Table 1

68

02:00-03:00

mon

Technical instructions Cm-SOL

Installation, legionella 8.x.3.3. Table 2 In this menu 3 time intervals can be set (3 starts (green fields) and 3 stops (3 red fields)) for each day of the week when Legionella protection will work. Factory setting: Legionella protection is active one day of the week (Monday) from 02:00 to 03:00 h. selection

Factory settings Table 2

02:00-03:00

mon

8.x.4. Choose source In this menu conventional heating source for tank disinfection according the schedule and temperature must be set. Selected heating source must be able to achieve set temperature in set schedule time (in menu are displayed only set convencional heating sources). selection

Facotry settings Choose source

El. heater

El. heater/Boiler 1/Boiler 2

example: configurated 3 conventional sources 8.x.5. Skip legionella time In this menu Skip legionella time function can be enabled or disabled. In case function is enabled and in time interval between two legionella protection activation, temperature and time of the protection function is reached, next interval for protection is skipped and next time interval is scheduled. selection

Factory settings Skip legionella time

OFF

OFF/ON

8.x.6. Disinfection time Setting the duration of water temperature that must be above set Protection temp. to have succesfull disinfection. Factory settings Disinfection duration

min./max. unit. 15

1 / 1440 min

8.x.7. Recirculation legionella In this menu DHW recirculation can be enabled/disabled when Legionella protection function is active to disinfect pipeline (circulation must be set in the system). When conventional heating source is started, recirculation pump is also started and works until disinfection is finished. NOTE: recirculation must be set and enabled in the installation menu. selection

Factory settings Recirculation leg.

Technical instructions Cm-SOL

OFF

OFF/ON

69

Installation, energy measuring

8.x. ENERGY MEASURING 8.x. Energy measuring In this menu are additional menus for setting the energy measuring functions. Energy is calculated according to temperatures from collector sensor, return flow sensor and written or measured current flow of glicol in the solar system. If return flow temperature sensor isn’t installed, for energy calculation is used with temperature of lower sensor of the currently active tank. example: configurated 2 collector fields, flowmeter

NOTE: energy measurement without return flow sensor installed and without flowmeter will be less accurate than with them. NOTE: input of gained solar energy and statistic is on the controller screen is done by intervals of 1 kWh! Interval of drawing gained solar energy in the graphical view of the statistic depend of the amount installed collectors ie. flow through collectors.

8.x.x. Flowmeter In this menu are additional menus for setting the characteristic of the flowmeter. NOTE: energy measuring with installed flowmeter is more accurate than manual input of the flow because always is used correct flow for the calculation (important with modulating pumps).

8.x.x.1. Flow meter In this menu flowmeter can be enabled or disabled. All set values remain like were set before. selection

Factory settings Flowmeter

OFF

OFF/ON

8.x.x.2. Flowmeter constant Setting of the measuring unit of flowmeter. selection

Factory settings

Flowmeter constant ml/impuls ml/imp. / l/imp.

8.x.x.3. Volume/impuls Input of the measured volume per impulse which provides flowmeter. Factory settings Volume per impuls

min./max. unit. 1

1 / 65000

-

8.x.x.4. Flowmeter sensor address Setting the address of input where flowmeter is connected (one free address of 10 possible). Factory settings

selection

Flowmeter sen. add. Not exist Not exist/T1/.../T10

70

Technical instructions Cm-SOL

Installation, energy measuring 8.x.x. Collector 1 flow In case flowmeter isn’t installed, precise flow through collector field 1 must be entered. NOTE: Solar pump must work at 100% power on set flow (flow regulator) and flow must be precisely read from the flowmeter (on pump group) and entered into controller. In case that flow isn’t correct, controller will wrongly measure gained solar energy! Factory settings Collector 1 flow

min./max. unit. 1.00

0.01/60.00 l/min

8.x.x. Collector 2 flow In case flowmeter isn’t installed, precise flow through collector field 2 must be entered. NOTE: Solar pump must work at 100% power on set flow (flow regulator) and flow must be precisely read from the flowmeter (on pump group) and entered into controller. In case that flow isn’t correct, controller will wrongly measure gained solar energy! Factory settings Collector 2 flow

min./max. unit. 1.00

0.01/60.00 l/min

8.x.x. Glycol type In this menu used glycol type must be set for correct calculation of gained solar energy. Factory settings Glycol type

setting Propylene gly. Ethylene gly./Propylene gly.

8.x.x. Mixing In this menu percentage of glycol in mixing of water and glycol in solar system must be precisely set for best calculation of gained solar energy. Factory settings Mixing

Technical instructions Cm-SOL

min./max. unit. 40

10 / 70

%

71

Installation, manual test

8.x. MANUAL TEST 8.x. Manual test Depending of set components and their outputs, in manual test all enabled outputs can be tested. NOTE: number and type of menus depends of enabled outputs in installation menu.

M M M example: configurated 2 tanks with pumps, 1 conventional heating source, 1 electric heater, recirculation pump and mixing pump

8.x.x. Manual test pump S1 Pressing the START button output is enabled (in this case tank 1 pump), and by pressing the STOP button, output is disabled (in this case tank 1 pump). With button BACK previous screen is displayed. When Manual test is on, mark for the Manual test function (M) is yellow.

1 kol.polje / cijevni kol. / 1 sprem. PTV / 1 AKU spremnik / pumpe / električni grijač / kotao1 / miješanje/dogrijavanje / mjerač protoka / osjetnik povratnog voda / recirkulacija

72

Depending on the selected output, with buttons START and STOP outputs are manually enabled or disabled.

