Centrometal BioTec-L Technical Instructions

* The preview only show first 10 pages of manuals. Please download to view the full documents.

Loading preview... Please wait.

Manuals information


Report / DMCA this file

Description

Hot water boiler

Manuals Content

HEATING TECHNIQUE Centrometal d.o.o. - Glavna 12, 40306 Macinec, Croatia, tel: +385 40 372 600, fax: +385 40 372 611

Technical instructions using REGULATION of hot water boiler BioTec-L

v2.35L xxkW

Français

Portugues

Slovenski

Srpski

Čeština

Hrvatski

English

Italiano

Deutsch

Magyar

Nederlands

Espanol

THE FIRST START-UP MUST BE DONE BY AUTHORIZED PERSON OTHERWISE PRODUCT WARRANTY IS NOT VALID

BioTec-L TURBT-L-02-2015 - v2.35L- eng



Screen SWITCHING ON After turning on the main switch, screen will display language selection menu and software version. To select the language, press the flag of language you want.

Software version Boiler power (25, 34, 45 kW)

v2.35L xxkW

Français

Portugues

Slovenski

Srpski

Čeština

Hrvatski

English

Italiano

Deutsch

Magyar

Nederlands

Espanol

Language selection

If the language selection is "disabled" (display > language sel > disabled), initial message wil appear in the screen as long as the set in the menu "Welcome time" (display > welcome time).

Software version v2.35 L XX kW

Boiler power (25, 34, 45 kW) Button’’OK’’

5

2

Initial message duration (countdown)

Technical instructions REGULATION BioTec-L

Main Menu, Buttons MAIN MENU The main menu is used to select the desired submenu. To select a specific menu you must press the appropriate icon on the screen. To switch between the ’’Main menu’’ and ’’Boiler working display’’ press the button ’’Display selection’’. To switch between graphic and numeric display of the boiler using press ’’Boiler operation display’’. 02:11

Temperature

History

File

Time Display selection: Main menu / work

Operation

Boiler operation display : graphic / numeric Date & Time

Display

Info

Glow

OFF

State of the current boiler status Installation

Start/stop boiler

Cleaning

BUTTONS Button ’’ON / OFF’’ options: on / off boiler operation’’

Button ’’OK’’

Button ’’DISPLAY SELECTION’’ options: main menu / work

Button ’’START’’/’’STOP’’

Button ’’BOILER OPERATION DISPLAY’’ options: graphic / numeric

Navigation buttons: ’’LEFT’’, ’’RIGHT’’, ’’UP’’, ’’DOWN’’

Button ’’ENTER’’

Button ’’DELETE’’

Button ’’BACK’’

Button ’’FACTORY SETTINGS’’

Button’’PREVIOUS SCREEN’’

Button ’’INFORMATION’’

Button ’’NEXT SCREEN’’

Technical instructions REGULATION BioTec-L

Button ’’COPY’’

Button ’’PASTE’’

3

Screen, Symbols

SYMBOLS

11

10 1 5

xx°C

15

12 xx°C

x%

14 05:08

xx °C

6 7

0

8

0.0%

xx°C

OFF

0.0%

13 9

xx°C

xx°C

3 1 2 3 4

5 6 7 8

4

2

- Boiler BioTec-L - Buffer tank - Boiler pump P1 - 3-way thermic valve or 3-way mixing valve with motor drive (protection valve) - Symbol of fan operation (when working, symbol is turning) - Fan speed (rpm) - Curent position of primary air actuator - Current position of secondary air actuator

4

9 - Combustion chamber temperature 10 - Flue gas temperature sensor 11 - The percentage of oxygen in the flue gases 12 - Outer temperature sensor 13 - Glow indicator (if enabled) 14 - The symbol in this section depend ont the selected configuration 15 - Boiler temperature

Technical instructions REGULATION BioTec-L

Configuration

CONFIGURATION (authorized persons only) 02:11

Temperature

History

File

Operation

Date & Time

Display

Info

Glow

OFF

Cleaning Installation

Enter PIN * * * *

For entry into Configuration menu press ”Installation“ button. When you press ”Installation“ button control unit ask for pin. Enter pin and confirm it by presing “Enter“ button. 9. Installation 1.

2.

3.

4.

Configuration Temperature Lambda probe Stabilization

5.

6.

7.

8.

Power D1 Power D2 Power D3 Power D4

In installation menu press ”Configuration“ button to enter into «Configuration» menu.

Technical instructions REGULATION BioTec-L

5

Configuration Configuration menu: 9.1.1. Configuration

9.1.1. Configuration

Radiator h.

Corrector

Floor h.

Motor drive

Room thermo.

Protection valve 2.Heating Cir.

DHW

9.1.1. Configuration

Protection valve

2.Circ. Room t.

2.Heating Cir.

Configure the system by selecting installed components! Some components exclude others (eg. you can choose radiator heating or floor heating, not both of them), some components can be selected only with another component (eg. room thermostat can be selected only if you select radiator h. or floor h., if you don't select this component room thermostat can't be selected).

When the configuration contains motor drive, you need to enter VALVE TIME. This parameter defines how many seconds is required for mixing valve opening/closing. THIS NUMBER MUST CORRESPOND EXACTLY TO THE TIME IT TAKES THE MOTOR DRIVE TO OPEN THE VALVE (DEPENDS ON THE TYPE OF MOTOR) Valve time 120

9.1.1. Configuration

120 sec

File

Radiator h.

Corrector

Choosing this configuration, you Floor h.set 3-way valve Room thermo. should time! Info

6

Technical instructions REGULATION BioTec-L

Configuration 1

GENERAL CONNECTION SCHEMES CONFIGURATION In ”Tecnical instructions for installation of hot water boiler BioTec-L” are showned general connection schemes. Configuration 1: (Basic configuration) On this configuration all compontents are unselected. 9.1.1. Configuration

9.1.1. Configuration

Radiator h.

Corrector

Floor h.

Motor drive

Room thermo.

Protection valve

DHW

2.Heating Cir.

9.1.1. Configuration

Protection valve

2.Circ. Room t.

2.Heating Cir.

On display is displayed:

3 xx°C

1

xx°C

x%

05:08

xx °C

0

xx°C

0.0% OFF

0.0%

xx°C

xx°C

1 2 3 4

- Boiler BioTec-L 2 4 - Buffer tank - Outer temperature sensor - Return flow protection by 3-way termostatic valve (60°C) VTC 531 (60°C), LTC 141 (60°C) or laddomat 21 (63°C)

Technical instructions REGULATION BioTec-L

7

Configuration 2 Configuration 2 is from scheme 4 and scheme 5 from ”Tecnical instructions for installation of hot water boiler BioTec-L” In this configuration the following components are selected: - radiator heating, corrector, motor drive (heating circuit), DHW (domestic hot water) 9.1.1. Configuration

9.1.1. Configuration

Radiator h.

