Trimod HE® User manual

Item LE11916AA-11/19-01 CT

Trimod HE®

EN

2

ENGLISH 3

Contents 1. Introduction 1.1 Overview

5 5

1.2 Purpose of the manual

5

1.3 Symbols in the manual

5

1.4 Where and how to keep the manual

6

1.5 Update of the manual

6

1.6 Manufacturer's liability and guarantee

6

1.6.1 Guarantee terms

7

1.6.2 Extension of the guarantee and maintenance contracts

7

1.7 Copyright

7

2. Regulatory and safety requirements

8

2.1 General notes

8

2.2 Definitions of “Skilled Technician” and “Operator”

8

2.2.1 Skilled Technician

8

2.2.2 Operator

8

2.3 Personal Protective Equipment

9

2.4 Hazard signs in the workplace

9

2.5 Signs on the equipment

10

2.6 General warnings

10

2.7 How to proceed in an emergency

12

2.7.1 First-aid procedures

12

2.7.2 Fire procedures

12

3. Technological description

13

3.1 Trimod HE technology

13

3.2 Features

15

4. Unpacking and positioning

18

4.1 Visual check

18

4.1.1 Equipment check

18

4.2 Unpacking

18

4.3 Check of the content

18

4.4 Movement

19

4.5 Positioning constraints

19

4.6 Final operations

19

3

User manual

Trimod HE

Contents 5. Control panel 5.1 Description

20

5.2 Service Mode

21

5.3 Main screen

21

5.4 Main menu and submenu

23

5.4.1 UPS Status

24

5.4.2 UPS Setup

26

5.4.3 Power Modules

30

5.4.4 Events

32

5.4.5 Tools

32

5.4.6 Log Out

32

5.5 POWER ON/OFF menu

33

5.6 Switching off the UPS

33

5.7 Switching on the UPS

33

6. Diagnosis

34

6.1 Luminous and audible notifications

34

6.2 Messages

36

7. Maintenance

43

7.1 Installation

43

7.2 Preventive maintenance

43

7.3 Periodical checks

43

7.4 Ordinary maintenance checks

43

7.5 Extraordinary maintenance

43

8. Warehousing

44

8.1 UPS

44

8.2 Batteries

44

9. Dismantling

45

9.1 Battery disposal

45

9.2 UPS dismantling

45

9.3 Electronic component dismantling

45

10. Technical data

4

20

46

1. Introduction CAUTION The instructions in this manual are intended for an OPERATOR (paragraph 2.2.2)

1.1 Overview

Congratulations on your LEGRAND Trimod HE UPS purchase. Thanks to this UPS, your critical equipment will always be protected by a constant and reliable electricity supply. LEGRAND is specialized in designing and producing UPS. Trimod HE is unique in its kind: it is modular, redundant and belongs to the last generation of high power UPS. High reliability, low running costs and excellent electrical performance are some of its characteristics. The high quality standard of LEGRAND in design and production allows Trimod HE to pass the strictest quality tests. The UPS has been designed in compliance with the existing European Union directives, with the technical standards that include their requirements and with the eco-design guidelines. The equipment is produced at an ISO14001 certified factory. This publication, simply defined “user manual” herein, contains all the information for the use of the Trimod HE UPS, also referred to as “equipment” in this manual. The contents of the user manual are intended mainly for an operator (see paragraph 2.2.2) or for people, generically defined as “users”, who have the need and/or obligation to provide instructions or work directly on the equipment for their assigned tasks. These people can be the following: - managers; - heads of operating areas; - department heads; - direct private users.

1.2 Purpose of the manual

The purpose of this manual is to provide the operator with instructions for safely using the equipment after the installation performed by a skilled technician. Extraordinary maintenance operations are not dealt with in this manual because they are the sole preserve of the LEGRAND Technical Support Service. The reading of this manual is essential but does not substitute the skill of technical personnel who must have received adequate preliminary training. The intended use and configurations envisaged for the equipment as shown in this manual are the only ones allowed by the Manufacturer. Any other use or configuration must be previously agreed with the Manufacturer in writing and, in this case, the written agreement will be attached to the manuals. This manual also makes reference to laws, directives and standards that the operator is required to be aware of and consult. The original text of this publication, drafted in Italian, is the only reference for the resolution of disputes of interpretation linked to translations into other languages.

1.3 Symbols in the manual

Some operations are shown in graphic symbols that draw the attention of the reader to the danger or the importance they imply: DANGER This indication shows a danger entailing a high degree of risk that, if not avoided, will lead to death or serious injury or considerable damage to the equipment and things around it.

5

User manual

Trimod HE

1. Introduction WARNING This indication shows a danger entailing a medium degree of risk that, if not avoided, could lead to death or serious injury or considerable damage to the equipment and things around it. CAUTION This indication shows a danger entailing a low level of risk that, if not avoided, could lead to minor or moderate injury or material damage to the equipment and things around it. INDICATION This symbol indicates important information which should be read carefully.

1.4 Where and how to keep the manual

This manual must be kept in a safe, dry place and must always be available for consultation. It is recommended to make a copy of it and file it away. If information is exchanged with the Manufacturer or the authorised assistance personnel, it is essential to refer to the equipment’s rating plate data and serial number. INDICATION The manuals provided with the equipment are an integral part of it and must therefore be kept for its entire lifetime. In case of need (for example in case of damage that even partially compromise its consultation) the operator is required to get a new copy from the Manufacturer, quoting the publication code on the cover.

1.5 Update of the manual

The manual reflects the state of the art when the equipment was put onto the market. The publication conforms with the directives current on that date. The manual cannot be considered inadequate when new standards come into force or modifications are made to the equipment. Any addition to the manual that the Manufacturer considers appropriate to send to the users, must be kept together with the manual of which they will become an integral part. The version of the manual updated to its latest release is available on the Internet at http://www.ups.legrand.com

1.6 Manufacturer's liability and guarantee

The skilled technician and the operator shall scrupulously comply with the precautions indicated in the manuals. They must: - always work within the operating limits of the equipment; - always carry out constant and careful maintenance through a skilled technician who complies with all the procedures indicated in the installation and maintenance manual. The Manufacturer declines all indirect or direct responsibility arising from: - assembly and cabling made by personnel not qualified and authorized by LEGRAND and not fully qualified according to national standards to work on equipment presenting electrical hazards; - assembly and cabling made without using safety equipment and tools required by national safety standards; - failure to observe the installation and maintenance instructions and use of the equipment which differs from the specifications in the manuals; - use by personnel who have not read and thoroughly understood the content of the user manual; - use that does not comply with the specific standards used in the country where the equipment is installed; - modifications made to the equipment, software, functioning logic unless they have been authorised by the Manufacturer in writing; - repairs that have not been authorised by the LEGRAND Technical Support Service; - damage caused intentionally, through negligence, by acts of God, natural phenomena, fire or liquid infiltration; - damage caused by the use of batteries and protections not specified in the manuals; - damage caused by improper unloading and transportation after delivery of the equipment; - accidents caused by a wrong assembly of the safety protections or due to the lack of application of the safety labels specified in the installation manual.

6

The transfer of the equipment to others also requires the handing over of all the manuals. Failure to do it will automatically nullify any right of the buyer, including the terms of the guarantee where applicable. If the equipment is sold to a third party in a country where a different language is spoken, the original owner shall be responsible for providing a faithful translation of this manual in the language of the country where the equipment will be used.

1.6.1 Guarantee terms The guarantee terms may vary depending on the country where the UPS is sold. Check the validity and duration with LEGRAND's local sale representative. If there should be a fault in the equipment, contact the LEGRAND Technical Support Service which will provide all the instructions on what to do. Do not send anything back without LEGRAND's prior authorization. The guarantee becomes void if the UPS has not been brought into service by a properly trained skilled technician (see paragraph 2.2.1). If during the guarantee period the equipment does not conform with the characteristics and performance laid down in this manual, LEGRAND at its discretion will repair or replace the UPS and relative parts. All the repaired or replaced parts will remain LEGRAND's property. LEGRAND is not responsible for costs such as: - losses of profits or earnings; - losses of equipment, data or software; - claims by third parties; - any damage to persons or things due to improper use, unauthorized technical alterations or modifications; - any damage to persons or things due to installations where the full compliance with the standard regulating the specific usage applications have not been guaranteed.

1.6.2 Extension of the guarantee and maintenance contracts The standard guarantee can be consolidated in a single extension contract (maintenance contract). Once the guarantee period has passed, LEGRAND is available for giving a technical assistance service able to meet all requirements, maintenance agreements, 24/7 availability and monitoring. Please, contact the LEGRAND Technical Support Service for further information.

1.7 Copyright

The information contained in this manual cannot be disclosed to any third party. Any partial or total duplication of the manual by photocopying or other systems, including electronic scanning, which is not authorised in writing by the Manufacturer, violates copyright conditions and may lead to prosecution. LEGRAND reserves the copyright of this publication and prohibits its reproduction wholly or in part without previous written authorisation.

7

User manual

Trimod HE

2. Regulatory and safety requirements DANGER Before carrying out any operation on the equipment, it is necessary to read the entire manual carefully, especially this chapter. Keep the manual in a safe place and consult it repeatedly during the use of the UPS.

2.1 General notes

The equipment has been made for the applications given in the manuals. It must not be used for purposes other than those for which it has been designed or differently from those specified in this manual.

2.2 Definitions of “Skilled Technician” and “Operator” 2.2.1 Skilled Technician The professional figure who will carry out the installation, start-up and ordinary maintenance is called "Skilled Technician". This definition refers to people who have specific technical qualifications and are aware of the methods of installing, assembling, repairing, commissioning and safe use of the equipment. In addition to the requirements listed in the section below for a general operator, the Skilled Technician is qualified according to national safety standards to work under dangerous electrical voltage and uses the personal protective equipment required by national safety standards for all the operations indicated in this manual (see the examples listed in paragraph 2.3). WARNING The safety manager is responsible for protection and company risks prevention according to what is indicated in the European directives 2007/30/EC and 89/391/EEC regarding safety in the workplace. The safety manager must ensure that all people working on the equipment have received the instructions included in the manuals with particular reference to those contained in this chapter.

2.2.2 Operator The professional figure assigned to the equipment for normal use is called "Operator". This definition refers to people who know how to operate the equipment as described in the user manual and have the following requisites: 1. technical education which enables them to operate according to safety standards in relation to the dangers linked to the presence of electric voltage; 2. training on the use of personal protective equipment and basic first aid interventions. The company safety manager, in choosing the person (operator) who uses the equipment, must consider: - the person’s work fitness according to the laws in force; - the physical aspect (not disabled in any way); - the psychological aspect (mental stability, sense of responsibility); - the educational background, training and experience; - the knowledge of the standards, regulations and measures for accident prevention. He shall also impart training in such a way as to provide thorough knowledge of the equipment and its component parts. The operator shall consult the user manual at any time. He shall also follow the regulations provided to achieve maximum safety for himself and others during all operating phases. Some typical activities the operator is expected to carry out are: - the use of the equipment in its normal functioning state and the restore of the functioning after it shuts down; - the adoption of the necessary provisions for maintaining the quality performance of the UPS; - the cleaning of the equipment; - cooperation with personnel responsible for ordinary maintenance activities (skilled technicians).

8

2.3 Personal Protective Equipment DANGER The UPS poses a considerable risk of electric shock and a high short circuit current. During use and maintenance operations, it is forbidden to operate without the equipment listed in this paragraph. People responsible for operating this equipment and/or passing close to it must not wear garments with flowing sleeves, nor laces, belts, bracelets or other metal pieces that might cause a danger. The following signs sum up the minimum Personal Protective Equipment to wear at all times. Additional requirements may be provided for by the safety regulations in force in the country of installation. Anti-accident and no-spark shoes with rubber sole and reinforced toe Safety gloves for protection from mechanical risks Dielectric gloves for protection from dangerous voltages Protective clothing for electrical work

Electrical protection helmet and visor

Insulated tools

2.4 Hazard signs in the workplace

The following signs must be exhibited at all points of access to the room where the equipment is installed: Electric current This sign indicates the presence of electrical live parts. Emergency interventions Do not use water to quench fires but only the extinguishers specifically designed for putting out fires in electrical equipment. No smoking This sign indicates that smoking is not allowed in the area.