Technical instructions Cm-SOL

Installation, save/load

8.x. SAVE/LOAD 8.x. Save/Load In this menu are additional menus for saving and loading changed parameters and resetting to the factory setting. 8.x.1. Factory setting Reset all parameters to the factory setting. After reset to factory setting previously saved files remains (user and advanced) and they can be loaded after reset. Also, statistic remains as before reset to factory setting. After pressing the facotry setting, current setting can (but don’t have to) be saved in new or already saved file (saving is done into service save file). After this, loading of factory setting must be confirmed by entering PIN 0000 two times (same PIN for installation menu). If done correctly, message that factory setting is loaded appears. After factory setting is loaded, controller must be switched off and back on on the main switch. Factory set scheme: 1 collector field of vacuum tube collectors, 1 DHW tank with upper and lower sensors.

8.x.2. Save Saving current service files (settings). File can be saved to new or existing name. File names can have upper or lower case, numbers and signs up to max. lenght of 24 characters. Pressing the button with arrow, upper/lower/signs input type can be switched (upper right corner).

8.x.3. Load Load previously saved service files (settings).

8.x.4. DELETE Delete previously saved files. Currently active files can’t be deleted (files that have pushpin symbol on the icon). Service files can be deleted only in installation menu (under PIN).

Technical instructions Cm-SOL

73

Installation,information

8.x. INFO 8.x. Info In this menu are additonal menus for informations regarding system and software.

8.x.1. Statistics In this menu are additional menus regarding statistic data of solar system.

8.x.1.1. Display numbers View of the statistics for working of each individual output (in minutes of work) and total energy gained (in kWh/MWh).

8.x.1.2. Display graphs In this menu are additional menus for graphical view of the statistic data: received energy graphs and temperatures graph (24 and 48 h).

8.x.1.2.1.Energy graphs In this menu are additional menus for graphical view of received energy. If columns doesn’t fit in the graph screen, graph area can be increased or decreased with multiplier. Received energy can be viewed by months in period of one year.

8.x.1.2.1.1. Multiplier If columns of received energy doesn’t fit to the graph screen, graph area can be increased or decreased (x1, x2, x3, x5, x10) (multiplication of axis by energy) with the multiplier. 8.x.1.2.1.2. 12 month energy As solar energy is received, a current month graph it’s automaticaly drawn. On this view is always possible to see received energy for period of one year by intervals of one month.

74

Technical instructions Cm-SOL

Installation, information 8.x.1.2.2. Temperatures In this menu are additional menus for graphic view of the temperatures from installed sensors. 8.x.1.2.2.1. 24h temperatures Diagram of temperatures of configurated sensors in 24 h. 8.x.1.2.2.2. 48h temperatures Diagram of temperatures from configurated sensors in 48 h.

8.x.2. Software version In this menu are software version of controller and WiFi ID of the Cm WiFi-box: - current software version of the regulation - if connected, WiFi ID of the Cm WiFi-box

8.x.3. Current configuration In this menu current system configuration is displayed. 1. K x - number of boilers (0, 1, 2) 2. C x - number of collector fields (1, 2) 3. S x - number of tanks (1, 2, 3, 4) 4. B x - number of pools (0, 1) 5. H x - hydraulic connection (1 (Pump), 2 (Zone valve 2-way), 3 (Zone valve 3-way)) example: configurated: 1 boiler, 1 collector field, 2 tanks, 1 pool, hydraulic connection zone 3-way valve 8.x.4. Current file In this menu current selected file is displayed. Controller is working according to this file. Selected and active can be or configuration saved by serviceman (under PIN) or configuration saved by user.

Technical instructions Cm-SOL

75

Installation, information 8.x.5. Change of glycol Depending of the work of solar system and glycol manufacturer recommendation, glycol in the solar system must be replaced regulary (offten overheating of the glycol (steam in the collectors) results with faster glycol aging and it’s geting thicker, which results with lower collector efficiency and in the end it can result with clogging of the collector). Recommendation is to replace the glycol every 2 years. After glycol replacing in the solar system, counter in the menu -> 8.12.2. Reset glycol counter must be reset, which restarts time interval of 2 years, after which warning for glycol replacement is displayed. NOTE: Warning for glycol replacement appears after 2 years from last counter reset. When warning appears solar system works normally, only warning is active until of the counter is resetted. Glycole counter reset menu is under installation menu -> 8.12.2. Reset glycole counter

8.x.6. History In this menu are informations regarding history of errors, warnings and informations in chronological order of occurrence (in user menu errors are separated from warnings). With mark of error/warning/information displayed is it’s full name, date and time of occurence and error code. By pressing the error/warning/information area detailed description is displayed with possible correction solution. After 50. input, oldest input is deleted when new occurs. History of the errors/warnings/informations can’t be deleted.

8.x.7. Enterance log In this menu log of entry to the installation menu (under PIN) is displayed (date and time).