Corrector

Floor h.

Motor drive

Room thermo.

DHW

Protection valve 2.Heating Cir.

9.1.1. Configuration

Protection valve

2.Circ. Room t.

2.Heating Cir.

On display is displayed: 1 xx°C

8

7

-°C

x%

11

5 3

6

05:08

xx°C

20.0°C

4

20.0-0.0°C

xx °C

25.0°C

0

xx°C

0.0% xx°C

0.0%

xx°C

xx°C

10

2

9

OFF

1 2 3 4 5 6 7 8

- Boiler BioTec-L - Buffer tank - Outer temperature sensor - Heating etage (radiator h.) - Room corrector - Heating pump P3 - Main flow sensor - Mixing valve with el. actuator of heating circuit (motor drive) 9 - DHW boiler 10 - DHW pump P2 11 - Day/night temperature indicator

In this configuration, on the previous screen, a new button is displayed (Pump DHW continously) 9.1.2. Pump DHW continously factory: ON OFF

9.1 Configuration 1.

Configuration

OFF 2.

Pump DHW continously

ON

When DHW sensor (ERROR 1) occurs, regulation cannot automatically turn ”ON/OFF“ DHW pump. For intervention work serviceman can turn ”ON“/“OFF“ DHW pump manually. In this case, the pump DHW work all the time until serviceman manually turn it ”OFF“. 8

Technical instructions REGULATION BioTec-L

Configuration 3 Configuration 3 is from scheme 6 from ”Tecnical instructions for installation of hot water boiler BioTec-L” In this configuration the following components are selected: - protection valve (return flow protection) 9.1.1. Configuration

9.1.1. Configuration

Radiator h.

Corrector

Floor h.

Motor drive

Room thermo.

Protection valve 2.Heating Cir.

DHW

9.1.1. Configuration

Protection valve

2.Circ. Room t.

2.Heating Cir.

On display is displayed: 3 05:08 xx°C

1

x%

xx°C

xx °C

0

xx°C

0.0% OFF

0.0% -°C xx°C

xx°C

5

4

1 - Boiler BioTec-L 2 - Buffer tank 3 - Outer temperature sensor Technical instructions REGULATION BioTec-L

2

4 - Mixing valve with el. actuator (return flow protection) (protection valve) 5 - Return flow sensor 9

Configuration 4 Configuration 4 is from scheme 7 from ”Tecnical instructions for installation of hot water boiler BioTec-L” In this configuration the following components are selected: - protection valve (return flow protection) - DHW (domestic hot water) 9.1.1. Configuration

9.1.1. Configuration

Radiator h.

Corrector

Floor h.

Motor drive

Room thermo.

DHW

Protection valve 2.Heating Cir.

9.1.1. Configuration

Protection valve

2.Circ. Room t.

2.Heating Cir.

On display is displayed:

1

3 05:08

xx°C

x%

xx°C

xx °C

0

xx°C

0.0% xx°C

0.0% -°C xx°C

xx°C

5

4

2

7

OFF

1 2 3 4

- Boiler BioTec-L - Buffer tank - Outer temperature sensor - Mixing valve with el. actuator (return flow protection) (protection valve) 5 - Return flow sensor 6 - DHW tank 7 - DHW pump

6

In this configuration, on the previous screen, a new button is displayed (Pump DHW continously) 9.1.2. Pump DHW continously factory: ON OFF

9.1 Configuration 1.

Configuration

OFF 2.

Pump DHW continously

ON

When DHW sensor (ERROR 1) occurs, regulation cannot automatically turn ”ON/OFF“ DHW pump. For intervention work serviceman can turn ”ON“/“OFF“ DHW pump manually. In this case, the pump DHW work all the time until serviceman manually turn it ”OFF“. 10

Technical instructions REGULATION BioTec-L

Configuration 5 Configuration 5 is from scheme 8 and 9 from ”Tecnical instructions for installation of hot water boiler BioTec-L”. In this configuration the following components are selected: radiator heating, corrector motor drive (heating circuit), 2.Heating Circuit, 2.Circuit room thermostat 9.1.1. Configuration

9.1.1. Configuration

Radiator h.

Corrector

Floor h.

Motor drive

Room thermo.

Protection valve

DHW

2.Heating Cir.

9.1.1. Configuration

Protection valve

2.Circ. Room t.

2.Heating Cir.

On display is displayed:

xx°C

1

8

7

-°C

x%

11

5 3

6

20.0°C

4 05:08

xx°C 20.0-0.0°C

xx °C

25.0°C

0

xx°C

0.0% OFF

0.0%

xx°C

xx°C

2

1 2 3 4 5

- Boiler BioTec-L - Buffer tank - Outer temperature sensor - Heating etage (radiator h.) - Room corrector

10

6 - Heating pump P3 (circuit 1) 7 - Main flow sensor 8 - Mixing valve with el. actuator of heating circuit (motor drive)

Technical instructions REGULATION BioTec-L

9

9 - Heating pump (circuit 2) 10 - Room thermostat (circuit 2) 11 - Day/night temperature indicator 11

Configuration 6 In this configuration the following components are selected: - floor heating - motor drive (heating circuit) 9.1.1. Configuration

9.1.1. Configuration

Radiator h.

Corrector

Floor h.

Motor drive

Room thermo.

Protection valve

DHW

2.Heating Cir.

9.1.1. Configuration

Protection valve

2.Circ. Room t.

2.Heating Cir.

On display is displayed:

xx°C

1

8 x%

7

6

-°C

3 20.0°C

5 xx°C

4 02:08

xx °C

0

xx°C

0.0% OFF

0.0%

xx°C

xx°C

1 2 3 4 5

2 - Boiler BioTec-L - Buffer tank - Outer temperature sensor - Heating etage (floor h.) - Day/night temperature indicator

12

6 - Heating pump P3 7 - Main flow temperature sensor 8 - Mixing valve with el. actuator of heating circuit (motor drive)

Technical instructions REGULATION BioTec-L

Configuration 7 In this configuration the following components are selected: - radiator heating - room corrector 9.1.1. Configuration

9.1.1. Configuration

Radiator h.

Corrector

Floor h.

Motor drive

Room thermo.

Protection valve

DHW

2.Heating Cir.

9.1.1. Configuration

Protection valve

2.Circ. Room t.

2.Heating Cir.

On display is displayed:

xx°C

1

5 3

6

7

05:08

xx°C

x%

4

20.0-0.0°C

xx °C

25.0°C

0

xx°C

0.0% OFF

0.0%

xx°C

xx°C

2

1 2 3 4 5

- Boiler BioTec-L - Buffer tank - Outer temperature sensor - Heating etage (radiator h.) - Room corrector

6 - Heating pump P3 7 - Day/night temperature indicator

Technical instructions REGULATION BioTec-L

13

Temperatures 1. TEMPERATURES

02:11

Temperature

History

File

Operation

Date & Time

Display

Info

Glow

Installation

Cleaning

OFF

To enter in Temperature menu press ”Temperature“ button. Content of this menu depends on selected configuration.