9

User manual

Trimod HE

2. Regulatory and safety requirements 2.5 Signs on the equipment

Displayed on the UPS are explanatory plates that can vary depending on the country the equipment is intended for and constructional standards applied. Safety labels are in English. A set of labels is supplied in several languages. During the installation, it is the responsibility of the skilled technician to replace the labels in English with those in the most understandable language in the country in which the equipment is installed. Make sure the instructions are adhered to. It is strictly prohibited to remove these plates and to work in a way that differs from what is written there. The plates must always be clearly read and they must be cleaned periodically. If a plate deteriorates and/or is no longer legible, even partially, the Manufacturer must be contacted for another one in order to replace it. CAUTION The plates must not be removed or covered. No other plates may be affixed to the equipment without the Manufacturer's prior written authorisation. WARNING Potential risks can be drastically reduced by wearing the Personal Protective Equipment listed in this chapter. These protections are indispensable. Always operate with due care around dangerous areas marked by the appropriate warning signs on the equipment.

2.6 General warnings DANGER The UPS works with dangerous voltages. Only SKILLED TECHNICIANS shall perform all installation and ordinary maintenance operations. No part of the equipment can be repaired by the operator. Extraordinary maintenance operations must be carried out by LEGRAND Technical Support Service personnel. WARNING A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries: a) remove watches, rings or other metal objects. b) use tools with insulated handles. c) wear rubber gloves and boots. d) do not lay tools or metal parts on top of batteries. e) disconnect the charging source prior to connecting or disconnecting battery terminals. f ) determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not having a grounded supply circuit); g) never leave live cables uncovered. Do not dispose of batteries in a fire. The batteries may explode. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. The batteries installed inside the cabinet must be disposed of correctly. For the disposal requirements refer to local laws and relevant standards. CAUTION The UPS functions with TT and TN systems. It has a pass-through neutral architecture: the status of the output neutral is the same as the input neutral. When a load needs a different neutral status from the input status, it is necessary to place downstream of the equipment a suitably scaled isolation transformer protected in compliance with the standards in force.

10

CAUTION Do not open the battery fuse holders of the external battery units while the UPS is powering the loads in battery mode. WARNING To reduce the risk of fire or electric shock, the UPS must work in clean and indoor environments with controlled temperature and humidity. It must be kept away from inflammable liquids and corrosive substances. The room temperature must not be above +40°C (+104°F) and the relative humidity must be a maximum of 95% not condensing. CAUTION Trimod HE 10 is a category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the user may be required to take additional measures. All the other Trimod HE models are products for commercial and industrial application in the second environment installation restrictions or additional measures may be needed to prevent disturbances. CAUTION - The equipment must be maintained and used according to the instructions written in the manuals. - The departmental manager must instruct the operating and maintenance personnel on the safe use and maintenance of the equipment. - Only specifically-trained, highly skilled personnel are allowed access to the equipment in order to perform maintenance. While the maintenance operation is being carried out, signs saying "Maintenance work in progress" must be affixed in the department in such a way that they can be easily seen from any access area. - Any intervention on the equipment must be done only after it has been disconnected from the power supply network by means of a switch disconnector and must be locked with an appropriate padlock. - The UPS must not be turned on if liquid is leaking from the batteries. - Depositing flammable material near the equipment is strictly forbidden. The equipment should always be locked, and only specifically trained personnel are allowed access to it. - Do not disable any safety notification or warning device and do not ignore any alarm or warning message no matter whether they are generated automatically or represented by plates fixed to the equipment. - Do not run the equipment with fixed protections not installed (panels etc.). - In case of breaking, buckling or malfunctioning of the equipment or parts of it, repair or replace immediately. - For no reason can the structure of the equipment, the devices mounted on it, the operation sequence etc, be modified, manipulated or tampered with in any way, without prior consultation with the Manufacturer. - Keep a register and enter therein the date, time, type, performer’s name and any other useful information about each and any routine and extraordinary maintenance operation. - Do not use oils or chemical products for cleaning because they could scratch, corrode or damage certain parts of the equipment. - The equipment and workplace must be kept completely clean. - Upon completion of the maintenance operations, before connecting the power supply, carefully check that no tools and/or material of any kind have been left next to the equipment. CAUTION The skilled technician must not leave at the disposal of the operator: - the keys for opening the UPS door; - the installation and maintenance manual.

11

User manual

Trimod HE

2. Regulatory and safety requirements 2.7 How to proceed in an emergency

The following information are general. For specific interventions consult the regulations in force in the country where the equipment is installed.

2.7.1 First-aid procedures When administering first aid, adhere to the company rules and the usual procedures.

2.7.2 Fire procedures Do not use water to quench fires but just the extinguishers specially designed for putting out fires on electrical equipment.

12

3. Technological description 3.1 Trimod HE technology

LEGRAND® has developed an innovative project that is the only one of its kind by producing Trimod HE, the uninterrupted power supply able to adapt at any moment to changed demands of the protected loads. The concepts underlying the Trimod HE project are modularity, expandability and redundancy in such a way as to offer maximum reliability and to be the guarantee of considerable savings. Trimod HE is a modular uninterrupted power supply whose base module is the single phase power type and it can be programmed to obtain the desired input/output configuration. It is thus possible to manage three phase and single phase voltages on input and output to have a choice of the the traditional three phase/three phase, three phase/single phase, single phase/three phase and single phase/single phase. At the same time it is possible to obtain simultaneously single phase and three phase lines on output or two or more single phase lines even with different power. For every configuration it is possible to have redundancy that is both complete and partial. For example, one normal three phase (or redundant) line can coexist with a redundant single phase (or normal) line on output. The philosophy underlying modularity has also been applied to the batteries that have been supplied in individual drawers that can be extracted and make installation and maintenance easier. The UPS is controlled by one to four command boards depending on the model. Both the command boards (CM) and the power modules (PM) are identified by a unique address inside the system, as shown below:

Trimod HE 10

Trimod HE 15-20

CM 0

PM 0

PM 1

PM 2

Trimod HE 20

CM 0

PM 0

PM 1

PM 2

PM 3

PM 4

PM 5

13

User manual

Trimod HE

3. Technological description

CM 0

Trimod HE 30 TT/TM

CM 0

PM 1

PM 2

CM 1* PM 3

PM 4

PM 5

CM 2* PM 6

PM 7

PM 8

* for the MULTI CTRL models only

14

PM 1

PM 2

CM 1* PM 3

PM 4

PM 5

CM 0

PM 0

PM 1

PM 2

CM 1

PM 3

PM 4

PM 5

CM 2

PM 6

PM 7

PM 8

CM 3

PM 9

PM 10 PM 11

Trimod HE 40

PM 0

Trimod HE 60

PM 0

Trimod HE 80

Each command board can manage three power modules. If a command card becomes faulty, only the modules under its control are put into safe mode and turned off, while the UPS continues to function online, without any interruption in the load. It is therefore possible to have redundancy on both the individual phase (power module failure) and in the UPS (command board failure). The replacement of the hot-swap of the power modules is also possible by switching off the relative control and group of modules attached to it, without having to power the load from the bypass with the consequent temporary loss of protection. The command boards are connected to a control panel with display from which it is possible to verify the status and setups of the UPS and to a communication interface with and RS-232 and SNMP connection, dry contacts and logical contacts. It is possible to access all the UPS functions from the control panel and communicate through any of the interfaces present thereby guaranteeing the redundancy of the peripherals as well. In installations with three separate single phase line on output, it is possible to manage each line independently through the software. For example, it is possible to prioritise the autonomy of one of them during battery functioning. A bypass input line separated from that of the mains input makes it possible to supply the bypass with a second power source (the neutral wires of the two lines must be in common). The technology used in the hardware and the firmware of the UPS represents the current state of the art. A sophisticated microprocessor-type control optimises the performance of the UPS on the Booster/PFC side and on the output inverter. The recharge curve of the battery has been designed to get the maximum useful life out of the accumulators and have the greatest autonomy possible if the main power goes off. The electronic boards are entirely assembled on LEGRAND automated lines and tested to the highest quality standards. Every device goes through an extended period of operation at full load before being sent to the customer.

3.2 Features

Modular-redundant architecture The modular-redundant architecture is the best solution for protecting the nerve centres of a company and has the following advantages: - there is one control of the devices supplied; - modular expandability; - module redundancy; - easy maintenance; - low running cost; - compactness. Efficiency The Trimod HE UPS concentrate particularly on both the energy absorbed from the mains and the energy provided to the load. They are characterised by high efficiency (up to 96%), PF on input>0.99, THDi <3%. The advantages of a high efficiency are: - reduction of the power absorbed from the UPS but not supplied to the load and transmitted to the environment as heat; - less heat loss transmitted to the environment means reducing the need for ventilation or air conditioning systems in the installation site; - no power factor correction cost and so no increase in charges; - no need to increase the size of any generator upstream of the UPS. Expandability Most UPS systems on the market are of the non-modular and non-expandable type thus requiring an initial upscaling of the system to make future expansions possible. The advantages of an expandable system are: - optimisation of investments for UPSs, making them adequate for the current requirements without precluding future expansions and avoiding wastes of energy; - increase in the efficiency of the system thanks to proper sizing. Reliability To obtain a level of redundancy with traditional UPSs it is necessary to put at least two in parallel thereby doubling the power acquired, the space occupied and the electricity consumed. Trimod HE’s modular architecture makes it possible to have redundant configurations within a single cabinet. The advantages are: - a UPS with a redundant modular architecture can be configured as an N+X redundant simply by choosing a proper number of power modules to be installed in the UPS cabinet. Even in the case of a fault in a module, the equipment continues to function avoiding any downtime; - clear indications and a large display make it possible to find the fault more quickly; - the modular architecture makes it possible to speed up the solution to problems through the simple replacement of the faulty module without interrupting the service; - high percentage of faults resolved at the first attempt.

15

User manual

Trimod HE

3. Technological description Dual input Trimod HE has two input disconnectors, one for the mains and the other for powering the load by means of a bypass line completely indipendent from the mains. The two lines are interconnected by default and they may be rendered indipendent during the installation or commissioning of the equipment (the neutral cables of the two lines must be in common). Power module The high-efficiency single phase module, available in three power sizes of 3400 VA (PM4), 5000 VA (PM6) and 6700 VA (PM7) respectively, is mainly made up of the following functional blocks: - command and control logic (managed by a microprocessor); - PFC rectifier/booster; - inverter; - battery charger; - automatic bypass. In each power module there is a microcontroller that can oversee the main functions of the individual unit, monitor its correct functioning and flag up any malfunctions. The power module is Plug & Play to make the power expansion and any maintenance operation easier. Every module is put in parallel with other identical ones until reaching the power of the UPS. The power modules are independent of each other and can function even if there is a fault in one of them. At the front of the module there is a multicoloured LED with traffic-light code green-yellow-red, making it possible to identify the functioning status of the electronic unit quickly. The power modules are housed on shelves also called tunnels that can house three modules. The block diagram of the power module is the following:

Batteries The battery modules are designed for easy insertion into the dedicated cabinet and they do not need any operation for their positioning: their lightness makes them simple to handle and therefore easy to maintain or replace. A drawer consists of five 12 V 7.2 Ah or 9 Ah batteries, connected in series and thanks to the Plug & Play connection it is easy to extract and insert it in the cabinet. The nominal battery voltage for the Trimod HE is 240Vdc, therefore a complete branch consists of four battery drawers (for a total of twenty 12Vdc batteries) that form what is called KB (Battery Kit). In order to ensure the maximum level of safety, especially during maintenance, the voltage of each drawer is properly isolated into two branches of 24 V and 36 V and it is only restored when the drawer is completely inserted into its housing. This allows conformity with the standard EN 62040-1 on electrical safety that requires the use of adequate protection and particular care when handling dangerous voltages above 50 Vdc where direct contact is possible. The autonomy can be further increased by adding more battery drawers in multiples of four, using both the seats in the UPS cabinet if available, and the seats in the additional modular battery cabinets.