76

Technical instructions Cm-SOL

Installation, internet supervision

8.x. INTERNET SUPERVISION 8.x. Internet supervision Controller automaticaly recognizes when Cm WiFi-box module is connected and in user and installation menus (under PIN) is new menu for Internet supervision displayed. In this menu internet supervision or supervision+control through WiFi network can be enabled/disabled, WiFi network name and password can be entered, time syncronisation can be enabled/disabled, time zone can be set and manual connection reset can be done. User can install and commision set Cm WiFi-box by himself. 8.x.1. WiFi module commision In this menu Cm WiFi-box module can be enabled or disabled. Factory settings WiFi module

selection OFF

OFF/ON

8.x.2. Internet supervision In this menu internet supervision can be enabled/disabled and select Internet supervision (without possibility to change parameters) or select Internet supervision+control (parameters can be changed). selection

Factory settings

Internet supervision Sup.+control OFF/Sup./Sup.+control

8.x.3. WiFi network name In this menu WiFi network name to which Cm WiFi-box will connect must be entered. Possible is to enter 31 character, with upper and lower case, numbers and symbols. NOTE: Insert correct network name, with paying attention to the upper and lower case, numbers and symbols.

8.x.4. WiFi password In this menu WiFi password at the network to which Cm WiFi-box will connect must be entered. Possible is to enter 31 characters, with upper and lower case, numbers and symbols. NOTE: Insert correct network password, with paying attention to the upper and lower case, numbers and symbols. 8.x.5. Time syncronisation In this menu controller time syncronisation with server time can be enabled/disabled. selection

Factory settings Time sync.

ON

OFF/ON

8.x.6. Time zone In this menu time zone can be set according to controller installation location. Factory settings Time zone

Technical instructions Cm-SOL

min./max. unit. 1h

-12 / 14

h

77

Installation, internet supervision, counters reset 8.11.7. Connection reset In this menu internet connection can be manually reset. In case of data sending to web server is blocked, connection can be manually reset.

CM WiFi-box requires active DHCP server of Access Point (e.g. router) because manual setting of network parameters is not possible. For more informations contact administrator of your home network.

For detailed setting of the Cm WiFi-box see technical instructions for Cm WiFi-box received with module.

8.12. RESET COUNTERS 8.12. Reset counters In this menu are additional menus for gained solar energy counters reset and reset of the glycol counter (glycol replacement).

8.12.1. Reset energy counter In this menu counter of total gained solar energy from collectors can be reset to 0.

8.12.2. Reset glycol counter In this menu counter of the solar system glycol replacement interval can be reset to 0. After reset, counter start to count time of 2 years after which warning (reminder) for glycole replacement is active again. Counter can be reset without warning appearing on the screen. When glycole replacement warning appears on the screen, glycole in the solar system must be replaced with new one and reset the counter so after 2 years warning will appear again.

78

Technical instructions Cm-SOL

Errors

ERRORS LIST ERROR

E1

E2

E3

E4

E5

E6

NAME

COLLECTOR 1 SENSOR

DESCRIPTION Possible cause: interruption in el. wires between sensor and controller, contact on the regulation, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Collector/tank pump doesn’t work. Troubleshooting: Check sensor installation position, check damage / function of the sensor and (silicone) cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor.

COLLECTOR 2 SENSOR

Possible cause: interruption in el. wires between sensor and controller, contact on the regulation, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Collector/tank pump doesn’t work. Troubleshooting: Check sensor installation position, check damage / function of the sensor and (silicone) cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor.

TANK 1 UPPER SENSOR

Possible cause: interruption in el. wires between sensor and controller, contact on the regulation, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Regulation works without tank that has sensor error, electric heater/pump of conventional heating source (boiler) doesn’t work. Troubleshooting: Check sensor installation position, check damage / function of the sensor and cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor.

TANK 1 LOWER SENSOR

TANK 2 UPPER SENSOR

TANK 2 LOWER SENSOR

Technical instructions Cm-SOL

Possible cause: interruption in el. wires between sensor and controller, contact on the controller, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Controller works without tank that has sensor error. Troubleshooting: Check sensor installation position, check damage / function of the sensor and cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor.

Possible cause: interruption in el. wires between sensor and controller, contact on the controller, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Controller works without tank that has sensor error. Troubleshooting: Check sensor installation position, check damage / function of the sensor and cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor.

Possible cause: interruption in el. wires between sensor and controller, contact on the controller, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Controller works without tank that has sensor error. Troubleshooting: Check sensor installation position, check damage / function of the sensor and cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor.

79

Errors

E7

E8

E9

E10

E11

E12

80

TANK 3 UPPER SENSOR

TANK 3 LOWER SENSOR

TANK 4 UPPER SENSOR

TANK 4 LOWER SENSOR

Possible cause: interruption in el. wires between sensor and controller, contact on the controller, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Controller works without tank that has sensor error. Troubleshooting: Check sensor installation position, check damage / function of the sensor and cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor.

Possible cause: interruption in el. wires between sensor and controller, contact on the controller, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Controller works without tank that has sensor error. Troubleshooting: Check sensor installation position, check damage / function of the sensor and cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor.

Possible cause: interruption in el. wires between sensor and controller, contact on the controller, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Controller works without tank that has sensor error. Troubleshooting: Check sensor installation position, check damage / function of the sensor and cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor.

Possible cause: interruption in el. wires between sensor and controller, contact on the controller, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Controller works without tank that has sensor error. Troubleshooting: Check sensor installation position, check damage / function of the sensor and cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor.

BOILER 1 SENSOR

Possible cause: interruption in el. wires between sensor and controller, contact on the controller, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Conventional heating source pump doesn't work. Troubleshooting: Check sensor installation position, check damage / function of the sensor and cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor.

BOILER 2 SENSOR

Possible cause: interruption in el. wires between sensor and controller, contact on the controller, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Conventional heating source pump doesn't work. Troubleshooting: Check sensor installation position, check damage / function of the sensor and cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor.