1. Temperature 1.

2.

Boiler temp. Diff. Boiler

Items located within this framework depends on the selected configuration

14

Technical instructions REGULATION BioTec-L

Temperatures

1.1 BOILER TEMPERATURE 1.1 Boiler temp. 85

1. Temperature 1.

2.

Boiler temp. Diff. Boiler

85 °C

5.

Differential of DHW

6.

Heating circuit M.D

3.

Min buf.tank temp.

4.

DHW temp.

Possible selection: - factory: 85 °C - Minimum: 75 °C - Maxsimum: 90 °C The possibility of setting boiler working temperature

1.2 DIFFERENTIAL OF BOILER TEMPERATURE 1.2 Diff. Boiler 5

1. Temperature 1.

2.

Boiler temp. Diff. Boiler

5 °C

5.

Differential of DHW

6.

Heating circuit M.D

3.

Min buf.tank temp.

4.

DHW temp.

Possible selection: - factory: 5 °C - Minimum: 5 °C - Maxsimum: 7 °C The possibility of setting differential of boiler temperature.

1.3 MINIMUM BUFFER TANK TEMPERATURE 1.3. Min buf.tank temp. 20 20 °C

1. Temperature 1.

2.

Boiler temp. Diff. Boiler

5.

Differential of DHW

6.

Heating circuit M.D

3.

Min buf.tank temp.

4.

DHW temp.

Possible selection: - factory: 20 °C - Minimum: 5 °C - Maxsimum: 64 °C The possibility of setting minimum buffer tank temperature Technical instructions REGULATION BioTec-L

15

Temperatures

1.4 DOMESTIC HOT WATER TEMPERATURE 1.4 DHW temp. 50

1. Temperature 1.

2.

Boiler temp. Diff. Boiler

50 °C

5.

Differential of DHW

6.

Heating circuit M.D

3.

Min buf.tank temp.

4.

DHW temp.

Possible selection: - factory: 50 °C - Minimum: 40 °C - Maxsimum: 80 °C The possibility of setting domestic hot water temperature.

1.5 DOMESTIC HOT WATER DIFFERENCE 1.5 Differential of DHW 5 5 °C

1. Temperature 1.

2.

Boiler temp. Diff. Boiler

5.

Differential of DHW

6.

Heating circuit M.D

3.

Min buf.tank temp.

4.

DHW temp.

Possible selection: - factory: 5 °C - Minimum: 4 °C - Maxsimum: 40 °C The possibility of setting domestic hot water difference.

16

Technical instructions REGULATION BioTec-L

Temperatures

1.6 TEMPERATURES IN HEATING CIRCUIT MOTOR DRIVE This option is only available when configuration contains motor drive.

1. Temperature 1.

2.

Boiler temp. Diff. Boiler

5.

Differential of DHW

6.

Heating circuit M.D

3.

Min buf.tank temp.

4.

DHW temp.

1.6.1 HEATING CIRCUIT MOTOR DRIVE 1.6.1. Heating circuit M.D factory: ON On

1.6 Heating circuit M.D 1.

5.

2.

6.

Heating circuit M.D

Night room temp. OFF

3.

4.

Heating curve Correction coeff. Day room temp.

Possible selection:

Day/Night Temp. ON

7.

8.

Table 1 Transition Time

- factory: ON -OFF, ON

By using this option ”heating circuit M.D“ can be turned off/on.

1.6.2 HEATING CURVE 1.6.2 Heating curve 1.0

1.6 Heating circuit M.D 1.

Heating circuit M.D

2.

3.

4.

Heating curve Correction coeff. Day room temp.

5.

6.

Night room temp. Day/Night Temp.

7.

8.

1.0

Table 1 Transition Time

Possible selection - Factory: 1,0 - Minimum: 0,1 - Maximum: 4,0 This parameter determine the coefficient of the heating curve. The regulation calculate required flow temperature according to the heating curve and outside temperature to achieve the desired room tempearature. Technical instructions REGULATION BioTec-L

17

Temperatures

Flow temperature

Coefficient

Coefficient

Outside temperature 1.6.3 CORRECTION COEFFICIENT 1.6.3 Correction coeff. 1.0 1.0

1.6 Heating circuit M.D 1.

Heating circuit M.D

2.

3.

4.

Heating curve Correction coeff. Day room temp.

5.

6.

Night room temp. Day/Night Temp.

7.

8.

Table 1 Transition Time

Possible selection: - Factory: 1.0 - Minimum: 0,1 - Maximum: 5,0 This parameter determines coefficient of room corrector influence. If is moved 1 step on the room corrector scale, how many degrees will be changed in regulation. 18

Technical instructions REGULATION BioTec-L

Temperatures

1.6.4 VALUE OF DAY ROOM TEMPERATURE 1.6.4 Day room temp. 20.0 20.0 °C

1.6 Heating circuit M.D 1.

Heating circuit M.D

2.

3.

4.

Heating curve Correction coeff. Day room temp.

5.

6.

Night room temp. Day/Night Temp.

7.

8.

Table 1 Transition Time

Possible selection: - factory: 20,0°C - Minimum: 5°C - Maximum: 30,0°C This parameter determines the value of day room temperature.

1.6.5 VALUE OF NIGHT ROOM TEMPERATURE 1.6.5 Night room temp. 20.0 20.0 °C

1.6 Heating circuit M.D 1.

Heating circuit M.D

2.

3.

4.

Heating curve Correction coeff. Day room temp.

5.

6.

Night room temp. Day/Night Temp.

7.

8.

Table 1 Transition Time

Possible selection: - factory: 20,0°C - Minimum: 5°C - Maximum: 30,0°C This parameter determines the value of night room temperature.

1.6.6 DAY/NIGHT TEMPERATURE CHOICE 1.6.6 Day/Night Temp. Factory: Day Temp. Day Temp.

1.6 Heating circuit M.D 1.

Heating circuit M.D

5.

Night room temp. Day Temp.

2.

3.

4.

Heating curve Correction coeff. Day room temp.

6.

Night Temp.

7.

8.

Table

Day/Night Temp. Table 1 Transition Time

Possible selection: - factory: Day temperature Day temperature, Night temperature, Table This option enables you to choose type of desired temperature (day, night or table.) In next page you can see how to fill a table. Technical instructions REGULATION BioTec-L 19

Temperatures

1.6.7 DAY/NIGHT TEMPERATURE TABLE 1. circuit - Table 1

1.6 Heating circuit M.D 1.

Heating circuit M.D

2.

3.

Heating curve Correction coeff.

4.

Day room temp.

5.

6.

Night room temp.