16

Digital display and alarm display Trimod HE is managed by one to four microprocessor-type command cards (according to the version) and it has a backlit LCD alphanumeric display with twenty characters on four lines. The display is incorporated in the front of the UPS were there is also a high-brightness functioning status indicator with traffic light type green-yellow-red. Five simple keys situated near the display enable the user to display the functioning data, set the functioning parameters, analyse the status of the individual power modules, select the language in which the messages are to be displayed, start the hot-swap mode and carry out a guided set of functional tests and procedures. BCM - Battery Charger Module 3 108 51 The additional battery charger module works in parallel and in sync with the battery chargers in the power modules and it is managed by the same algorithm that governs the recharging cycle. Every power module can provide up to 2.5A of charge current. Every additional battery charger module provides up to 15A of charge current that are added to the current of the battery chargers in the power modules. This guarantees a reduction of the charge time in installations requiring long autonomies and increases the availability of the UPS after a black out. During functioning, the battery charger module takes current from the input phase where it is installed. It is possible to install any quantity of BCMs as long as there is at least one power module and enough empty slots in the UPS cabinet. All the information regarding the functioning status of the BCM is given by the LED on the front of the module and by what is shown on the UPS display. The battery charger module is managed by a microprocessor to optimize performance and reliability. Its use in conjunction with batteries having capacities above 60Ah is recommended. ECO MODE One functioning mode of the Trimod HE UPS is called “eco mode”. With this mode it is possible to save energy while guaranteeing uninterruptability of the power supply to the load connected. During the functioning in eco mode, the load is powered directly from the electrical mains through the automatic bypass circuit inside the power modules. This means that the output voltage and frequency are the same as the mains. The advantage obtained in the eco mode is a greater electrical efficiency and consequently a reduction in consumption. If the output voltage leaves the window of tolerance (-20% / +15% of the voltage set on the output), the UPS actuates its inverter stage and powers the load with the energy stored in the batteries. The autonomy during the stored energy mode depends on the configuration of the UPS (nominal power, battery capacity) and on the percentage of load applied. When the mains are back within the tolerance values, the UPS switches automatically back to the eco mode. It is possible to change the functioning mode between on-line and eco mode (and viceversa) both with the UPS on and with the UPS off (in this case entering the Service Mode).

17

User manual

Trimod HE

4. Unpacking and positioning 4.1 Visual check

On delivery of the UPS, carefully inspect the packaging and the product for any damage that might have occurred during transport. Check there is no damage to the indicator on the outer label reading “Shock Watch”. If there is possible or ascertained damage, immediately inform: - the transporter; - the LEGRAND Technical Support Service. Check that the equipment corresponds with the items indicated in the delivery documentation. Follow the instructions in Chapter 8 when storing the UPS.

4.1.1 Equipment check The equipment and the relative supplied accessories must be in perfect conditions. Check that: - the shipping data (address of the recipient, no. of packages, order no, etc.) correspond to what is contained in the delivery documentation; - the technical rating plate data on the label applied to the UPS correspond with the material described in the delivery documentation; - the documentation accompanying the equipment includes the installation and user manuals. In case of discrepancy, immediately inform the LEGRAND Technical Support Service before commissioning the equipment.

4.2 Unpacking

To remove the packaging material, comply with the icons on the outside of the box and observe the following procedure: 1. cut the wrapping material and open the plastic packaging safety holds; 2. open the top of the box; 3. remove the upper protection; 4. remove the four protective corners; 5. remove the packaging container pulling it upwards; 6. remove the pallet and the front/rear bracket from the UPS by undoing the four fixing screws present; 7. examine the UPS for any damage. Immediately inform the shipper and the supplier in the case of apparent damage. Keep the packaging material for any future shipment. The package can be fully recycled.

4.3 Check of the content

The content of the supply is subject to thorough checking before the shipment; nonetheless it is always advisable to check that it is complete and in order on receiving the material. The following list is general: - 1 Trimod HE UPS; - 1 envelope of accessories containing washers for the contact with the earthing, set of screws for fitting the panels, two eight-pole terminal strips, a serial cable and fuses (the latter are only included on models with internal batteries); - 1 envelope of accessories containing one or more EC15 connectors according to the model and connecting jumpers for the terminal strip (ONLY for Trimod HE 10, 15, 20 and 30 TM); - 1 front closing panel; - 2 base strips for side closing; - user manual; - acceptance report; - quickstart and installation and maintenance manual. Should there be defects and/or missing material, immediately inform the LEGRAND Technical Assistance Centre before commissioning the equipment. CAUTION The quickstart and the installation manual must be used and consulted by SKILLED TECHNICIANS only. INDICATION When purchasing empty cabinets, the power modules and any battery drawers to be installed must be purchased separately.

18

4.4 Movement WARNING Move the UPS very carefully, lifting it as little as possible and avoiding dangerous swings or falls. The equipment must always be handled by trained and instructed personnel equipped with the Personal Protective Equipment illustrated in chapter 2. The Trimod HE UPS has wheels at the back of the cabinet. Before installation and while it is still empty, it can be moved by hand by at least two people. For any lifting, use a forklift or a transpallet with an adequate carrying capacity, placing the forks in the wooden base and making sure they come out the other side by at least twenty centimetres. WARNING Do not move the UPS after installation or following the insertion of any power module and battery drawer.

4.5 Positioning constraints Minimum recommended distances for the UPS X=100 mm / Y=200 mm

Recommended minimum distances UPS Trimod HE® + Trimod HE® BATTERY X=100 mm / Y=200 mm

BATTERY CABINET

The UPS must be positioned respecting the following conditions: - temperature and humidity must be within permitted limits; - fire regulations must be respected; - the wiring must be simply made; - front and rear accessibility must be available for assistance or periodic servicing; - the cooling flow of air must be guaranteed; - the air conditioning system must be adequately scaled; - dust or corrosive/explosive gasses must be absent; - the premises must be free of vibration; - the rear and side space must be enough to guarantee an adequate circulation of air for cooling; - the support surface must be scaled in for the carrying capacity necessary to support the equipment.

To safeguard the batteries as well as possible it is necessary to bear in mind that their average lifetime is strongly influenced by the operating room temperature. Position the UPS in an environment with a temperature range between +20°C (+68°F) and +25°C (+77°F) to guarantee the optimum life of the batteries. Before proceding with the installation operations, make sure that there is enough lighting to clearly see every detail. Provide artificial lighting if the natural lighting does not satisfy the requirements cited. In the case of maintenance operations in places that are not sufficiently well lit, portable lighting systems must be used, avoiding shadows that prevent or reduce visibility on the point where you intend to work or on the surrounding areas.

4.6 Final operations

Once the UPS has been properly positioned, fit the two base strips and the front one provided in the accessory kit.

19

User manual

Trimod HE

5. Control panel 5.1 Description WARNING The control panel allows to access some configuration pages of the UPS menu. Only a skilled technician (paragraph 2.2.1) is authorized to modify the configuration set during the installation. Wrong settings could lead to injury or material damage to the equipment and the things around it. The control panel is in the front part of the UPS and consists of an LCD display with 4 x 20 character rows, a backlit multicolour status indicator and a five keys keyboard.

LEGEND 1 - 4 line x 20 character LCD display 2 - ESCAPE key Main functions: - exit a function without changing it; - passage from a lower to a higher menu level; - exit the main menu and return to the status display; - silence of the buzzer. 3 - ARROW UP key Main functions: - selection of the prior function; - increase of a value within a function; - selection of a new item within a function (e.g. from DISABLED to ENABLED); - scroll a menu with more than four lines; - change of the page of the main screen. 4 - ARROW DOWN key Main functions: - selection of the subsequent function; - decrease of a value within a function; - selection of a new item within a function (e.g. from ENABLED to DISABLED); - scroll a menu with more than four lines; - change of the page of the main screen.

20

5 - ENTER key Main functions: - confirmation of a value; - access a menu item; - passage from a higher to a lower menu level; - it allows access to the Service Mode. 6 - ON/OFF key Main functions: - to turn the UPS on and off; - to enable the hot-swap replacement of the power modules (only for MULTI CTRL models); - to shut down the output phases individually (only with the UPS set with 3 output independent phases). 7 - multicolour backlit status indicator

5.2 Service Mode

This is the functioning mode necessary to make the setup during the installation and to manage the software updating of the command boards and power modules. To access this mode, press the ENTER key with the the UPS off until the display shows the text "Service Mode..." At the end of the start-up procedure, press the ENTER key to access the navigation menu. It is possible to choose one of the following languages for the text displayed: Italian, English, German, French, Russian, Spanish, Polish and Portuguese. Follow the path: UPS Setup  Operator Panel  Language and press the ENTER key to confirm the choice. Press the ON/OFF key to exit. Alternatively, the UPS turns off automatically after 20 minutes of not receiving manual or serial commands.

5.3 Main screen

The main screen is shown on the display during UPS operation. Using the ARROW UP and ARROW DOWN keys it is possible to scroll through the different pages. Every page gives several information about the status of the UPS. The pictures of the different pages of the main screen are shown below: MAIN PAGE

DATA DISPLAYED

1 input - output - battery 1st line: Functioning status of the UPS. If the text is "TRIMOD", the UPS is functioning properly 2nd line: Input voltages 3rd line: Voltage set on output, active power absorbed by the load and total percentage of the load applied. 4th line: Bar showing remaining battery capacity and the actual time of functioning in case of a power failure. 2 input - percentage output - battery 1st line: Functioning status of the UPS. if the text is "TRIMOD", the UPS is functioning properly 2nd line: Input voltages 3rd line: Percentage of the loads on the output phases 4th line: Bar showing remaining battery capacity and the actual time of functioning in case of a power failure. 3 bypass - output - battery 1st line: Functioning status of the UPS. If the text is "TRIMOD", the UPS is functioning properly 2nd line: Bypass voltages 3rd line: Voltage set on output, active power absorbed by the load and total percentage of the load applied. 4th line: Bar showing remaining battery capacity and the actual time of functioning in case of a power failure. 4 bypass - percentage output - battery 1st line: Functioning status of the UPS. If the text is "TRIMOD", the UPS is functioning properly 2nd line: Bypass voltages 3rd line: Percentage of the loads on the output phases 4th line: Bar showing remaining battery capacity and the actual time of functioning in case of a power failure.

21

User manual

Trimod HE

5. Control panel MAIN PAGE 5 load availability on output

6 measurements on output

7 output line voltages

8 measurement on input

9 bypass line voltages

10 battery status

Charging

22

- maint.