Technical instructions Cm-SOL

Errors

E13

BACK FLOW SENSOR

E14

OUTDOOR SENSOR

E15

NOT ACTIVE

E100

COMMUNICATION ERROR WITH WIFI

Technical instructions Cm-SOL

Possible cause: interruption in el. wires between sensor and controller, contact on the controller, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Controller works normally, for energy measuring uses tank lower sensor (less accurate calculation of received energy). Troubleshooting: Check sensor installation position, check damage / function of the sensor and cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor. Possible cause: interruption in el. wires between sensor and controller, contact on the controller, cold connection or damaged sensor, set wrong sensor type at configuration. Controller status: Controller works normally, outside temperature isn’t displayed on screen. Troubleshooting: Check sensor installation position, check damage / function of the sensor and cable, check connection contacts, check sensor type (PT1000 or NTC), if there is availible free input set it for this sensor and connect sensor.

Possible cause: Damaged UTP cable or connections on mainboard of controller or WIFI-box. Controller status: Controller works normally, there isn’t connection to the web portal. Troubleshooting: Replace UTP cable, call authorized serviceman.

81

Warnings

WARNING LIST WARNING

W1

W2

W3

W4

W5

82

NAME

DESCRIPTION

FACTORY SETTINGS LOADED

Possible cause: Displayed when regulation automatically loads facotry settings because values in database are not correct. In normal circumstances this warning appears after first turning on after firmware change. Controller status: System configuration is set to factory setting, regulation doesn’t work properly. Note: Find the cause of the factory reset, configure the regulation again, call authorized serviceman.

DATE AND TIME ARE NOT SET

Possible cause: Clock is reset to 00:00 and date is reset to 01.01.2000. after controller switching off or power supply failure. Controller status: Controller works normaly but all functions that use schedule doesn’t work properly. Troubleshooting: Replace the battery (CR1220) in the display, set date and time.

REPLACE THE GLYCOL

Possible cause: Period of 2 years has passed from last glycol counter reset. Controller status: Controller works normally. Note: Reset glycol counter after replacing the glycol in solar system.

LOW SYSTEM PRESSURE

Possible cause: Airvent valve on collectors isn’t open, fluid is leaking on connections, solar system isn’t filled enough. Regulation status: Controller works normally. Note: Refill the solar system with solar fluid and airvent the system.

ALL TANKS ARE DISABLED

Possible cause: All tanks in the solar system are disabled. Controller status: Regulation works normaly. Note: Enable at least one tank for normal working of the solar system. If all tanks are disabled, collector pump doesn’t work and boiling will start in the collectors.

Technical instructions Cm-SOL

Information

INFORMATION LIST INFO.

I1-1

I1-2

I2

I3

I4

NAME

DESCRIPTION

POWER SUPPLY FAILURE

Description: Power supply failure or switching off the controller on main switch (0/1). Controller status: Information is entered into History without displaying on the screen. Time of entry is time of power failure/time of swithing off main switch. Troubleshooting: Check if the main switch is on 1, if there is power supply to the controller, if fuse is not damaged, call athorized serviceman.

POWER SUPPLY RETURN

Description: Power supply returns or swithing on the controller on main switch (0/1). Controller status: Information is entered into History without displaying on the screen. Time of entry is time of power return/time of swithing on main switch. Troubleshooting: -

MAXIMUM COLLECTOR TEMPERATURE

Description: When temperature in collectors is above maximum set collector temperature, collector pump stops to protect armature and ability to circulate because of steam. All tanks are full with energy, air in the collectors, to low flow through collectors, to many collectors, to low pressure in the solar system. Controller status: Controller works normaly, collector pump doesn’t work Note: If this information occures regulary, check for air in the solar system (collectors), pressure in the solar system, recommended flow through collectors, set temperatures in the tanks/maximum temperature of collectors. It’s recommended to enable collector cooling function and/or tank cooling function.

FREEZE PROTECTION

TANK DISINFECTION

Technical instructions Cm-SOL

Description: Information of active antifreeze protection function - low outdoor temperature. Controller status: Controller works normaly. Note: Check freezing point of the solar fluid in the system to prevent possibility of solar system damage and offten solar tank cooling.

Description: Information of active legionella protection function (Tank disinfection). Controller status: Controller works normaly. Note: Check if the legionella protection function was done.

83

Electric connection

ELECTRIC CONNECTION

Power supply 230V (F/N) 8x seminconductor outputs (pumps, valves) (O1-O8) Power supply +5V (+5V)

Relay outputs ( )

10x multifunction inputs for sensors (T1-T10) (PT1000 or NTC5k sensors tanks, boilers, collectors outdoor sensor, flow sensor and pressure sensor)

Spoj standardne pumpe (izlaz 1) / napajanja (napajanje pumpe preko triaca regulacije)

2x alarm outputs (CAL1 common) 2x izlaz 0-10V (upravljanje pumpama) (0-10V) 2x PWM output (pumps) (PWM) (not active)

230V/50Hz Earth N L example configuration: - output function 1

STANDARD PUMP Spoj PWM upravljane pumpe (PWM1) / napajanja (napajanje pumpe preko triaca regulacije)