TUE

WED

THU

FRI

SAT

SUN

06:00

06:00

06:00

06:00

06:00

05:00

06:00

22:00

22:00

22:00

22:00

22:00

10:00

22:00

Day/Night Temp.

7.

8.

MON

Table 1 14:00

Transition Time

23:00

Day temperature

Night temperature

Each cell marks the beginning of some type (day/night) of selected room temperature. According to this table every day from monday at 06:00 am is activated day room temperature, until 22:00 pm when is activated night room temperature until tuesday, when at 06:00 am is again activated day room temperature. On saturday, the day temperature is activated at 05:00 am and works until 10:00 am when is switched to night temperature. At 14:00 pm is again activated day room temperature up to 23:00 pm when is again switched to night temperature. When passed one cycle (week) circle starts again from the beginning. The values of a day/night room temperature can be selected as is described in previous pages.

1.6.8 TRANSITION TIME

(is used only when the configuration doesn’t contain room corrector)

1.6.8 Transition Time. 3600 3600 sec

1.6 Heating circuit M.D 1.

Heating circuit M.D

2.

3.

4.

Heating curve Correction coeff. Day room temp.

5.

6.

Night room temp. Day/Night Temp.

7.

8.

Table 1 Transition Time

Possible selection: - factory: 3600sec - Minimum: 0 sec - Maximum: 18000 sec This parameter is used only when configuration doesn’t contain room corrector, because regulation doesn’t have information of room temperature. This parameter is time which is presumed that the system will achieve a given room temperature in a transition from day to night mode, and vice versa. So, this is time in which will ”flow temperature“ be optimally adjusted to achieve quick transition.

20

Technical instructions REGULATION BioTec-L

Temperatures

1.7 CORRECTOR This option is only available when the selected components are from configuration 7 (selected corrector, floor or radiator heating, motor drive is not selected.

1. Temperature 1.

Boiler temp.

2.

Diff. Boiler

5.

Differential of DHW

6.

Corrector

3.

Min buf.tank temp.

4.

DHW temp.

1.7.1 VALUE OF DAY ROOM TEMPERATURE 1.7.1 Day room temp. 20.0 20.0 °C

1.7 Corrector 1.

2.

3.

4.

Day room temp. Night room temp. Day/Night Temp. Table 1

Possible selection: - factory: 20,0°C - Minimum: 5°C - Maximum: 30,0°C This parameter determines the value of day room temperature.

1.7.2 VALUE OF NIGHT ROOM TEMPERATURE 1.7.2 Night room temp. 20.0 20.0 °C

1.7 Corrector 1.

2.

3.

4.

Day room temp. Night room temp. Day/Night Temp. Table 1

Possible selection: - factory: 20,0°C - Minimum: 5°C - Maximum: 30,0°C This parameter determines the value of night room temperature. Technical instructions REGULATION BioTec-L

21

Temperatures

1.7.3 DAY/NIGHT TEMPERATURE CHOICE 1.7.3 Day/Night Temp. Factory: Day Temp. Day Temp.

1.7 Corrector 1.

Day room temp. Day Temp.

2.

3.

4.

Table

Night room temp. Night Temp.

Day/Night Temp. Table 1

Possible selection: - factory: Day temperature Day temperature, Night temperature, Table This option enables you to choose type of desired temperature (day, night or table.)

1.7.4 DAY/NIGHT TEMPERATURE TABLE 1. circuit - Table 1

1.7 Corrector 1.

2.

3.

4.

Day room temp. Night room temp.

MON

TUE

WED

THU

FRI

SAT

SUN

06:00

06:00

06:00

06:00

06:00

05:00

06:00

22:00

22:00

22:00

22:00

22:00

10:00

22:00

Day/Night Temp. Table 1

14:00 23:00

Day temperature

Night temperature

Each cell marks the beginning of some type (day/night) of selected room temperature. According to this table every day from monday at 06:00 am is activated day room temperature, until 22:00 pm when is activated night room temperature until tuesday, when at 06:00 am is again activated day room temperature. On saturday, the day temperature is activated at 05:00 am and works until 10:00 am when is switched to night temperature. At 14:00 pm is again activated day room temperature up to 23:00 pm when is again switched to night temperature. When passed one cycle (week) circle starts again from the beginning. The values of a day/night room temperature can be selected as is described in previous pages.

22

Technical instructions REGULATION BioTec-L

History 2. HISTORY By pressing this option on the main screen you will see Errors/warnings/ informations list used in order to have an insight into the errors/warnings/ informations that have occurred. History

Written is: - time of occurrence errors/ warnings/ informations - error/warning/information code - description of the error/warning/information.

The first press on the field error/warning/information field is indicated, in addition to see and date generated errors/warnings/information

History MAIN FLOW SENSOR ERROR

E6

OFF

16-Feb-2015 13:53:01

02-Jan

E14

LAMBDA PROBE ERROR

07-Jan

W5

INTERVENTION WORK (Lambda sensor)

15-Jan

I2

26-Jan

E24

ROOM CORRECTOR ERROR

29-Jan

E5

OUTSIDE TEMPERATURE SENSOR ERROR

1x

IGNITION AUTOMATICLY PROCEEDED

The second press on the selected error/warning/information, prints a detailed description of the error/warnings/information and corrective action errors/warnings/information. If for some error/warning/information there is no description on current software version, on the screen will be displayed ”empty“.

History

E6

MAIN FLOW SENSOR ERROR

Empty

Technical instructions REGULATION BioTec-L

OFF

16-Feb-2015 13:53:01

2x

23

File 3. FILE

3. FILE: By pressing this option on the main screen you will see menu with:

File

3.1. LOAD FACTORY 3.2. SAVE 3.3. LOAD

3.1. LOAD FACTORY After pressing ''LOAD FACTORY'' you will see a message ''LOAD FACTORY SETTINGS?''. Pressing button ''OK'' will load the default settings of regulation. Pressing the'' BACK'' will return to the previous menu.

3.2. SAVE After pressing ''SAVE'' you will see a 3 slots to save data (Memory 1, 2, 3). Presing to one of this three buttons you will se message ''SAVE CURRENT SETTINGS?''. Pressing button ''OK'' the current setting of regulation will be saved in memory. Pressing the ''BACK'' will return to the previous menu.

3.3. LOAD After pressing ''LOAD’' you will see ''LOAD SAVED SETTINGS?''. Pressing button ''OK'' saved settings (saved in option SAVE) will be loaded. Pressing the ''BACK'' will return to the previous menu.

24

Technical instructions REGULATION BioTec-L

Operation 4. OPERATION 4.1 MANUAL TEST 02:11

Temperature

History

File

Operation

Date & Time

Display

Info

Glow

Installation

Cleaning

OFF

To enter in Operation menu press ”Operation” button.

4. Operation

4.1. Manual test 1.

2.

1.

Manual test

2.