DATA DISPLAYED 1st line: Functioning status of the UPS. If the text is "TRIMOD", the UPS is functioning properly 2nd line: Phase L1 - power in kVA or in Watt compared with the nominal power or current compared with the rated or relative percentage 3rd line: Phase L2 - power in kVA or in Watt compared with the nominal power or current compared with the rated or relative percentage 4th line: Phase L3 - power in kVA or in Watt compared with the nominal power or current compared with the rated or relative percentage 1st line: Functioning status of the UPS. If the text is "TRIMOD", the UPS is functioning properly 2nd line: Output L1 phase - Voltage, current and active power 3rd line: Output L2 phase - Voltage, current and active power 4th line: Output L3 phase - Voltage, current and active power 1st line: Functioning status of the UPS. If the text is "TRIMOD", the UPS is functioning properly 2nd line: line voltage between phase L1 and L2 on output 3rd line: line voltage between phase L2 and L3 on output 4th line: line voltage between phase L3 and L1 on output 1st line: Functioning status of the UPS. If the text is "TRIMOD", the UPS is functioning properly 2nd line: Input L1 phase - Voltage, current and active power 3rd line: Input L2 phase - Voltage, current and active power 4th line: Input L3 phase - Voltage, current and active power 1st line: Functioning status of the UPS. If the text is "TRIMOD", the UPS is functioning properly 2nd line: Line voltage between L1 and L2 of bypass line 3rd line: Line voltage between L2 and L3 of bypass line 4th line: Line voltage between L3 and L1 of bypass line 1st line: Functioning status of the UPS. If the text is "TRIMOD", the UPS is functioning properly 2nd line: Voltage, charging current (negative value when charging in progress, positive value when the batteries are powering the equipment) 3rd line: Battery capacity percentage compared with the nominal percentage, time remaining, total autonomy time 4th line: Battery status - Battery Stand-by - Discharging - Reserve autonomy - End autonomy - Charging - ph1 - battery recharging status (current limitation) - Charging - ph2 - battery recharging status (voltage limitation) - Charging - maint: Battery recharging in maintenance mode - Charging - float.: Battery charging in floating mode - Testing batteries: Battery test in progress - Equaliz. batteries: Battery equalizing in progress - BATTERY FAULT: battery voltage lower than 100V - MaxTime on Battery: end of the maximum set time for the functioning in battery mode

5.4 Main menu and submenu Press the ENTER key on the main screen of the display to access the menu of the UPS. The main screen has the following items: - UPS Status: it allows to check the UPS status in real time; - UPS Setup: it allows to set all the UPS functions; - Power Modules: it allows to analyze the status of the individual power modules in real time; - Events: it allows to display the events memorized in the UPS history; - Tools: it allows to carry out a series of functional tests on the UPS; - Log Out: it allows to terminate the password-protected session. Press the ENTER key to access the relative submenus. The following table sums up all the menu and submenu pages: UPS Status (paragraph 5.4.1)

UPS Setup (paragraph 5.4.2)

Power Modules (paragraph 5.4.3)

Events (paragraph 5.4.4)

Tools (paragraph 5.4.5)

Log Out (o) (paragraph 5.4.6)

UPS Info

Options

PM Status

Log View

Battery

-

UPS Cfg

Output

Diagnostics (*)

Signalling test (*)

Measures

Input

PM SW update (*)

LCD Display Test (*)

Alarms

Bypass

Assistance

History Data

Batteries

CM errors recovery

Operator Panel Clock Setup Dry contacts (*) Only available in “Service Mode”

(o) Available in password-protected session

The UPS has a menu and relative submenu tree structure, the functions of which are explained in the following paragraphs. On the right of the display, an arrow appears turned downwards or upwards when there are further items to display. Press the ARROW UP and ARROW DOWN keys to display them.

23

User manual

Trimod HE

5. Control panel 5.4.1 UPS Status Model

UPS Info

Equipment model (TRIMOD)

SYNC. address

Synchronisation address of the command board

Number of CM

Number of command boards recognised

Max VA

Maximum apparent power[kVA]

Max W

Maximum active power [kW]

Max Ichg

Maximum current available to charge the batteries [A]

SW Ver.

Firmware version of the command board

PM SW Ver.

Firmware version of the power modules

Boot Ver.

UPS Cfg

Bootloader version in the command board

S/N

UPS serial number

OUT

Single Phase/ Three Phases 120° / Three Phases indep.

IN

Single Phase / Three Phases / inv.3 phases / Undefined (_ _ _)

BYP

Single Phase / Three Phases / inv.3 phases / Undefined (_ _ _)

X/Y - X/Y - X/Y

X Power modules for each phase managed by the command board Y Power modules for each phase managed by the UPS

Number BCM

Number of Battery Charger Modules recognised

Installed KB Batt. Cap.

Capacity of the batteries installed [Ah]

Batt.N per KB Power

Output active power on phase X [W] Output apparent power on phase X [VA]

Vrms

Output effective voltage on phase X [V rms]

Irms Peak Current Frequency Output X

Number of batteries in series available in one KB

Appar. Power

Vrms ph-ph

Measures

Number of KB installed

I Crest factor Power fact.

Output effective line voltage [V rms] Output effective current on phase X [A rms] Output peak current of phase X [A] Pure sine output voltage frequency on phase X [Hz] Crest factor for phase X Power factor of the load connected to the UPS on phase X

Max W

Maximum active power on phase X [W]

Power

Output active power on phase X, expressed as a percentage in relation to the maximum active power available on phase X [%]

Max VA

Maximum apparent power on phase X [VA]

Appar. Power

Output apparent power on phase X, expressed as a percentage in relation to the maximum apparent power available on phase X [%]

INDICATION To change the value of X and therefore vary the phase from which the data is read, press the ENTER key after entering the submenu. 24

Power Appar. Power Vrms

Measures

Input X

Absorbed input active power on phase X [W] Absorbed input apparent power on phase X [VA] Effective input voltage of phase X [V rms]

Vrms bypass

Effective input voltage of phase X of bypass line of the UPS [V rms]

Vrms ph-ph

Effective input line voltage [V rms]

Irms Peak Current Frequency

Absorbed effective input current on phase X [A rms] Input peak current of phase X [A] Pure sine input voltage frequency on phase X [Hz]

I Crest Factor Crest factor for phase X Power Fact.

Power factor of the load connected to the UPS on phase X

INDICATION To change the value of X and therefore vary the phase from which the data is read, press the ENTER key after entering the submenu.

Measures

Voltage

Battery voltage [V]

Current

Current supplied by the batteries (negative if the UPS is charging the batteries) [A]

Residual Cap.

Battery charge status, expressed as percentage [0-100%]

(Status)

Battery charge operating status: - Battery Stand-by - Discharging - Reserve autonomy - End autonomy - Charging - ph1 - Charging - ph2 - Charging - maint. - Charging - float. - Testing batteries - Equaliz. batteries - BATTERY FAULT - MaxTime on Battery

Batteries

Total Auton.

Total autonomy the UPS would have with batteries 100% charged

Resid.Auton.

Residual autonomy of the UPS

V Res.Th. Disch.Count

Misc.

Total number of complete battery discharges

Usage

Total number of hours in which the UPS has functioned in battery mode [h]

Cal.

Day and time of the last calibration. The text “Factory” is displayed if no calibration has yet been made.

Calibr.count

Measures

Threshold voltage of the string of batteries for autonomy end [V]

Total number of calibrations made

Int.Temp

Temperature inside the UPS [°C]

Pos.H.V.Bus

Voltage on positive DC BUS [V]

Neg.H.V.Bus

Voltage on negative DC BUS [V]

25

User manual

Trimod HE

5. Control panel Alarms

Alarm Log. See chapter 6.

INDICATION To scroll through the list of alarms, press the ARROW UP and ARROW DOWN keys. UPS RunTime OnBatteryTime This Batt.

History Data

Total UPS runtime Total UPS untime on battery mode Total UPS runtime with the batteries currently installed

CHG Runtime

Total battery charger runtime

DrainedOut N.

Total number of complete battery discharges

Booster Int.

Total number of booster interventions

BypassInterv.

Total number of bypass interventions

Batt.calibr.

Total number of battery calibrations

Chg.cycle N.

Total number of battery charge cycles

Batt.equal.N.

Total number of battery equalization cycles

Replace batt.N.

Total number of times the batteries have been replaced

Load>80% N

Total number of times the load has exceeded 80% of the rated load

Load>80% T

Total time the load has exceeded 80% of the rated load

Load>100% N

Total number of times the load has exceeded 100% of the rated load

Load>100% T

Total time the load has exceeded 100% of the rated load without the overload being signalled

5.4.2 UPS Setup Start-up on Battery Auto Restart Options

If enabled, it allows the UPS to be started up with no mains supply If enabled, automatic restarts are permitted DISABLED

During normal functioning, the output is not powered.

ENABLED

During normal functioning, the output is powered.

Output options (*)

(*) Available in the “Service Mode” only

26

Voltage

This sets the output voltage value [V] Nominal Value (*)

This makes it possible to set the output frequency value (50 Hz or 60 Hz) independently of the input frequency.

Auto Selection

If enabled, the UPS detects the frequency of the input voltage and synchronises the output to the same value. If disabled, the UPS uses the "Nominal Value".

Frequency

Output Inverter (*)

This sets the output configuration and the applied load: - Single Phase: a unique single phase output - Three Phases 120°: three phase output suited to the supply of three phase loads (e.g. a motor) - Three Phases indep.: three single phase output lines that are independent of each other L1 phase

Phases in startup (**)

L2 phase L3 phase

(*) Available in the “Service Mode” only

This makes it possible to program the start-up status for each output: - Always ON: phase always on during start-up - Always OFF: phase always off during start-up - Last state: phase restored to the status prior to the shut down

(**) Available with the inverter set up as three independent phases only

CAUTION Only a skilled technician is authorized to modify the settings on the Output menu

Input

If enabled, the UPS synchronises the output pure sine with that of the input. PLL Enable If disabled, the output voltage is not synchronised with the input and it is indicated with the status light (green) flashing. This makes it possible to select the frequency range in which the UPS synchronises the output voltage with the input: - NORMAL: syncronization for frequency variations of ±2% of the PLL Range ° nominal value - EXTENDED: syncronization for frequency variations of ±14% of the nominal value - CUSTOM: this can be set by the user (see the next menu item) This makes it possible to set the customised frequency interval in which the UPS synchronises the output voltage with the input. The value can Custom PLL Range be selected from a minimum of 0.5 Hz to a maximum of 7.0 Hz with steps of 0.1 Hz. Input Dip Enable This allows the input dip function to be enabled/disabled

° Available with PLL range set in CUSTOMISED mode INDICATION The PLL function ensures that the output frequency of the UPS is synchronised with that of the input, guaranteeing that passage through zero (zero-crossing) occurs at the same moment. The input-output synchronisation is guaranteed even in case of bypass intervention (e.g. because of overload). INDICATION By disabling the PLL function, the automatic bypass function is deactivated as well. The UPS turns off in case of an extended overload. CAUTION Only a skilled technician is authorized to modify the settings on the Input menu 27

User manual

Trimod HE

5. Control panel

Bypass Enable

If enabled, the UPS manages the bypass intervention automatically. If disabled, the UPS never switches to bypass mode so in the case of an extended overload or in the case of failure and absence of redundancy, the UPS turns off.

Forced Mode

If enabled, the UPS activates the bypass permanently

DIP Speed

This makes it possible to vary the sensibility of the switching circuit: - SLOW: indicated for loads not sensitive to voltage variations and that cause peaks of current - STANDARD: normal mode - FAST: for all loads that are extremely sensible to voltage variations

Off-line Mode

If enabled, the UPS functions in eco mode. During the functioning, the load is powered directly by the automatic bypass circuit. If there is a power failure or the voltage input tolerance is exceeded, the UPS activates the inverter thereby powering the load through the batteries.

Bypass

Start-up on Bypass

If enabled, on mains start-up the initial powering of the load occurs via bypass. If disabled, the inrush current is managed by the inverter as in a battery start-up.

CAUTION Only a skilled technician is authorized to modify the settings on the Bypass menu Reserve Time Threshold values MaxTime on Battery

Charger

Batteries

Standby Charge

Capacity (*)

This sets the maximum functioning time in battery mode. Once this time has elapsed, the UPS turns off. Set at OFF to disable the function If enabled, it activates the battery charge with the UPS off

Restart Enable

This enables or disables the restart of the UPS when the mains returns after the total discharge of the batteries

Min. Autonomy

This sets the percentage charge value of the batteries to be reached with the function of standby charge in order to restart automatically the UPS after a total battery discharge.

Auto Restart

Total KB

This sets the start time of the battery autonomy warning [min]

This sets the total number of KB installed. The parameter is necessary for the UPS to provide correct values for the autonomy based on the load applied and for a correct battery charge. This sets the capacity value of the batteries in the UPS [Ah].