230V/50Hz Earth N L example configuration: - output function 1 - function PWM 1

230V/50Hz

230V/50Hz Earth N L

2 3 1 1-PWM input 2-Signal

PWM PUMP

84

Spoj PWM upravljane pumpe (PWM1) / napajanja (napajanje pumpe neovisno od regulacije)

example configuration: - function PWM 1

2 3 1 1-PWM input 2-Signal

PWM PUMP

Technical instructions Cm-SOL

Tablica otpora

RESISTANCE LIST NTC PT1000 SENSOR (measuring field -30 - +400 °C) Temperature (°C)

Resis. (W)

Temperature (°C)

Resis. (W)

-30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 205 210 215 220

885 904 923 942 962 981 1.000 1.019 1.039 1.058 1.077 1.096 1.116 1.135 1.154 1.173 1.193 1.212 1.231 1.250 1.270 1.289 1.308 1.327 1.347 1.366 1.385 1.404 1.424 1.443 1.462 1.481 1.501 1.520 1.539 1.558 1.578 1.597 1.616 1.635 1.655 1.674 1.693 1.712 1.732 1.751 1.770 1.789 1.809 1.828 1.847

225 230 235 240 245 250 255 260 265 270 275 280 285 290 295 300 305 310 315 320 325 330 335 340 345 350 355 360 365 370 375 380 385 390 395 400

1.866 1.886 1.905 1.924 1.943 1.963 1.982 2.001 2.020 2.040 2.059 2.078 2.097 2.117 2.136 2.155 2.174 2.194 2.213 2.232 2.251 2.271 2.290 2.309 2.328 2.348 2.367 2.386 2.405 2.425 2.444 2.463 2.482 2.502 2.521 2.540

Technical instructions Cm-SOL

RESISTANCE LIST NTC 5k/25°C SENSOR (measuring field from -20 - +130 °C) Temperature Resistance (°C) ( )

-20 -15 -10 -5 0 5 10 15 20 25 30 34 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130

48.534 36.465 27.665 21.158 16.325 12.694 9.950 7.854 6.245 5.000 4.028 3.266 2.663 2.184 1.801 1.493 1,244 1.041 876 740,7 629,0 536,2 458,8 394,3 340,0 294,3 255,6 222,7 190,7 170,8 150,5

85

Connecting schemes

EXAMPLES OF SELECTING THE SOLAR SYSTEM COMPONENTS collectors

Examples of selecting the solar system components 1. example: 1 flat collector field + 1 DHW tank + recirculation + electric heater + 1 oil boiler + back flow sensor

tanks

collector fields

one filed two fields

field type

vacuum tube flat plate

tank 1 type

not exist DHW BUF BUF with DHW pool

tank 2 type

not exist DHW BUF BUF with DHW pool

tank 3 type

not exist DHW BUF BUF with DHW pool

Examples of selecting the solar system components TV

Ox K1

Px

S1 Ox

Ox

EG Px

K1

Px TEHNIKA GRIJANJA

Ox

Ox

hydraulic conn.

pump zone 2-way zone 3-way

mixing/heating

not exist exist

HV

heating

tanks

boiler 1 type

not exist wood pellet/wood chips gas/oil heat pump electric boiler

one field two fields

field type

vacuum tube flat plate

tank 1 type

not exist DHW BUF BUF with DHW pool

recirculation

not exist exist

flowmeter

not exist exist

tank 2 type

not exist DHW BUF BUF with DHW pool

back flow sen.

tank 3 type

not exist DHW BUF BUF with DHW pool

hydraulic conn.

pump zone 2-way zone 3-way

mixing/heating

not exist exist

heating

not exist exist

collector fields

el. Heater installed

sensor address

not exist T1… T10

2. example: 1 vacuum tube collector field + 1 DHW tank + recirculation + electric heater + 1 accumulation tank + heating BUF/DHW + pool + back flow sensor + flowmeter

TV

Tx Px

K1

collectors

el. Heater installed

Px

Px

not exist exist

S2

S1

Px

Tx boiler 1 type

recirculation

not exist exist

flowmeter

back flow sen.

86

not exist wood pellet/wood chips gas/oil heat pump electric boiler

Tx Px

EG

MP Tx

Tx

Tx HV

Tx Px

not exist exist sensor address

not exist T1… T10

Technical instructions Cm-SOL

Connecting schemes In next pages are some of possible connecting schemes which solar regulation supports. Every tank can be DHW tank (shown in majority of schemes) or accumulation tank (buffer) or accumulation tank with build in DHW tank or on first 3 places pool. DHW tanks are serially connected - always from S1 goes to the top. On schemes options for electric heater, recirculation, heating pump, flowmeter... are NOT displayed. They can be enabled for every scheme according the description in technical manual. 2