Chimney sweeper 3.

3.

Forced shutdown 4.

5.

Fan

6.

Primary close

Secondary open P1

Primary open Secondary close

Parts in this section depend about heating configuration

To be able to use manual test, you must first turn ”OFF“ the boiler in the usual way by pressing button and then STOP. 02:11

Temperature

History

File

Operation

Date & Time

Display

Info

Glow

Installation

Cleaning

Temperature

OFF

Technical instructions REGULATION BioTec-L

02:11

Date & Time

Installation

History

Datum i sat

File

STOP? Ekran Info

Display

Instalacija

Operation

Datoteka Glow

OFF

Informacije

25

Info 4.3 FORCED SHUTDOWN This option is used to forced stop all processes. First must be pressed the ON/OFF button to put the boiler in shutdown procedure and then ''forced shutdown'' button. All processes are stopped.

Option ”FORCED SHUTDOWN“ is not usual procedure for turning OFF the boiler 4. Operation 1.

2.

3.

Manual test Chimney sweeper Forced shutdown

5. Način rada 1.

PTV / Grijanje

5.

Čistač dim. prolaza

2.

Ručni test Stop all processes?

3.

Dimnjačar

5.

Prisilno gašenje

IMPORTANT! To be able to stop all processes, you must first turn off the boiler in the usual way by pressing and then STOP. 02:11

Temperature

History

File

Operation

Date & Time

Display

Info

Glow

Installation

Cleaning

26

02:11

Temperature

OFF

Date & Time

Installation

History

Datum i sat

File

STOP? Ekran Info

Display

Instalacija

Operation

Datoteka Glow

OFF

Informacije

Technical instructions REGULATION BioTec-L

Date and time, display 5. DATE AND TIME

Date & time

By pressing this option on the main screen you can set the date and time. This option is used to set the date and time. It is necessary for starting times, and the recording of errors/warnings/informations (for the occurrence of errors / warnings, remembers the date and time of occurrence). After setting the date and time it is necessary to press the ''CONFIRM'' for saving date and time.

6. DISPLAY

6. Display: By pressing this option on the main screen you will see menu with:

Display

6.1. Screensaver 6.2. Language selection 6.3. Init. message time

6.1. SCREENSAVER Possible selection: Default: 600 seconds Minimum: 10 seconds Maksimum: 3600 seconds If at some time nothing was pressed on the screen, the screensaver will turn on, to prevent damage on the screen. Once you touch the screen, the screensaver will turn of.

6.2. LANGUAGE SELECTION Possible selection OFF ON (default) This option enables or disables screen with the choice of language regulation when you turn-on main switch. If is marked ''OFF'', after turning-on the main switch, it will be set on before selected language and after some time, display will show the work display of the boiler (duration of this screen can be adjusted in Section x.x.).

6.3. INITIAL MESSAGE TIME Possible selection: Default: 5 seconds Minimum: 0 seconds Maksimum: 20 seconds This option is used to set the desired duration of the initial message after turning on the main switch. This option is only available if the option'' LANGUAGE SELECTION'' (point 7.2.) Is set to'OFF''.

Technical instructions REGULATION BioTec-L

27

Info 7. INFO

02:11

Temperature

History

File

Operation

Date & Time

Display

Info

Glow

Installation

Cleaning

OFF

To view informations about boiler and software press Info button.

02:11

1 Temperature

History

File

2

Operation

v2.35L 25kW Date & Time

Info

Display

SID: 72CDCE37

Regulator

OFF

Installation

1 - Software version 2 - Boiler power

28

Technical instructions REGULATION BioTec-L

Glow 8. GLOW

02:11

Temperature

History

File

Operation

Date & Time

Display

Info

Glow

Installation

Cleaning

7. Glow ON

OFF

Default: OFF

OFF ON

In menu "Glow” option for glow maintenance can be turned on or of. ENABLED OPTION GLOW: when, on fuel load storage, remain only glow, boiler can maintain remain glow for max 12h, depend about heating requirement

Technical instructions REGULATION BioTec-L

29

Ignition IGNITION Boiler must not be used in flammable and explosive environment. It must not be used by children or disabled persons (either physically or mentally), as well as by person without knowledge or experience, unless they are under control or trained by s person responsible for their safety. Children must be supervised in the vicinity of the product. Protective gloves must be used!

Protective gloves must be used!

IGNITION PHASE: - Open upper and middle boiler doors (see pages 4 i 5 in “Technical instructions for installation of hot water boiler BioTec-L”) Follow these steps for succesfull igniton phase:

- °C

xx°C

05:08

x%

0

2.

0.0% 3.

- press button for boiler start - on display will be displayed window for boiler start - press ”OK” button

xx°C

START?

0.0%

OFF

5.

xx°C

xx°C

- °C

xx°C

05:08

x%

Primary and secondary wings seeking initial position. Please xx°C 0.0% wait and try again. 0.0%

- if this message is shown on display than wait for primary and secondary air actuators - primary and secondary air is ready for work when indicator stop blinking

0

xx°C

x%

OFF 0

xx°C

xx°C

Primary and secondary air indicators.

<0> <0>

xx°C

30

Technical instructions REGULATION BioTec-L

Ignition - °C

xx°C

05:08

x%

IGNITION (1/3) - Fill the boiler with wood! - Close the upper and lower door! 0 - Leave middle door opened! xx°C 0.0% - Start the fire!

- cover the refractory stone with one row of wood logs (be careful to not plug hole on refractory stone (detail A)

1.

2.

3.

0.0%

- on display is displayed message "IGNITION 1/3"

OFF

5.

xx°C

xx°C

Detail A

- cover the wood logs with fine chopped wood (use enough fine chopped wood to cover wood logs below) - height of fine chopped wood layer must conform a approx. height of first row of wood logs - cover the fine chopped wood with crumped paper (use enough crumpled paper to cover fine chopped wood) (detail B) - place the wood logs on crumpled paper - fill the fuel loading chamber with wood logs (detail C) - close upper and lower doors - leave middle door opened - ignite the fire throuh middle boiler door (detail C) - press ”enter“ button

Detail B

Technical instructions REGULATION BioTec-L

Detail C

31

- °C

xx°C

05:08

x%

IGNITION (2/3)

- Leave middle door opened! Wait until the flue gas 0 xx°C temperature rises: 0.0% 22°C/50°C 0.0% 1.

- on this step is neccessary to wait until flue gas temperature raise 50°C OFF

xx°C

- °C

05:08

x%

IGNITION (3/3) 1.

0

Čistač dim. prolaza

When you the middle door, Ručni testclose xx°C press the button

- press ”enter” button

2.

0.0%

3.

Dimnjačar

0.0% 5.

AUTOMATIC CONTINUE: 04:41

Prisilno gašenje

- on display is displayed message "IGNITION 3/3" - close middle boiler door

5.