(*) Only available in “Service Mode”

CAUTION Only a skilled technician is authorized to modify the settings on the Batteries menu

28

Language

This sets the language on the display

Buzzer

This enables/disables all the sound signals

Keyboard Beep

Operator Panel

This enables/disables the sound made by key presses

Locked turn off (*)

If enabled, the password is required to shutdown the UPS

Display Backlight

This sets the backlighting of the display: - FIXED: always lit - TIMED: the backlighting goes off after one minute of keyboard inactivity - DISABLED: the lighting is always off

Display Contrast

This sets the display contrast

Password Change

This sets a password that blocks access to the UPS settings

Password level

It indicates the level of the password (the default value is USER)

(*) Only available with the chosen password.

Clock Setup

DD/MM/YY – HH:mm:SS

This sets the date/time of the UPS. By pressing the ENTER key, the value to modify is selected. By pressing the ARROWS UP/DOWN keys, the selected value is increased or decreased. DD: day MM: month YY: year HH: hour mm: minutes SS: seconds

Function

This allows the signal to be associated with the contact: - Mains/Battery - Runtime autonomy - Alarm - Overload - Bypass - UPS is working

Setup

This makes it possible to select: - NORMALLY CLOSED - NORMALLY OPEN

Contact 1

Dry contacts

Contact 2 Contact 3 Contact 4 Contact 5 All

Function Setup Function Setup Function Setup Function Setup

(see contact 1) (see contact 1) (see contact 1) (see contact 1)

Makes it possible to set all the contacts: - NORMALLY CLOSED - NORMALLY OPEN

29

User manual

Trimod HE

5. Control panel 5.4.3 Power Modules Mod.

PM Info X

Model of power module X

SW Ver

Version of the firmware inside power module X

HW Ver

Hardware version of power module X

S/N

Serial number of power module X

Max VA

Maximum apparent power available for power module X [VA]

Max W

Maximum active power available for power module X [W]

Max Ichg

Maximum current available from the battery charger of power module X [A] Power

Active power absorbed by power module X [W]

Appar.Power Apparent power absorbed by power module X [VA] Vrms

Input X

Effective input voltage of power module X [V rms]

Vrms bypass

Effective input voltage for power module X of the bypass line [V rms]

Vrms ph-ph

Effective input line voltage of power module X [V rms]

Irms

Effective current absorbed from the mains by the power module X [A rms]

Peak Current Input peak current of power module X [A] Frequency PM Status

Pure sine input frequency voltage of power module X for the bypass line [Hz]

I Crest factor Crest factor applied by power module X to the mains Power Fact. Power PM Measures

Power factor applied by power module X to the mains Active power supplied by power module X [W]

Appar. Power Apparent power supplied by power module X [VA] Vrms Vrms ph-ph Irms

Effective output voltage of power module X [V rms] Effective output line voltage of power module X [V rms] Effective output current supplied by power module X [A rms]

Peak Current Output peak current of power module X [A] Frequency Output X

Pure sine output voltage frequency of power module X [Hz]

I Crest factor Crest factor of the output current of power module X Power Fact.

Output power factor for power module X

Max W

Maximum active power available from power module X [W]

Power

Active power supplied by power module X, expressed as a percentage in relation to the maximum active power available from power module X [%]

Max VA

Maximum apparent power available from power module X [VA]

Apparent power supplied by power module X, expressed as Appar. Power a percentage in relation to the maximum apparent power available from power module X [%] (continues)

30

Battery X

PM Measures Misc. X

PM Status

PM History Data

Voltage

Battery voltage detected by power module X [V]

Current

Current required to the batteries by power module X (negative if the batteries are charging) [A]

Charger

Status of the battery charger inside power module X

INV HSink Temp. BST HSink Temp.

Temperature of power module X Invertor heat sink [°C] Temperature of power module X Booster/PFC heat sink [°C]

Fan Speed

Fan speed of power module X expressed as a percentage [%]

Pos.H.V.Bus

Voltage on the positive BUS DC of power module X [V]

Neg.H.V.Bus

Voltage on the negative BUS DC of power module X [V]

Run Time

Total Runtime

Batt.Time

Total runtime on battery mode

Chg.Time

Total runtime of the battery charger

Bypass int.

Total number of bypass interventions

Battery int.

Total number of transfers to battery mode

Dumper int. Total number of dumper interventions Mains High

Total number of times when the tension of the input line has exceeded the maximum value allowed by the power module

Overheat N. Total number of overheating Overload N.

Total number of overloads

HVBus Run.N. Total number of overvoltages on the BUS OutDCLevel N. Total number of presence of DC output voltages on the power module INDICATION Press the ENTER key to change the value of X that represents the power module the data is read from. The value of X starts from 0 that represents the first power module installed in the first tunnel at the top left of the UPS. Diagnostics (*)

PM errors recovery

This clears the memory of errors detected in the power module. It deletes only with resettable errors.

Update all PM

This allows the sequential and automatic update of the software in all the power modules present in the UPS. The procedure starts by pressing the ENTER key. If the update is not necessary, a message saying “PM SW Versions updated!” appears on the display. By pressing the ESC key, the procedure ends.

Single PM SW update

This allows the update of the software in each individual power module. Using the ARROW UP/DOWN keys, it is possible to choose the module that has to be updated (‘PM00’ indicates the module installed in the first tunnel at the top left). By pressing the ENTER key a comparison is made between the software currently present in the selected module and the new software. The procedure starts by pressing the ENTER key. When the update is complete, a message saying “PM SW Version updated!” appears on the display. By pressing the ESC key, the procedure ends.

PM SW update (*)

(*) Only available in “Service Mode” CAUTION Only a skilled technician is authorized to carry out an update 31

User manual

Trimod HE

5. Control panel 5.4.4 Events All Critical Events

Log View

Warning

This displays all the events This displays the events that have generated critical alarms This displays the events that have generated noncritical alarms

Info

This displays the events that have generated simple warnings

Automatic

This performs a test on the batteries to check their status and performance

5.4.5 Tools Battery Test

Battery

Batt. Calibration

Battery cycle

This calibrates the batteries, finding the discharge curve. In order for the UPS to provide precise information regarding the charge status, it is necessary to perform the calibration in the following cases: - after installation and before the first start-up; - in case the batteries are replaced; - every six months after the first year of the UPS's life. This carries out a battery test and their equalization to check the status, the performance and to maximise the life of the batteries.

Signalling Test (*)

This carries out the signalling test of the status indicator signal (green, orange and red) and of the acoustic signalling.

LCD Display Test (*)

This performs the test of the alphanumeric display. When the ENTER key is pressed, all the available characters are displayed.

(*) Only available in “Service Mode”

Assistance

CM errors recovery

Display Identifier

This displays the code to communicate to the technical support service.

Use code

Insert the code provided by the Technical Support Service.

This clears the memory of the errors detected by the command board. It works only with resettable errors.

5.4.6 Log Out It is possible to set a password to prevent non-authorised personnel to modify the configuration of the UPS. By choosing a password, it is necessary to enter a private session to modify the UPS settings. At the end of the operations use the "Log Out" menu to leave the private session. If the password has been forgotten, it is necessary to contact the LEGRAND Technical Support Service.

32

5.5 POWER ON/OFF menu

When the UPS is on, it is possible to access a menu called POWER ON/OFF by pressing the ON/OFF button for less than 0,5 seconds. The choices that can be made in this menu are the following:

L1 phase (**)

Press the ENTER key to access the submenu in which it is possible to choose whether to turn phase L1 on or off independently of the others. By pressing the ARROW UP/DOWN keys it is possible to choose the ON or the OFF value. By pressing the ENTER key the value is confirmed; pressing the ESC key you leave the submenu.

L2 phase (**)

Press the ENTER key to access the submenu in which it is possible to choose whether to turn phase L2 on or off independently of the others. By pressing the ARROW UP/DOWN keys it is possible to choose the ON or the OFF value. By pressing the ENTER key the value is confirmed; pressing the ESC key you leave the submenu.

L3 phase (**)

Press the ENTER key to access the submenu in which it is possible to choose whether to turn phase L3 on or off independently of the others. By pressing the ARROW UP/DOWN keys it is possible to choose the ON or the OFF value. By pressing the ENTER key the value is confirmed; pressing the ESC key you leave the submenu.

UPS

Press the ENTER key to accesss the submenu for shutting down the UPS. By pressing the ENTER key again, the UPS shuts down; by pressing the ESC key you leave the submenu. Press the ENTER key to access a submenu to make the hot-swap substitution of the power modules.

Hot swap

CAUTION This operation is reserved to a skilled technician and it is possible only for MULTI CTRL models

(**) Available with the Inverter set up with three phases independent only

5.6 Switching off the UPS CAUTION The shut down procedure must only be applied if the load is off or does not need powering by the UPS. There are two possible ways to shut down the UPS. It is possible to shut down the UPS from the POWER ON/OFF menu or it is possible to perform the following procedure: 1. Keep the ON/OFF key pressed for at least 2 seconds. 2. The display shows the text "Turn off the UPS?". Press the ENTER key. 3. Wait for the shut down operation to complete. If a prolonged shutdown is planned, do as instructed in chapter 8.

5.7 Switching on the UPS

The operator can turn on the UPS by doing the following: 1. Press the ON/OFF key. 2. When the display shows the text " to confirm UPS turn ON”, press the ENTER key. If no operation is carried out within 30 seconds, the UPS turns off. If the display shows the message "WARNING: different UPS setup! to confirm UPS turn on”, the UPS setup is different from the last power up. A skilled technican must check the UPS setup before confirming the power up. 3. Wait for the power up operations to complete. The load is only supplied when the bar with the text “UPS initialize...” displayed reaches the end and the main screen appears.

33

User manual

Trimod HE

6. Diagnosis 6.1 Luminous and audible notifications

The status indicator on the front panel of the UPS and the led on the front of every power module change their colour according to the actual functioning status of the UPS or of the individual power module in accordance with the table shown below. INDICATION Some luminous notifications can be accompanied by an audible signal. To turn off the audible notification, press the ESC key. On every subsequent press, the notification is silenced or enabled. INDICATION If it is not possible to solve the problem, contact the LEGRAND Technical Support Service. STATUS INDICATOR

POWER MODULE LED

AUDIBLE NOTIFICATION

STATUS MESSAGE

UPS STATUS DESCRIPTION AND OPERATING ADVICE

GREEN Steady

GREEN Steady

-

TRIMOD

Normal functioning with mains present and load within the limits

-

-

-

3V Battery Fail

Contact the LEGRAND Technical Support Service

GREEN Steady ORANGE Flashing

ORANGE Flashing

-

Out/phase turned OFF

Phase off in configuration of 3 independent phases output. Check the output setup.

GREEN Steady ORANGE Flashing

-

-

Modules turned off

Command board in hot-swap

GREEN Steady

1 module: ORANGE Steady Remaining modules: GREEN Steady

-

Equalizing Battery

Battery Equalization in progress

-

Mains supply is absent on at least one power module and/or the frequency of the mains is not correct (>68Hz or <43Hz) and/or the input PLL is not synchronised. A skilled technician must check the mains.

GREEN Quick flashing

GREEN Quick flashing

-

GREEN Quick flashing

-

-

-

One or more of the following problems are present: bypass absent, input PLL not synchronised, bypass voltage outside the limits, bypass sequence not correct or reversed, bypass frequency out of tolerance. A skilled technician must check the bypass line.

GREEN Quick flashing

GREEN Quick flashing

-

Bypass line KO

The bypass line cannot be used to power the load

ORANGE Quick flashing

ORANGE Flashing

-

Forced on Bypass UPS on Bypass

Operation in forced bypass mode

ORANGE Steady

ORANGE Steady

500 ms on and 12 s off

UPS on Battery

Stored energy mode

ORANGE Steady

ORANGE Steady

-

Battery Cal...