TV

3

TV

S1

S1

Ox

Ox

Ox Px

Px Ox

Ox

K1

5

TV

TEHNIKA GRIJANJA

Ox

Ox

6

TV

Px

TV

K1

Ox

K1

K1

S2

Ox Px HV

Ox

Px

S1

Ox

K2

TEHNIKA GRIJANJA

HV

Ox

Ox

K1

Px

Px Ox

HV

4

Px

S1

Ox

Ox

TV

Ox

K1

Ox

K1

Ox

K1

1

S2

S2

S1

Ox

Ox

S1

Ox

Ox

Ox

Ox

Ox

K1

Ox

K1

K2

Px TEHNIKA GRIJANJA

TEHNIKA GRIJANJA

Px

Ox

Ox

Ox

Px

Ox

Ox

Ox

Px

Px

7

8

TV

Ox

9

TV

Px S2

Px

S1

Ox

S2

Ox

S2

S1

Ox

Px

Px

TV

Ox

K1

K1

Px

Ox Px

Ox

Px

Ox

Px

Px

K1

Ox

S1

Ox

Ox

Px

Ox

Ox

Px

Ox

K1

Ox

K1

K2

Px TEHNIKA GRIJANJA

TEHNIKA GRIJANJA

Ox

Ox

10

Ox

Ox

11

TV

Ox

S2

Px

TV

Ox K1

S2

S1

Ox

Ox Px

Ox

12

TV

Ox K1

K1

Ox

Ox

Ox

Ox

S1

Ox

S2

S1

Ox

Ox

Px

Ox

Ox

Ox

K1

Ox

K1

K2

Px TEHNIKA GRIJANJA

TEHNIKA GRIJANJA

Ox

Px

Ox

Ox

Ox

Px

13

Px

Ox

Ox

Ox

Px

TV

Ox

Ox Px

Px

Px

14

TV

Ox

Px

K1

K1

Ox

Px

S3

S2

Ox

S1

Ox

S3

S2

Ox

Ox

S1

Ox

Ox

Ox

K1

Px TEHNIKA GRIJANJA

Ox

Px

Ox

Ox

Ox

Ox

Px

Ox

Ox

Ox

Px Px Px

Px

15

TV

Ox

16

1. 1 collector+1 tank+pump 2. 1 collector+1 tank+pump+1 boiler 3. 1 collector+1 tank+pump+2 boilers

TV

Ox Px

K1

K1

Px Px

Px S3

S2

Ox

S1

Ox

S3

Ox

S2

Ox

Px

S1

Ox

Ox

Px

Ox

K1

Px TEHNIKA GRIJANJA

Ox

Ox

17

Ox

Ox

Ox

TV

18

Ox

Ox

TV

Ox

K1

K1

Ox

Ox

S3

S2

Ox

S1

Ox

S3

Ox

S2

Ox

Px

S1

Ox

Ox

Px

Ox

K1

Px TEHNIKA GRIJANJA

Ox

Px

Ox

Ox

Ox

Ox

Px

Px Px

Technical instructions Cm-SOL

Ox Px

Px

4. 1 collector+2 tanks+pumps 5. 1 collector+2 tanks+pumps+1 boiler 6. 1 collector+2 tanks+pumps+2 boilers 7. 1 collector+2 tanks+3-way valve 8. 1 collector+2 tanks+3-way valves+1 boiler 9. 1 collector+2 tanks+3-way valves+2 boiler 10. 1 collector+2 tanks+2-way valves 11. 1 collector+2 tanks+2-way valves+1 boiler 12. 1 collector+2 tanks+2-way valves+2 boilers

Ox

Ox

13. 1 collector+3 tanks+pumps 14. 1 collector+3 tanks+pumps+1 boiler 15. 1 collector+3 tanks+3-way valve 16. 1 collector+3 tanks+3-way valves+1 boiler 17. 1 collector+3 tanks+2-way valves 18. 1 collector+3 tanks+2-way valves+1 boiler

87

Sheme spajanja 19

20

TV

TV

Ox

K1

K1

Ox

S4

S3

Ox

S2

Ox

S1

Ox

S4

Ox

S3

Ox

S2

Ox

S1

Ox

Ox

Ox

K1

Px TEHNIKA GRIJANJA

Ox

Px

Ox

Ox

Ox

Ox

Ox

Px

Px

Ox

Ox

Ox

Ox

Px

Px

Px

Px

Px

21

22

TV

Ox Px

TV

Ox Px

K1

K1

Px Px

Px

Px S4

S3

Ox

S2

Ox

S1

Ox

S4

Ox

S3

Ox

Px

Px

Ox

Ox

S2

Ox

S1

Ox

Ox

Ox

K1

Px TEHNIKA GRIJANJA

Ox

23

Ox

Ox

Ox

24

TV

Ox

Ox

Ox

TV

Ox

Px

K1

K1

Ox

Ox

S4

S3

Ox

S2

Ox

S4

S1

Ox

Ox

S3

Ox

Px

S2

Ox

S1

Ox

Ox

Px

Ox

K1

Px TEHNIKA GRIJANJA

Ox

Px

Ox

Ox

Ox

Ox

Ox

Px

Px

26

TV

TV

K1

Ox Ox K2

K2

K1

Ox

Px

Ox Ox

S1

S1 Ox

Ox Px

Px

Px

Ox

K1

Px Ox

Ox

Ox

HV

27

TV

28

TV Ox Ox

S2

K2

K2

K1

Ox Ox

S2

S1 Ox

Ox

TEHNIKA GRIJANJA

Ox

HV

K1

Ox

Px

Px

Px

Ox

Px

Px

25

Ox

S1 Ox

Ox Px Px Px Px

Px Px Px Px

Ox

K1

Px TEHNIKA GRIJANJA

Ox

29

Ox

Ox

TV Px

30

TV

K1

Ox Ox

S2

K2

K2

K1

Ox Ox

S1

S2

S1

Ox Px

Ox

Ox

Px

Px

Px

Ox

K1

Px TEHNIKA GRIJANJA

Ox

Px

Ox

Ox

Ox

19. 1 collector+4 tanks+pumps 20. 1 collector+4 tanks+pumps+1 boiler 21. 1 collector+4 tanks+3-way valves 22. 1 collector+4 tanks+3-way valves+1 boiler 23. 1 collector+4 tanks+2-way valves 24. 1 collector+4 tanks+2-way valves+1 boiler