PTV / Grijanje

- middle boiler door must be opened all time - when is flue gas temperature higher than 50°C press ”enter“ button

xx°C xx°C

xx°C

- on display is displayed message "IGNITION 2/3"

OFF

xx°C

- if you don’t press ”enter” button boiler will be automatic continue when counter count to zero (automatic continue)

xx°C

Additional: During ignition phase is possible to see main display. It is neccessary to press button. Because ignition phase is on proces, display will be displayed current ignition step to (1). By pressing button we return to full preview of ignition phase. - °C

05:08

xx°C

x% IGNITION (1/3)

xx°C

- Fill the boiler with wood! - Close the upper and lower door! 0 - Leave middle door opened! xx°C 0.0% - Start the fire!

x%

IGNITION (1/3)

1

05:08

xx°C

- Fill the boiler with wood! - Close the upper and lower door!

1.

0

2.

3.

0.0%

xx°C

0.0%

OFF

OFF

0.0%

5.

xx°C

xx°C

xx°C

xx°C

- °C

xx°C

05:08 xx°C

x%

IGNITION (2/3)

- Leave middle door opened! Wait until the flue gas 0 xx°C temperature rises: 0.0% 22°C/50°C 0.0%

x%

1

05:08

xx°C

IGNITION (2/3)

- Wait until the flue gas temperature rises:

OFF

1.

0

OFF

0.0%

xx°C

xx°C

xx°C

32

xx°C

0.0%

xx°C

Technical instructions REGULATION BioTec-L

Protection valve

3-WAY MIXING VALVE WITH EL. ACTUATOR (RETURN FLOW PROTECTION) (PROTECTION VALVE) 3-way mixing valve must be installed according to the next steps: - when is presed button ”Valve closing” in manual test valve must closed entry from accumulation tank (see Case 1) - when is pressed button ”Valve opening” in manual test valve must open entry from accumulation tank and close bypass (see Case 2) - depend on el. actuator type is neccessary to input valve opening time on installation menu In below of this technical instruction see how to make manual test of protection valve

bar

Case 1. Valve is 100% closed

bar

Case 2. Valve is 100% open

Technical instructions REGULATION BioTec-L

33

Protection valve

MANUAL TEST (VALVE CLOSING) 02:11

Temperature

History

File

Operation

Date & Time

Display

Info

Glow

Installation

Cleaning

OFF

4. Operation 1.

2.

Manual test Chimney sweeper

4.1. Operation 1.

2.

7.

Primary open

8.

Secondary close

xx°C

x% xx °C

0

Secondary open

6.

Primary close

3.

4.

5.

Fan

P1 Valve closing Valve opening

Manual test Valve closing

xx°C

0.0% 0.0%

xx°C

xx°C

After test, valve must be completely closed (like as shown in Case 1). 34

Technical instructions REGULATION BioTec-L

Protection valve

MANUAL TEST (VALVE OPENING) 02:11

Temperature

History

File

Operation

Date & Time

Display

Info

Glow

Installation

Cleaning

OFF

4. Operation 1.

2.

Manual test Chimney sweeper

4.1. Operation 1.

2.

7.

Primary open

8.

Secondary close

xx°C

P1 Valve closing Valve opening

Manual test Valve opening

x% xx °C

0

Secondary open

6.

Primary close

3.

4.

5.

Fan

xx°C

0.0% 0.0%

xx°C

xx°C

After test, valve must be completely opened (like as shown in Case 2). Technical instructions REGULATION BioTec-L

35

Protection valve

OPENING TIME (authorized persons only) 02:11

Temperature

History

File

Operation

Date & Time

Display

Info

Glow

Installation

Cleaning

10.

11.

12.

Temp. firebox Glow Flue gas temp. Protection valve

* * * *

OFF

9.12 Protection valve

9. Installation 9.

Enter PIN

13.

14.

2.

File

15.

16.

1.

Display

Opening time Timebase

Other Heating circuit

9.12.1 Opening time 270 270 sec

In this step is neccessary to input el. actuator opening time (labeled on el. actuator by manufacturer. This step is crucial for proper operation of el. actuator.

36

Technical instructions REGULATION BioTec-L

Operation phases

OPERATION PHASES (SHOWN ON THE SCREEN)

xx°C

xx°C

x%

05:08

xx °C

0

xx°C

0.0% OFF

0.0%

xx°C

xx°C

Operation phases Operation phase

Description

OFF

The boiler is switched off (standby boiler until the next start).

S0

- The message on the screen: "IGNITION 1/3". - Fan works on max. speed - Primary / secondary is positioning themselves. - The process continues to the next phase "S1" after the user confirms the message or automatically if the Tdp (flue gas temperature) is higher than 50 ° C. If Tdp is higher then 50 ° C at the time of starting the operation of the boiler phase "S0" does not appear on the screen (automatically skipped).

Technical instructions REGULATION BioTec-L

37

Operation phases Operation phase

Description - The message on the screen: "IGNITION 2/3". - Fan works on max. speed - Primary / secondary is positioning themselves. - Waiting for the Tdp> 50°C. When Tdp> 50°C: a) The user can confirm the message "IGNITION 2/3" then screen will show the message "IGNITION 3/3" which user also can confirm which exceeds the boiler in the next phase "SP1" or "SP2".

S1

b) If the user didn’t confirm the message "IGNITION 2/3" or didn’t confirm message "IGNITION 3/3" boiler will after 5 minutes automatically switch to the next phase "SP1" and on the screen remains message "IGNITION 3/3" with the inscription "automatic continuation". This message remains on the screen until the confirmation by the user but has no effect on the operation of the boiler. Exceptions: 1. If upper boiler door is opened, there is no possibility of manual confirmation of the message "IGNITION 2/3" either is not possible to automatically move to the next message "IGNITION 3/3". Closing the upper boiler door, boiler moves to above described (normal) procedure phase "S1". 2. If upper boiler door is opened when on the screen is displayed message "IGNITION 3/3" move to the next stage ("SP1") or "SP2" is only possible by using the manual message confirmation while automatically is not possible. - Setting the start position primary / secondary is necessary for the next phase "SP2".

SP1

- When the primary / secondary are adjusted boiler goes into a phase "SP2", - If the required position of primary / secondary had been set earlier, this phase "SP1" doesn’t appear on the screen).

38

Technical instructions REGULATION BioTec-L

Operation phases Operation phase

Description - The time of duration this stage "SP2" is factory defined.

SP2

SD4

Dx

DOP0

- Before the end of this stage regulation based on the measured parameters of the boiler operation allows the transition to the next phase "SD4" ("DX") or otherwise records information in history and extends this state "SP2" for factory defined time period after which repeats the comparison of the measured and the required parameters and allow you to move to the next stage "SD4" ("DX") or if the conditions are not satisfy writes an error and stops the operation of the boiler. - Set the power blades D4 - If the required position primary / secondary had been earlier set this state "SD4"does not appear on the screen. - Stage "DX" is the common name for operation phases of the boiler on “D4","D3","D2","D1". - phase “DX” doesn’t appear displayed on the screen but is displayed one of the operation of the boiler “D4", "D3", "D2", "D1" which depends about boiler modulation phase. - Indicate that the upper boiler door is opened.