Battery calibration in progress

ORANGE Steady

-

-

Battery Test...

Battery test in progress continues...

34

STATUS INDICATOR

POWER MODULE LED

AUDIBLE NOTIFICATION

STATUS MESSAGE

UPS STATUS DESCRIPTION AND OPERATING ADVICE

ORANGE Long intermittent

GREEN Steady

-

Make Maintenance

Contact the LEGRAND Technical Support Service

ORANGE Long intermittent

GREEN Steady

-

Check Batteries

A skilled technician must check the batteries status

ORANGE Quick flashing

ORANGE Flashing

-

Maintenance Bypass

Manual bypass mode

ORANGE Short and double intermittent with pause

ORANGE Steady

Short and double intermittent with pause

RUNTIME RESERVE!

Autonomy reserve during battery mode. Short time left before the load is powered by the bypass line.

RED Steady

RED Steady only on the module with the fault

Quick intermittent

FAULT CHARGER

Battery charger faulty on at least one power module. A skilled technician must replace the faulty module.

RED Steady

RED Steady only on the module with the fault

Quick intermittent

FAULT MODULE

A skilled technician must replace the faulty power module

RED Quick flashing

ORANGE Flashing

Quick intermittent

BATTERIES KO

RED Quick flashing

RED Quick flashing

Quick intermittent

BATTERY DISCONNECTED

RED Quick flashing

RED Short and double intermittent with pause

Quick intermittent

BATTERY RUNAWAY

Excessive battery voltage. If the alarm persists over time a skilled technician must check the batteries.

RED Quick flashing

RED Short and double intermittent with pause

Quick intermittent

HVBUS RUNAWAY FAIL

Contact the LEGRAND Technical Support Service

OUT DC LEVEL FAIL

Reset the power module error from the control panel in Service Mode (paragraph 5.4.3) and turn on the UPS. If the error persists, one or more power modules are faulty and a skilled technician must replace them.

Batteries faulty or not connected. A skilled technician must check the batteries. Batteries faulty or not connected. A skilled technician must check the batteries.

RED Quick flashing

RED Steady

RED Quick flashing

RED Short and double intermittent with pause only on the module in alarm mode

Quick intermittent

OVERHEAT

Overheating of one or more power modules. Check the functioning of the module fans and clean the air intake grilles.

RED Quick flashing

RED Short and double intermittent with pause only on the overloaded module

Quick intermittent

OVERLOAD

Overload on one or more power modules. Check the applied load.

RED Quick flashing

-

Quick intermittent

CM FAILURE

Contact the LEGRAND Technical Support Service

RED Quick flashing

-

Quick intermittent

Reference Error! or Reference Warning

Contact the LEGRAND Technical Support Service

RED Quick flashing

-

Quick intermittent

BACKFEED

Contact the LEGRAND Technical Support Service

Quick intermittent

35

User manual

Trimod HE

6. Diagnosis 6.2 Messages

This paragraph shows the messages that appear on the control panel display or in the event list (see paragraph 5.4.4) and the probable cause that could have generated them. INDICATION If it is not possible to solve the problem, contact the LEGRAND Technical Support Service. FIRST ROW OF THE MAIN SCREEN MESSAGE TRIMOD

MEANING AND OPERATING ADVICE The UPS is functioning properly

Service Mode

UPS in Service Mode. The parameters can be modified through the control panel and updates can be made.

UPS initialize...

The UPS is starting-up

CM initialize...

The command board is starting-up all the power modules after the exit from the hot-swap mode

CM turning off...

The command board is turning off all the power modules after entering the hot-swap mode

Service Mode...

The UPS is starting up in Service Mode

Maintenance Bypass Forced on Bypass

The load is powered directly from the mains by means of the manual bypass. The UPS has entered the forced Bypass mode through a selection from the control panel.

UPS on Bypass

UPS in bypass mode.

Bypass line KO

A skilled technician must check the bypass line.

EPS in stand-by

Output non powered during normal functioning (with mains present)

Modules turned OFF

Command board in hot-swap. The power modules are no longer powered and ready to be replaced.

Out/phase turned OFF

Phase or output off. Configuration obtained via display or after a UPS malfunctioning.

UPS on Battery

UPS in battery mode. This configuration is due to a fault in the UPS power supply system or a loss of mains.

UPS in off-line

The load is powered directly from the bypass line. In case of a power failure, the UPS transfers to battery mode.

Battery Cal...

The UPS is performing the calibration of the batteries through a command from the control board

Battery Test...

The UPS is carrying out a test on the batteries in order to check their status and proper operation

Equalizing Battery Buzzer Muted RUNTIME RESERVE! FAULT MODULE

The UPS is performing battery equalization The buzzer has been silenced The battery charge is low while the UPS is working in battery mode. One or more more modules are faulty. A skilled technician must replace them. continues...

36

MESSAGE BACKFEED FAULT CHARGER BATTERIES KO BATTERY DISCONNECTED STRONG OVERLOAD

MEANING AND OPERATING ADVICE A backfeed error has been detected. Contact the LEGRAND Technical Support Service. The battery charger circuit of one or more power modules is faulty. A skilled technician must replace them. Batteries faulty. A skilled technician must check their status and replace them if necessary. The UPS detects a battery voltage inferior to 10 V. A skilled technician must verify the batteries and the cabling. The load has caused an excessive lowering of the output voltage

OVERLOAD

The total load is more than the nominal power of the UPS

OVERHEAT

The temperature inside the UPS is outside the nominal range. Check the functioning of the module fans and clean the air intake grilles.

OUT DC LEVEL FAIL HVBUS RUNAWAY FAIL BATTERY RUNAWAY 3V Battery Fail Abnormal batt.drain Check Batteries Make Maintenance Shutdown ongoing...

Reset the power modules error from the control panel in Service Mode (paragraph 6.4.3) and turn on the UPS. If the error persists, one or more modules are faulty and a skilled technician must replace them. Contact the LEGRAND Technical Support Service The voltage of the batteries is out of control. A skilled technician must check the status of the batteries and of the battery charger. The 3V battery of the command board is dead. Contact the LEGRAND Technical Support Service. Abnormal battery drain. Contact the LEGRAND Technical Support Service. A skilled technician must check the status of the batteries Contact the LEGRAND Technical Support Service The UPS is shutting down after being programmed to do so by the user

Charging Battery

The UPS is charging the batteries. The charging mode is indicated next to the message.

UPS EMERGENCY!

Contact the LEGRAND Technical Support Service

LOAD TURNED OFF! UPS TURNED OFF! UPS BLOCKED! PM FW not updated!

A prolonged excessive load (e.g. a short circuit) has caused a significant lowering of the output voltage for an excessive period and the load is no longer powered or the load has been shut down because of an extended overload in battery mode. The UPS is turning off due to a command given from the control panel Contact the LEGRAND Technical Support Service One or more power modules have the software not compatible with the command board. Update the modules before turning on the UPS.

Reference Error!

Synchronisation error among the command boards. Contact the LEGRAND Technical Support Service.

CM FAILURE

Communication error among the command boards. Contact the LEGRAND Technical Support Service.

Reference Warning

Synchronisation error among the command boards. Contact the LEGRAND Technical Support Service.

37

User manual

Trimod HE

6. Diagnosis ALARMS MESSAGE INVERTER FAIL

Fault detected in the Inverter circuit. One or more power modules are faulty. A skilled technician must replace them.

BOOSTER FAIL

Fault occurred in the Booster/PFC circuit. One or more power modules are faulty. A skilled technician must replace them.

CHARGER FAIL

Fault occured in the Battery charger circuit. One or more power modules are faulty. A skilled technician must replace them.

OVERHEAT

Overheating. Check the UPS ventilation system.

OVERLOAD

The load is higher than the rated power of the UPS.

HVBUS RUNAWAY OUTPUT DC LEVEL ERROR BATTERY VOLTAGE TOO HIGH MODULE COMMUNICATION FAIL PM -> CM

Contact the LEGRAND Technical Support Service A skilled technician must check that there is not a faulty power module or a voltage backfeed from the output Battery voltage too high. A skilled technician must check the batteries. Fault in the communication with the power modules. Contact the LEGRAND Technical Support Service.

BATTERY WIRING FAIL

Error in the battery connection with the power modules. One or more modules are faulty. A skilled technician must replace them.

MAINS WIRING FAIL

Error in the mains connection with the power modules. One or more modules are faulty. A skilled technician must replace them.

H.V.BUS WIRING FAIL

Error in the DC bus connection with the power modules. One or more modules are faulty. A skilled technician must replace them.

BATTERY DISCONNECTED OR POLARITY INVERTED MODULE COMMUNICATION FAIL CM -> PM

The batteries were not connected correctly ot the polarity has been inverted Fault in the communication system with the power modules. Contact the LEGRAND Technical Support Service.

UNPROTECTED LOAD

Load not protected

MAKE MAINTENANCE

Contact the Legrand Technical Support Service

CHECK BATTERIES

38

MEANING

A skilled technician must check the battery status

REFERENCE ERROR OVER CAN NETWORK!

Synchronisation failure among the command boards. Contact the LEGRAND Technical Support Service.

CM FAILURE ON CAN NET

Synchronisation failure among the command boards. Contact the LEGRAND Technical Support Service.

BACKFEED

A backfeed error has been detected. Contact the LEGRAND Technical Support Service.

ABNORMAL BATTERY DRAIN

Abnormal battery drain. Contact the LEGRAND Technical Support Service.

SCREEN DISPLAYED ON START-UP OR SHUT DOWN MESSAGE First Turn ON: Supply Mains!

MEANING AND OPERATING ADVICE The UPS has never been turned on. No mains input. Start-up not permitted. Make sure the mains is present before turning on.

Mains not Present! Start-up not Allowed

No mains input. Start-up not permitted. To start the UPS in stored energy mode select this configuration from the control panel (paragraph 5.4.2).

Emergency Power Off!

The Emergency Power Off (EPO) has been activated. The EPO command has been sent by a push-button or a switch on the input line has been opened during the normal functioning of the UPS. Check the emergency push-button.

Incomplete Setup for start-up!

The UPS requires a complete configuration for start-up. Check that the output configuration, bypass enabling, number of KB, number of batteries per KB and output voltage have been inserted properly.

Three Phase Voltage Sequence Invalid!

The three phase sequence is not valid. A skilled technician must check that the input three phase system has been correctly connected.

Invalid PM SW Versions: to execute update

The SW versions of some or of all the power modules are not correct. Press the ENTER key to update. At the end of the update, the UPS continues the start-up procedure.

Invalid PM HW Versions!

One or more power modules are not compatible with the UPS. Contact the LEGRAND Technical Support Service.

START-UP Error!

An error has occurred during the start-up procedure of the UPS. Contact the LEGRAND Technical Support Service.

Start-up aborted

The start-up has not been confirmed from the control panel within 30 seconds of the confirmation request of the start-up procedure.

UPS turned off by program! Incorrect setup turn-off Incorrect KB setup turn-off

UPS shut down as programmed via software in a remote controlled system An error has occurred during the configuration. UPS is shutting down. One or more of the parameters have not been set properly. Check the configuration from the control panel. An error has occurred during the configuration of the number of KB. Set the right number of KB from the control panel (paragraph 5.4.2)

Low Battery TurnOff

UPS shutdown during battery mode because the minimum voltage level of the batteries has been reached

Battery Start up Failed. Check polarity.

The batteries are not connected to the UPS or the BUS is not properly charged. A skilled technician must verify the batteries.

Battery Time Expired

UPS shutdown during battery mode because the maximum battery operating time set from the control panel has been reached (paragraph 5.4.2)

Load turned OFF Powered from Output Turned Off with charged H.V.bus Saving NVData error Invalid CM SW Versions: Execute update!