88

Px

Ox

Ox

25. 2 collectors+1 tank+pumps 26. 2 collectors+1 tank+pumps+1 boiler 27. 2 collectors+2 tanks+pumps 28. 2 collectors+2 tanks+pumps+1 boiler 29. 2 collectors+2 tanks+3-way valve 30. 2 collectors+2 tanks+3way valve+1 boiler

Technical instructions Cm-SOL

Sheme spajanja 31 K1

Ox

Px

Ox

Ox Px

32

33

TV

TV

Ox

K1

K1

Ox

S1

S1

Ox

Ox

Ox

K1

Px TEHNIKA GRIJANJA

Ox

Px

Ox

Ox Px

34

Ox

Px Px

Px

35

TV

Ox

Px

TV

Ox

Px

K1

K1

Px

Ox

Ox

Px

Px S1

S1

Ox

Ox

Px

Px

Ox

K1

Px TEHNIKA GRIJANJA

Ox

Ox

Ox

Ox

Ox

Ox

Px

36

37

TV

Ox

Px

TV

Ox

K1

K1

Px

S1

S1

Ox

Ox

Px

Px

Ox

Ox

Ox

K1

Px TEHNIKA GRIJANJA

Px

Ox

Ox Px

38

Px Px

Px

39

TV

Px

TV

Ox

K1

K1

Ox

Ox

Ox

S2

S1

Ox

S2

Ox

S1

Ox

Ox

Ox

K1

Px TEHNIKA GRIJANJA

Ox

Px

Ox

Ox

Ox

Px

Ox

Px

Ox

Ox

Px

Px

Px

40

Ox

Px

Px

41

TV

Ox

TV

Ox Px

K1

K1

Px Px

Px S2

S1

Ox

S2

Ox

S1

Ox

Px

Px

Ox

Ox

Ox

Ox

K1

Px TEHNIKA GRIJANJA

Ox

Ox

Ox

Ox

Ox

Ox

Px

42

43

TV

TV

Ox

K1

K1

Ox

Px

S2

S1

Ox

S2

Ox

S1

Ox

Px

Ox

Px

Ox

K1

Px TEHNIKA GRIJANJA

Ox

Px

Ox Px

Ox

Ox

Ox

Px Px

Px

Px

Ox

Ox Px

Px

31. 1 collector+pool 32. 1 collector+1 tank+pool+pumps 33. 1 collector+1 tank+pool+pumps+1 boiler 34. 1 collector+1 tank+pool+3-way valve 35. 1 collector+1 tank+pool+3-way valve+1 boiler 36. 1 collector+1 tank+pool+2-way valve 37. 1 collector+1 tank+pool+2-way valve+1 boiler

Technical instructions Cm-SOL

Ox

38. 1 collector+2 tanks+pool+pumps 39. 1 collector+2 tanks+pool+pumps+1 boiler 40. 1 collector+2 tanks+pool+3-way valve 41. 1 collector+2 tanks+pool+1 boiler+3-way valve 42. 1 collector+2 tanks+pool+2-way valve 43. 1 collector+2 tanks+pool+1 boiler+2-way valve

89

Commissioning list

SOLAR CONTROLLER COMMISSIONING LIST

90

Technical instructions Cm-SOL

Commissioning list

Cm-SOL 09/2018ENGv2.00

Cm-SOL controller commissioning list Basic informa on 1. Controller serial number :

.

2. User name and surname:_______________________________________________________ 3. Address / Phone:____________________________________________________________

4. Commissioned by:_____________________________________________________________ 5. Commissioning date:

.

.

.

Installa on 6. According to the technical instruc ons drill 3 holes on the controller installa on place, insert dowels, screw upper screw (to 4 mm). Remove lower controller cover, hang controller on to upper screw and with 2 lower screws fasten the controller. ………………………………..…... YES 7. Connect sensors, flowmeter, pressure sensor to the connec ng clamps (inputs T1 -T10.. YES 8. Connect pumps, valves to the connec ng clamps (outputs O1-O8)…………….…………..……. YES 9. Connect power supply to the connec ng clamps (F, N)………………………………………...……… YES 10. Install wire holder and close controller lower cover… .………………………………………….……… YES 11. Connect addi onal equipment to the UTP connector on the le controller side .

YES

NO

12. Turn on the controller on the main switch and select language. …..…………………….…….…

YES

Controller se ng

IMPORTANT!!! Menus are ac ve (dynamic) and are changed according to set configura on (menu numbers don't have to match Your current installa on)! Configura on of the solar system components 13. Configura on is done in the menu 8. Installa on ->8.Installa on->0000->Enter file name->… 8.1.1. Collectors