(understage)

DIF1

- Turning off the boiler either due to reaching the set temperature of the boiler, too low combustion chamber temperature or too high flue gas temperature (Tdp>300 °C ).

DIF2

- The boiler wait that the temperature in boiler drops to the set temperature of the boiler reduced by set differential.

DIF3

- Blowout while boiler is waiting that temperature in boiler drops to the set temperature of the boiler reduced by set differential.

DIF4

- Start boiler-setting primary / secondary, after the boiler temperature dropped to the set temperature of the boiler reduced by set differential.

Technical instructions REGULATION BioTec-L

39

Operation phases Operation phase

Description

GLW1 - Shutting down the boiler for keeping the glow. GLW2 - Phase of keeping the glow. GLW3 - Glow blowout in phase of keeping the glow. GLW4 - Start a new filling, set the primary / secondary. OFF1

- Shutting down after which the boiler goes into phase „OFF“.

PF-XXXX

- xxxx: Is any phase described above (for example PF-GLW2) - Appears after a power off/power in if there was a power failure. - The prefix "PF" disappears with new start of the boiler or by using option "forced shut down"

PF-ON

- This stage is printed during zeroing primary / secondary and after a power switch off / switch on. It indicates that after zeroing primary / secondary boiler automatically start again.

IMPORTANT! Automatically resume boiler operation after the disappearance of electric power (PF phases) is not possible if language selection option is turned on. For turning off the ”language selection option“ follow steps below: 02:11

Temperature

History

File

Operation

Date & Time

Display

Info

Glow

OFF

Cleaning Installation

6.2. Language selection Factory: ON ON

6. Display 1.

Screensaver OFF

2.

Language selection ON

3..

Init.message time

40

Technical instructions REGULATION BioTec-L

Example of the error/warning that appears on the main screen ERROR/WARNING ON THE MAIN SCREEN xx°C

DHW SENSOR ERROR

E1

2 3 4

05:08

ERRORS - WARNINGS

xx °C

1

xx°C

x%

0

xx°C

0.0% 15.09.2014. 11:30:46 Appear:

5 OFF

0.0%

x/x xx°C

xx°C

6 When the error/warning still present, error/warning name and code is painted red, and when error/warning is resolved, text turns green 1 2 3 4 5 6

Error / Warning / Information code Error / Warning / Information name Date and time of error / warning / information occurrence Number of errors / warnings / informations „OK” button Buttons for scrolling through errors / warning / informations

By pressing „OK” button error window will be minimized and showned on main display. xx°C

xx°C

x%

05:08

xx °C

0

ERRORS: X xx°C

WARNINGS: X

0.0% OFF

0.0%

xx°C

xx°C

Minimized window on main display All errors/warnings are recorded in history (see point 2.History)

Technical instructions REGULATION BioTec-L

41

Errors, warnings LIST AND ELIMINATION OF ERRORS / WARNINGS / INFORMATIONS

ERROR E1 Boiler status

Error DHW SENSOR

Intervention mode

Causes Error in temperature sensor in sanitary water tank. What to do? Check sensor position, check damages of sensor and cables, check contacts on connectors. Press „OK” button to confirm error. Boiler will continue with work but on main screen will be showned information about error. Instead temperature, on DHW tank will be showned „-°C”. Intervention mode: Boiler work to content heating demand but boler has reduced possibilities. If upper instructions didn’t help call service man.

ERROR E2 Boiler status Boiler work normally

Error BUFFER TANK SENSOR ERROR (UP) Causes Error in buffer tank sensor (up).

What to do? Check sensor position, check damages of sensor and cables, check contacts on connectors. Press „OK” button to confirm error. Boiler will continue with work but on main screen will be showned information about error. Instead temperature, on buffer tank (up) will be shown „-°C” and the request for AKU-tank temperature will not working. If upper instructions didn’t help call service man.

ERROR E3 Error BUFFER TANK SENSOR ERROR (DOWN)

Boiler status Intervention mode

Causes Error in buffer tank sensor (down). What to do? Check sensor position, check damages of sensor and cables, check contacts on connectors. Press „OK” button to confirm error. Boiler will continue with work but on main screen will be showned information about error. Instead temperature, on buffer tank (down) will be shown „-°C” and pump P1 works whenever the temperature in the boiler exceeds 65°C. Intervention mode: Boiler work to content heating demand but boler has reduced possibilities. If upper instructions didn’t help call service man. 42

Technical instructions REGULATION BioTec-L

Errors, warnings

ERROR E4 Error FLUE GAS SENSOR ERROR

Boiler status Intervention mode

Causes Error on flue gas sensor. What to do? Check sensor position, check damages of sensor and cables, check contacts on connectors. Press „OK” button to confirm error. Boiler will continue with work but on main screen will be showned information about error. Instead flue gas temperature will be showned „-°C”. Intervention mode: Boiler work to content heating demand but boler has reduced possibilities. If upper instructions didn’t help call service man. WARNING!!! If is this error present it is neccesary to hold open middle boiler door during ignition phase (as much is necessary for good iginition (no longer)). DON’T OPEN MIDDLE BOILER DOOR DURING BOILER WORK!!

ERROR E5 Error OUTSIDE TEMPERATURE SENSOR ERROR

Boiler status Boiler work normally

Causes Error on outer sensor. What to do? Check sensor position, check damages of sensor and cables, check contacts on connectors. Press „OK” button to confirm error. Boiler will continue with work but on main screen will be showned information about error. Instead outer temperature will be showned „-°C”. If is configuret configuration with motor drive in heating circuit system can’t work toward heating curve because don’t have information about outer temperature. In other configuration boiler work normally except displaying outer temperature.

Technical instructions REGULATION BioTec-L

43

Errors, warnings

ERROR E6 Boiler status Boiler work normally (depend about config.)

Error MAIN FLOW SENSOR ERROR Causes Error on main flow sensor.

What to do? Check sensor position, check damages of sensor and cables, check contacts on connectors. Press „OK” button to confirm error. Boiler will continue with work but on main screen will be showned information about error. Instead main flow temperature will be showned „-°C” If upper instructions didn’t help call service man. - If is configuret configuration with motor drive in heating circuit system will not work!! - In other configurations system work normally except displaying main flow temperature.

ERROR E7 Boiler status Boiler go to extinction phase

Error RETURN FLOW SENSOR ERROR Causes Error on return flow sensor.

What to do? Check sensor position, check damages of sensor and cables, check contacts on connectors. When boiler show this error boiler go to extinction phase and can’t be started until error will not be resolved. If upper instructions didn’t help call service man.