The load power has been cut off Start-up error. Voltage present on the UPS output. A skilled technician must check the UPS connections. The UPS has not shutdown properly. Make sure the DC buses are discharged before performing any maintenance operation on the UPS. Error saving some UPS parameters. If the problem persists, contact the LEGRAND Technical Support Service. The command boards have been programmed with different software versions. The software versions must be aligned by carrying out an update of the command boards through a PC. 39

User manual

Trimod HE

6. Diagnosis MESSAGES DISPLAYED ON START-UP MESSAGE

MEANING AND OPERATING ADVICE

WARNING: Alarm records in memory!

It is necessary to confirm the turning on of the UPS in presence of alarms in the even list

WARNING: different UPS setup!

The UPS configuration changed from the previous time the UPS was turned on. A skilled technician must verify the configuration before turning on the UPS.

Maintenance Bypass! Open output

Open the output breaker before turning on the UPS to exit the manual maintenance bypass mode.

Turn ON after low battery turn OFF.

The UPS is turned on after a previous end of autonomy in battery mode

to confirm UPS turn ON

Press the ENTER key to turn on the UPS

CRITICAL EVENTS (paragraph 5.4.4) MESSAGE

MEANING AND OPERATING ADVICE

Inverter Fail

Fault detected in the Inverter circuit. One or more power modules are faulty. A skilled technician must replace them.

Booster Fail

Fault detected in the Booster/PFC circuit. One or more power modules are faulty. A skilled technician must replace them.

Battery Charger Fail

Fault detected in the Battery charger circuit. One or more power modules are faulty. A skilled technician must replace them.

Overheat

Overheating. Check the UPS ventilation system.

Overload

Overload. Check the load level connected to the UPS.

H.V.Bus Runaway Failure Output DC Level Battery voltage too high

Contact the LEGRAND Technical Support Service A skilled technician must check that there is not a faulty power module or a voltage backfeed from the load Battery voltage too high. A skilled technician must check the batteries.

Power Module comm. failure

Contact the LEGRAND Technical Support Service

Emergency

Contact the LEGRAND Technical Support Service

Load turned OFF

The load power has been cut off

Irregular TurnOff

UPS shutdown in an anomolous way. The skilled technician must make sure that there is no voltage inside the UPS before performing any maintenance operation.

Overload TurnOff

UPS shutdown due to an extended overload

Emergency Power Off turn-OFF Battery KO Power Module battery wiring failure

UPS shutdown due to an Emergency Power Off Fault in the batteries. A skilled technician must check them. There is a fault in the connection of the batteries to the power modules. One or more power modules are faulty. A skilled technician must replace them. continues...

40

MESSAGE

MEANING AND OPERATING ADVICE

Power Module mains wiring failure

There is a fault in the connection of the mains to the power modules. One or more power modules are faulty. A skilled technician must replace them.

Power Module HVBus wiring failure

There is a fault in the connection of the HVBus to the power modules. One or more power modules are faulty. A skilled technician must replace them.

Communication failure between CM Backfeed Abnormal battery drain

Communication error among the command boards. Contact the LEGRAND Technical Support Service. A backfeed error has been detected. Contact the LEGRAND Technical Support Service. Abnormal battery drain. Contact the Legrand Technical Support Service.

NOTIFICATION EVENTS (paragraph 5.4.4) MESSAGE Low Battery TurnOff

MEANING AND OPERATING ADVICE UPS shutdown due to low battery voltage

Invalid sequence turn-OFF

UPS shutdown due to incorrect three phase sequence on input. A skilled technician must check that the input three phase system has been correctly connected.

Battery calibration aborted

Battery calibration interrupted by the user

Battery Time Expired StartUP error

Shutdown of the UPS because the maximum battery operating time set from the control panel has been reached (paragraph 5.4.2) Start-up error

Start-up granted with alarms

UPS start-up authorised in the presence of alarms

Start-up granted with new cfg

UPS start-up authorised with new configuration. The number of power modules installed on the UPS has changed.

Incorrect setup turn-off PM firmware updated Strong overload Powered from Output Turned Off with charged H.V.bus Make Maintenance Check Batteries

UPS shutdown because the configuration is wrong. The number of power modules detected by the UPS is not correct for the output configuration set. Power module software updated Strong overload Voltage present on the UPS output. A skilled technician must check the connections. The UPS has not shutdown properly. The UPS has shutdown without completely discharging the buses. Contact the LEGRAND Technical Support Service A skilled technician must check the batteries

Replace batteries

A skilled technician must check the battery status and change the batteries if necessary

Low Battery Emergency

The load is powered directly from the bypass line due to an end of autonomy continues...

41

User manual

Trimod HE

6. Diagnosis MESSAGE Charge finished Battery disconnected or polarity inverted

MEANING AND OPERATING ADVICE Faulty functioning of the battery charger. Contact the LEGRAND Technical Support Service. The batteries were not connected correctly ot the polarity has been inverted

INFORMATIVE EVENTS (paragraph 5.4.4) MESSAGE User Turn ON

User start-up of the UPS

User Turn OFF

User shutdown of the UPS

Auto turn ON

Automatic UPS start-up

Timed turn OFF Stand-by battery charge start

The UPS has been shut down via the delayed shutdown programming (paragraph 5.4.2) The battery charger has started in stand-by mode

UPS on battery

The UPS has transferred to battery mode

UPS on mains

The UPS has transferred to normal mode

Line Out turned OFF

The output is not powered

Battery test executed

Battery testing successfully completed

Battery learning executed

Battery calibration successfully completed

Forced Bypass ON

The forced bypass mode has been enabled

Forced Bypass OFF

The forced bypass mode has been disabled

Maintenance Bypass ON

The load is powered directly from the bypass line

Maintenance Bypass OFF

The load is no longer powered directly from the bypass line

Enter in Hot Swap Exit From Hot Swap

42

MEANING

The UPS has started-up the hot-swap mode The UPS has exited the hot-swap mode

Event list erased

The event list has been erased

Battery replaced

The batteries have been replaced by the LEGRAND Technical Support Service

7. Maintenance DANGER INSTALLATION and ORDINARY MAINTENANCE operations must be carried out only by SKILLED TECHNICIANS (paragraph 2.2.1). EXTRAORDINARY MAINTENANCE operations must be carried out only by LEGRAND TECHNICAL SUPPORT SERVICE.

7.1 Installation DANGER The operator is not authorized to install and connect electrically the UPS. These operations are the sole preserve of a skilled technician (paragraph 2.2.1) who must follow the instructions addressed to him in the installation and maintenance manual. LEGRAND declines all liability for any injury or damage caused by activities carried out differently from the instructions written in this manual or by a skilled technician who doesn’t follow the requirements written in the installation and maintenance manual.

7.2 Preventive maintenance

The UPS does not contain parts for preventive maintenance by the operator. The operator must periodically perform: - a general external cleaning; - a check to verify the absence of alarms on the display; - a check to verify the correct functioning of the fans on each power module. After the first year of life of the UPS, check the batteries every six months through the “battery calibration” function to guarantee the optimal operation and continuous protection of the connected load. With this function, the UPS detects the discharge curve of the batteries in order to provide precise information on the charging state. Enter the main menu to perform this operation and follow the path: Tools  Batteries  Batt. Calibration Press the ENTER key to confirm the choice. Contact the LEGRAND Technical Support Service in case of problems.

7.3 Periodical checks

The correct functioning of the UPS unit must be guaranteed by periodical maintenance inspections. These are essential to safeguard the reliability of the UPS. WARNING The periodical checks involve operations inside the equipment in presence of dangerous voltages. Only maintenance personnel trained by LEGRAND are authorized to intervene.

7.4 Ordinary maintenance checks

Contact a skilled technician if it is necessary to replace or add power modules, battery drawers or external battery cabinets.

7.5 Extraordinary maintenance

Contact the LEGRAND Technical Support Service if there are failures that require the access to internal parts of the UPS.

43

User manual

Trimod HE

8. Warehousing DANGER All storage operations must be carried out only by a SKILLED TECHNICIAN (paragraph 2.2.1) DANGER A SKILLED TECHNICIAN must check that there is no voltage present before disconnecting the cables. All the battery breakers on the UPS and on the external battery cabinets must be open. The battery drawers of the Trimod HE MODULAR BATTERY (if present) and of the UPS (according to the model) must be removed.

8.1 UPS

The UPS must be stored in an environment with a room temperature between -20°C (-4°F) and +50°C (+122°F) and humidity less than 90% (not condensing).

8.2 Batteries

It is possible to store batteries without recharging them in the following conditions: - up to 6 months if the temperature is between +20°C (+68°F) and +30°C (+86°F); - up to 3 months if the temperature is between +30°C (+86°F) and +40°C (+104°F); - up to 2 months if the temperature is over +40°C (+104°F). CAUTION The battery drawers or the external battery cabinets must never be stored if the batteries are partially or totally discharged. LEGRAND is not liable for any damage or bad functioning caused to the UPS by wrong warehousing of the batteries.

44

9. Dismantling DANGER Dismantling and disposal operations must be carried out only by a SKILLED TECHNICIAN (paragraph 2.2.1). The instructions in this chapter are to be considered indicative: in every country there are different regulations with regard to the disposal of electronic or hazardous waste such as batteries. It is necessary to strictly adhere to the standards in force in the country where the equipment is used. Do not throw any component of the equipment in the ordinary rubbish.

9.1 Battery disposal

Batteries must be disposed of in a site intended for the recovery of toxic waste. Disposal in the traditional rubbish is not allowed. Apply to the competent agencies in your countries for the proper procedure.

Pb WARNING A battery may constitute a risk of electric shock and high short-circuit current. When working on batteries, the prescriptions indicated in chapter 2 must be adhered to.

9.2 UPS dismantling

The dismantling of the UPS must occur after the dismantling of the various parts it consists of. For the dismantling operations, it is necessary to wear the Personal Protective Equipment mentioned in paragraph 2.3 and to consult the instructions and diagrams in the installation and maintenance manual. Sub-divide the components separating the metal from the plastic, from the copper and so on according to the type of selective waste disposal in the country where the equipment is dismantled. If the dismantled components must be stored before their disposal, be careful to keep them in a safe place protected from atmospheric agents to avoid soil and groundwater contamination.

9.3 Electronic component dismantling

For the disposal of electronic waste like the control panels or the command boards, it is necessary to refer to the relevant standards. This symbol indicates that in order to prevent any negative effects on the environment and on people, this product should be disposed of separately from other household waste, by taking it to authorised collection centres, in accordance with the EU countries local waste disposal legislations. Disposing of the product without following local regulations may be punished by law. It is recommended to check that this equipment subject to WEEE legislations in the country where it is used.