8.1.1.1. Collector fields

8.1.1.2. Field type

Technical instructions Cm-SOL

enter X or value one field two fields vacuum tube flat plate

91

Commissioning list

Cm-SOL 09/2018ENGv2.00

8.1.2. Tanks

8.1.3. Hea ng

92

8.1.2.1. Tank 1 type

not exist DHW BUF BUF with DHW pool

8.1.2.2. Tank 2 type

not exist DHW BUF BUF with DHW pool

8.1.2.3. Tank 3 type

not exist DHW BUF BUF with DHW pool

8.1.2.4. Tank 4 type

not exist DHW BUF BUF with DHW pool

8.1.2.5. Hydraulic connec on

pump zone 2-way zone 3-way

8.1.2.6. Mixing/Hea ng

not exist exist

8.1.3.1. El. heater installed

not exist exist

8.1.3.2. Boiler 1 type

not exist wood pellet/wood chips gas/oil heat pump electric boiler

8.1.3.3. Boiler 2 type

not exist wood pellet/wood chips gas/oil heat pump electric boiler

8.1.4. Recircula on

not exist exist

8.1.5. Flowmeter

not exist exist

Technical instructions Cm-SOL

Commissioning list

Cm-SOL 09/2018ENGv2.00 8.1.6. Back flow sensor

8.1.7.Outdoor sensor

8.1.8. Pumps/Outputs

8.1.6.1. Sensor address

not exist =T

8.1.6.2. Sensor type

PT1000 NTC

8.1.7.1. Sensor address

not exist =T

8.1.7.2. Sensor type

PT1000 NTC

8.1.8.1. Outputs func on

PWM / AI

8.1.9. Pressure control

8.2. Collectors

8.3. Spremnik

Technical instructions Cm-SOL

enter output number = pump collector 1 = pump collector 2 = pump tank 1 = pump tank 2 = pump tank 3 = pump tank 4 = pump boiler 1 = pump boiler 2 = electric heater = pump recircula on = pump pool = pump exchanger = pump mixing/hea ng = zone 3-way 1 = zone 3-way 2 = zone 3-way 3 = zone 3-way 4 = zone 2-way 1 = zone 2-way 2 = zone 2-way 3 = zone 2-way 4 not exist exist

8.2.1.4. Collector 1 sensor address

not exist =T

8.2.2.4. Collector 2 sensor address

not exist =T

8.3.2.4.1.Tank 1 upper sensor address

not exist =T

8.3.2.5.1.Tank 1 lower sensor address

not exist =T

8.3.3.4.1.Tank 2 upper sensor address

not exist =T

8.3.3.5.1.Tank 2 lower sensor address

not exist =T

93

Commissioning list

Cm-SOL 09/2018ENGv2.00

8.4. Tank hea ng.

8.7. Energy measuring

8.3.4.4.1.Tank 3 upper sensor address

not exist =T

8.3.4.5.1.Tank 3 lower sensor address

not exist =T

8.3.5.4.1.Tank 4 upper sensor address

not exist =T

8.3.5.5.1.Tank 4 lower sensor address

not exist =T

8.4.2.8. Boiler 1 sensor address

not exist =T

8.4.3.8. Boiler 2 sensor address

not exist =T

8.7.1. Flowmeter

not exist disabled enabled ml/impuls l/impuls = volume/impuls = T (flowmeter address)

8.7.2. Collector 1 flow

lit/min.

8.7.3. Collector 2 flow

lit/min.

8.7.4. Glycol type

propylene glycol ethylene glycol

8.7.5. Mixing %

%

14. With Manual test func on test all connected components. …………….………..……………….… ->8.8. Manual test 15. Write down so ware version from controller: ->8.10.2.So ware version

94

YES

So ware version:

.

16. Enter correct date and me.……………………………………………………………………………….…...... ->5.4..Date and me

YES

17. Disable language selec on at start………………….…………………………………………………..….... ->5.2.Language selec on->OFF

YES

18. Reset glycol counter (a er filling the solar system with new glycol) ………………….…..…... ->8.12.2. Reset glycol counter

YES

Technical instructions Cm-SOL

Commissioning list

Cm-SOL 09/2018ENGv2.00 Next points enable and configure according the set system and customer demands

19. Enable and set Puls start collector……………………………..…………………….……………. ->8.2.1.3. Puls collector start

YES

NO

20. Enable and set Collector cooling………..…………………………………….……………………. ->8.2.2. Collector cooling

YES

NO

21. Enable and set An freeze protec on of the collector… ..………….……………………. ->8.2.3. An freeze protec on

YES

NO

22. If there are more tanks, enable and set Priority test………………………………..……. ->8.3.6. Priority test

YES

NO

23. Enable and set Tank cooling……………………………………………….…………….……………. ->8.3.7. Tank cooling

YES

NO

24. Enable and set DHW hea ng………………………………….……………………………….………. ->8.4. DHW hea ng

YES

NO

25. Enable and set Recircula on…………..…………………….…………………………….……………. ->8.5. Recircula on

YES

NO

26. Enable and set Legionella protec on..………………………………….…………….……………. ->8.6. Legionella protec on

YES

NO

27. If Cm WiFi-box (addi onal equipment) is installed, enter local WiFi network name and password to which it will be connected……………………………………………………………. YES ->8.11. Internet supervision

NO

28. Save made changes in ‘Service parameters’ ->8.Installa on->PIN->0000->8.9.Save/Load->8.9.2.Save ………………………..….……….….….

YES

29. According to customer’s demands set the: temperatures, differences, schedules

YES

NO

30. Save made changes to user file: ->6.Save/Load->6.1.Save ………………………………………………………………………………………..…….

YES

31. Inform the user with controller technical instruc ons ………………………..…………….…….….

YES

32. Notes regarding the commissioning: _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________

Technical instructions Cm-SOL

95

Centrometal d.o.o. shall not be responsible for possible incorrect data caused by printing errors or error made in transcription and all figures and diagrams are for explanatory purposes only and relevant adjustment have to be made at the spot. In any case, it reserves the right to modify its products as deemed to be required and useful without any prior notification.

Centrometal d.o.o. Glavna 12, 40306 Macinec, Croatia central tel: +385 40 372 600, fax: +385 40 372 611 service tel: +385 40 372 622, fax: +385 40 372 621

HEATING TECHNIQUE