ERROR E8 Boiler status Boiler go to extinction phase

Error BOILER SENSOR ERROR Causes Error on boiler sensor.

What to do? Check sensor position, check damages of sensor and cables, check contacts on connectors. When boiler show this error boiler go to extinction phase and can’t be started until error will not be resolved. If upper instructions didn’t help call service man.

ERROR E9 Boiler status Boiler can’t be started

Error UNKNOWN BOILER POWER Causes Key for power loading are not inserted or it is not recognized. What to do?

44

CALL SERVICE MAN! Technical instructions REGULATION BioTec-L

Errors

ERROR E10 Boiler status Boiler go to extinction phase

Error FAN ERROR Causes Invalid fan or rpm counter.

What to do? Check if is rpm counter placed, check possible damages on rpm counter or on cables, check contacts on connectors. When boiler show this error boiler go to extinction phase. Boiler can be started but if error shown again boiler go to extinction phase again. If upper instructions didn’t help call service man.

ERROR E14 Boiler status Intervention mode

Error LAMBDA PROBE ERROR

Press „OK” button to confirm error. Boiler will continue with work but on main screen will be showned information about error. Intervention mode: Boiler work to content heating demand but boiler has reduced possibilities. Call service man.

ERROR E17 (May occur only when installation contain CM2K (additional equipment)). Error SENSOR REG. 1+ CIRCUIT

Boiler status

Causes Error on flow temperature sensor of 1+ heating circuit (on regulator CM2K) What to do? Check sensor position, check damages of sensor and cables, check contacts on connectors. If upper instructions didn’t help call service man.

ERROR E18 (May occur only when installation contain CM2K (additional equipment)). Error CORRECTOR REG. 1+ CIRCUIT

Boiler status

Causes Error on room corrector of 1+ heating circuit (CM2K regulator), bad corrector connection to the CM2K or room corrector failure. What to do? Check damages of corrector and cables, check contacts on connectors. If upper instructions didn’t help call service man. Technical instructions REGULATION BioTec-L

45

Errors, warnings

ERROR E19 (May occur only when installation contain CM2K (additional equipment)). Boiler status

Error SENSOR REG. 2+ CIRCUIT

Causes Error on flow temperature sensor of 2+ heating circuit (on regulator CM2K) What to do? Check sensor position, check damages of sensor and cables, check contacts on connectors. If upper instructions didn’t help call service man.

ERROR E20 (May occur only when installation contain CM2K (additional equipment)). Boiler status

Error CORRECTOR REG. 2+ CIRCUIT

Causes Error on room corrector of 2+ heating circuit (CM2K regulator), bad corrector connection to the CM2K or room corrector failure. What to do? Check damages of corrector and cables, check contacts on connectors. If upper instructions didn’t help call service man.

ERROR E21 Boiler status Intervention mode

Error FIREBOX SENSOR

Press „OK” button to confirm error. Boiler will continue with work but on main screen will be showned information about error. Intervention mode: Boiler work to content heating demand but boler has reduced possibilities. Call service man.

ERROR E23 Error IGNITION ERROR, TRY AGAIN!

Boiler status OFF (Boiler operation phase)

Causes Bad ignition, too damp wood, non-closed middle or lower door, non-closed side covers for cleaning or rear top cover for cleaning), impassable flue pipe from the fan to the chimney, blocked passes for the primary or secondary air between the upper and middle boiler door. What to do? Check and close the insufficiently sealed openings and if necessary fill and start the boiler again, if you don’t help these actions, call an authorized service to check primary / secondary openings.

46

Technical instructions REGULATION BioTec-L

Errors

ERROR E24 Boiler status

Error ROOM CORRECTOR ERROR

Causes Interruption in electric cables between room corrector and boiler, bad connection to the boiler or room corrector failure. What to do? Check electric cables between the room corrector and boiler, and connection to the boiler. If upper instructions didn’t help call service man.

ERROR E25 Error

Boiler status

FAN is OFF, flue gas temp too high, Close the upper door!

OFF (Boiler operation phase)

Causes Too high flue gas temperature with the open upper boiler door. What to do? Close the uper door and restart the boiler (load fuel if necessary).

ERROR E26 Error FIREBOX SENSOR DISCONNECTED

Boiler status Intervention mode

Press „OK” button to confirm error. Boiler will continue with work but on main screen will be showned information about error. Intervention mode: Boiler work to content heating demand but boler has reduced possibilities. Call service man.

For errors below call service man! ERROR E12

COMMUNICATION ERROR WITH MOTHERBOARD

ERROR E13

COMMUNICATION ERROR WITH SENSOR BOARD

ERROR E16

COMMUNICATION ERROR WITH CMREG

Technical instructions REGULATION BioTec-L

47

Informations

Warnings (displayed on the screen and recorded in history) W1 - Factory settings loaded W2 - Flue gas temp. high, close the upper door! W3 - Fan protection Appear always when fan decrease rotating speed or if turning ”OFF“ itself because of high flue gas temperature. W4 - Flue gas temp. high, close the upper door! The boiler operates without using the firebox sensor W5 - Intervention work (lambda probe) The boiler operates without using the lambda probe W6 - Intervention work (flue gas sensor) The boiler operates without using the flue gas sensor W7 - Intervention work (RPM sensor) The boiler operates without using the RPM (rotates per minute) sensor

Informations (recorded in history) I1 - OFF during ignition Recorded into history whenever the boiler goes into shutdown phase due to reaching the set temperature of the boiler or too high flue gas temperature during phase S1 (ignition phase). I2 - ignition automaticly proceeded The boiler is after 5 minutes since the flue gas temperature reached 50 °C in operation phase S1 continued to work in stabilization phase (SP1,SP2). I3 - bad ignition Measured parameters of combustion in the boiler during ignition/stabilization were bad but still continued to work in conditions of work (DX) and the possible bad combustion of wood and the rest of unburned wood at the end of the operation (OFF). I4 - OFFduring stabilization Recorded into history whenever the boiler goes into shutdown phase due to reaching the set temperature of the boiler or too high flue gas temperature during phases SP1,SP2 (stabilization phases) I5 - power up (power down) Return power (230 V) after electric failure during boiler operation. I6 - glow after power up End of the boiler operation with "turned on" option "glow" when in the process of work occured electric failure (230 V). I7 - ”OFF“ after power up End of the boiler operation when in the process of work occurred electric failure (230 V).

48

Technical instructions REGULATION BioTec-L

Notes

Technical instructions REGULATION BioTec-L

49

Company Centrometal d.o.o. assumes no responsibility for possible inaccuracies in this book originated typographical errors or rewriting, all the pictures and diagrams are principal and it is necessary to adjust each actual situation on the field, in any case the company reserves the right to enter their own products such modifications as considered necessary.