45

User manual

Trimod HE

10. Technical data Main features 3 104 22 3 104 31 3 104 42 3 104 43 3 104 44 3 104 02 3 103 96 3 103 97 10 kVA

3 104 23 3 104 33 3 104 45 3 104 46 3 104 07 3 104 08 3 104 03

Nominal power

10 kVA

15 KVA

20 kVA

30 kVA

Active Power

10 kW

15 kW

20 kW

30 kW

15 kVA

Single-phase / Single-phase Single-phase / Three-phase Three-phase / Single-phase Three-phase / Three-phase (may be configured by a skilled technician)

Dual Input

Command boards

46

3 104 26 3 104 27 3 104 73 3 104 71 3 104 72 3 104 19 3 104 20

40 kVA

60 kVA

80 kVA

30 kVA

40 kVA

60 kVA

80 kVA

30 kW

40 kW

60 kW

80 kW

online, double conversion Classification according to EN62040-3: VFI-SS-111

Technology

IN/OUT Configuration

3 104 23 3 104 25 3 104 24 3 104 32 3 104 68 3 104 34 3 104 33 3 104 69 3 104 47 3 104 18 3 104 48 3 104 17 3 104 13 3 104 15 3 104 14 3 104 09 20 kVA 30 kVA TM 30 kVA TT

Three-phase / Three-phase

Available on all models

1

1 2 for the MULTI CTRL models (3 104 68-69-71)

1 3 for the MULTI CTRL model (3 104 72)

UPS architecture

Modular with power modules PF=1 Expandable, redundant N+X

Neutral system

Neutral passing straight from input to output (not isolated)

Bypass

Automatic (static and electromechanical) Manual (for maintenance)

4

Input electrical characteristics 3 104 22 3 104 31 3 104 42 3 104 43 3 104 44 3 104 02 3 103 96 3 103 9 10 kVA

3 104 23 3 104 33 3 104 45 3 104 46 3 104 07 3 104 08 3 104 03

Maximum three-phase/ three-phase current

19.2 A

28.8 A

38.4 A

57.6 A

Maximum three-phase/ single-phase current

19.2 A

28.8 A

38.4 A

Maximum single-phase/ three-phase current

57.6 A

86.4 A

Maximum single-phase/ single-phase current

57.6 A

86.4 A

Nominal input voltage

15 kVA

3 104 23 3 104 25 3 104 24 3 104 32 3 104 68 3 104 34 3 104 33 3 104 69 3 104 47 3 104 18 3 104 48 3 104 17 3 104 13 3 104 15 3 104 14 3 104 09 20 kVA 30 kVA TM 30 kVA TT

3 104 26 3 104 27 3 104 73 3 104 71 3 104 72 3 104 19 3 104 20

40 kVA

60 kVA

80 kVA

57.6 A

76.8 A

115.2 A

153.6 A

57.6 A

-

-

-

-

115.2 A

172.8 A

-

-

-

-

115.2 A

172.8 A

-

-

-

-

230 V + 15% - 20% (Single-phase) 400 V + 15% - 20% (Three-phase) (neutral line indispensable)

400 V + 15% - 20% (Three-phase) (neutral line indispensable)

Input frequency

50 / 60 Hz ± 2% 50 / 60 Hz ± 14 % (autosensing and/or selectable by the user)

Power factor on input

> 0.99

Total harmonic distortion of the input current

THDi < 3%

47

User manual

Trimod HE

10. Technical data Electrical output characteristics (normal mode) 3 104 22 3 104 31 3 104 42 3 104 43 3 104 44 3 104 02 3 103 96 3 103 97 10 kVA

3 104 23 3 104 33 3 104 45 3 104 46 3 104 07 3 104 08 3 104 03

Maximum three-phase/ three-phase current

14.5 A

21.7 A

29 A

43.5 A

Maximum three-phase/ single-phase current

43.5 A

65.2 A

87 A

Maximum single-phase/ three-phase current

14.5 A

21.7 A

Maximum single-phase/ single-phase current

43.5 A

65.2 A

Nominal output voltage

15 kVA

3 104 23 3 104 25 3 104 24 3 104 32 3 104 68 3 104 34 3 104 33 3 104 69 3 104 47 3 104 18 3 104 48 3 104 17 3 104 13 3 104 15 3 104 14 3 104 09 20 kVA 30 kVA TM 30 kVA TT

3 104 26 3 104 27 3 104 73 3 104 71 3 104 72 3 104 19 3 104 20

40 kVA

60 kVA

80 kVA

43.5 A

58 A

87 A

116 A

130.5 A

-

-

-

-

29 A

43.5 A

-

-

-

-

87 A

130.5 A

-

-

-

-

230 V ± 1% (Single-phase) 400 V ± 1% (Three-phase)

400 V ± 1% (Three-phase)

Nominal output frequency

50 / 60 Hz

Tolerance on the output frequency

If synchronized with the input frequency: adjustable range from ±1% to ±14% If not synchronized: ± 1%

Crest factor admitted on the output current

3:1

Efficiency (AC/AC online)

up to 96%

Efficiency ECO mode

99% max 115% for 10 minutes without automatic bypass intervention

Overload admitted

135% for 60 seconds without automatic bypass intervention

Electrical output characteristics (battery mode) 3 104 22 3 104 31 3 104 42 3 104 43 3 104 44 3 104 02 3 103 96 3 103 97 10 kVA Nominal output voltage

48

3 104 23 3 104 33 3 104 45 3 104 46 3 104 07 3 104 08 3 104 03 15 kVA

3 104 23 3 104 25 3 104 24 3 104 32 3 104 68 3 104 34 3 104 33 3 104 69 3 104 47 3 104 18 3 104 48 3 104 17 3 104 13 3 104 15 3 104 14 3 104 09 20 kVA 30 kVA TM 30 kVA TT

230 V ± 1% (Single-phase) 400 V ± 1% (Three-phase)

3 104 26 3 104 27 3 104 73 3 104 71 3 104 72 3 104 19 3 104 20

40 kVA

60 kVA

400 V ± 1% (Three-phase)

Output frequency

50 / 60 Hz ± 1%

Total harmonic distortion of output voltage on nonlinear nominal load

< 1%

Overload admitted

115% for 2 minutes 135% for 30 seconds

80 kVA

Batteries and Battery Charger Characteristics 3 104 22 3 104 31 3 104 42 3 104 43 3 104 44 3 104 02 3 103 96 3 103 97 10 kVA

3 104 23 3 104 33 3 104 45 3 104 46 3 104 07 3 104 08 3 104 03 15 kVA

3 104 23 3 104 25 3 104 24 3 104 32 3 104 68 3 104 34 3 104 33 3 104 69 3 104 47 3 104 18 3 104 48 3 104 17 3 104 13 3 104 15 3 104 14 3 104 09 20 kVA 30 kVA TM 30 kVA TT

3 104 26 3 104 27 3 104 73 3 104 71 3 104 72 3 104 19 3 104 20

40 kVA

60 kVA

Battery type

Lead-acid sealed without maintenance (VRLA)

Unitary capacity

Battery drawers for UPS or external modular battery cabinets: 12 Vdc 7.2Ah or 12 Vdc 9 Ah

Rated battery voltage

240 Vdc (20 x 12 Vdc batteries in series)

Type of battery charger

High performance PWM, one for each power module

Recharge curve

Smart Charge, advanced three-stage cycle

Nominal recharge current battery charger

2.5 A max for every power module installed

80 kVA

Features 3 104 22 3 104 31 3 104 42 3 104 43 3 104 44 3 104 02 3 103 96 3 103 97 10 kVA

3 104 23 3 104 33 3 104 45 3 104 46 3 104 07 3 104 08 3 104 03 15 kVA

3 104 23 3 104 25 3 104 24 3 104 32 3 104 68 3 104 34 3 104 33 3 104 69 3 104 47 3 104 18 3 104 48 3 104 17 3 104 13 3 104 15 3 104 14 3 104 09 20 kVA 30 kVA TM 30 kVA TT

3 104 26 3 104 27 3 104 73 3 104 71 3 104 72 3 104 19 3 104 20

40 kVA

60 kVA

Signals and alarms

Large four line alphanumeric screen, multicolour status indicator, acoustic notification

Communications ports

2 x RS 232 ports, 1 relay interface, 1 contact port, 1 SMNP module slot

Software

Protections

80 kVA

Free software for the Windows and Linux environments is available which expands the functions of: - displaying all the functioning and diagnostic data in case of problems; - setup of special functions; - automatic shutdown of all the computers supplied by the UPS (if connected to TCP/IP network) Visit us at http://www.ups.legrand.com to download a copy of the software free of charge. Electronics against overloads, short-circuit and excessive battery discharge Block of functions due to the end of autonomy In-rush limiter on start up E.P.O. contact Auxiliary contact for Backfeed protection

49

User manual

Trimod HE

10. Technical data Mechanical characteristics Empty power cabinets

Net weight (kg)

3 104 22 10 kVA

3 104 23 15 kVA

3 104 23 20 kVA

3 104 68 3 104 25 30 kVA TM

3 104 24 30 kVA TT

3 104 71 3 104 26 40 kVA

3 104 72 3 104 27 60 kVA

85

90

90

85

80

82

91

Dimensions wxh x d (mm)

414 x 1367 x 628

Power modules (PM4) 3400VA to be installed

3

-

-

-

-

-

-

Power modules (PM6) 5000VA to be installed

-

3

-

6

6

-

-

Power modules (PM7) 6700VA to be installed

-

-

3

-

-

6

9

-

-

-

Power module net weight (kg)

8,5

Battery drawer net weight (kg)

13

-

Empty power cabinets

Net weight (kg)

3 104 31 10 kVA

3 104 33 15 kVA

3 104 32 20 kVA

3 104 33 20 kVA

3 104 69 3 104 34 30 kVA TT

3 104 73 80 kVA

98

102

102

102

106

120

Dimensions wxhxd (mm)

414 x 1650 x 628

Power modules (PM4) 3400VA to be installed

3

-

6

-

-

-

Power modules (PM6) 5000VA to be installed

-

3

-

-

6

-

Power modules (PM7) 6700VA to be installed

-

-

-

3

-

12

Power module net weight (kg) Battery drawer net weight (kg) 50

8,5

13

-

Power cabinets with PM

Net weight (kg)

3 103 96 10 kVA

3 104 08 15 kVA

3 104 14 20 kVA

3 104 18 30 kVA TT

3 104 19 40 kVA

3 104 20 60 kVA

120

120

120

146

146

165

Dimensions wxhxd (mm)

414 x 1367 x 628

Power modules (PM4) 3400VA installed

3

-

-

-

-

-

Power modules (PM6) 5000VA installed

-

3

-

6

-

-

Power modules (PM7) 6700VA installed

-

-

3

-

6

9

-

-

-

Power module net weight (kg)

8,5

Battery drawer net weight (kg)

13

Power cabinets with PM

Net weight (kg)

3 103 97 10 kVA

3 104 03 15 kVA

3 104 09 20 kVA

3 104 15 30 kVA TT

155

155

155

181

Dimensions wxhxd (mm)

414 x 1650 x 628

Power modules (PM4) 3400VA installed

3

-

-

-

Power modules (PM6) 5000VA installed

-

3

-

6

Power modules (PM7) 6700VA installed

-

-

3

-

Power module net weight (kg)

8,5

Battery drawer net weight (kg)

13

51

User manual

Trimod HE

10. Technical data UPS (PM + batteries) 3 104 42

3 104 43

3 104 44

3 104 45

3 104 46

3 104 47

3 104 48

10 kVA

10 kVA

10 kVA

15 kVA

15 kVA

20 kVA

20 kVA

167

223

279

220

279

220

279

Net weight (kg) Dimensions w x h x d (mm)

414 x 1367 x 628

Power modules (PM4) 3400VA installed

3

3

3

-

-

-

-

Power modules (PM6) 5000VA installed

-

-

-

3

3

-

-

Power modules (PM7) 6700VA installed

-

-

-

-

-

3

3

UPS (PM + batteries)

Net weight (kg)

3 104 02 10 kVA

3 104 07 15 kVA

3 104 13 20 kVA

3 104 17 30 kVA TT

350

350

350

325

Dimensions wxhxd (mm)

52

414 x 1650 x 628

Power modules (PM4) 3400VA installed

3

-

-

-

Power modules (PM6) 5000VA installed

-

3

-

6

Power modules (PM7) 6700VA installed

-

-

3

-

Environmental conditions 3 104 22 3 104 31 3 104 42 3 104 43 3 104 44 3 104 02 3 103 96 3 103 97 10 kVA

3 104 23 3 104 33 3 104 45 3 104 46 3 104 07 3 104 08 3 104 03 15 kVA

3 104 23 3 104 25 3 104 24 3 104 32 3 104 68 3 104 34 3 104 33 3 104 69 3 104 47 3 104 18 3 104 48 3 104 17 3 104 13 3 104 15 3 104 14 3 104 09 20 kVA 30 kVA TM 30 kVA TT

3 104 26 3 104 27 3 104 73 3 104 71 3 104 72 3 104 19 3 104 20

40 kVA

Operating temperature

0 ÷ 40 °C

Relative humidity during operation

0% ÷ 95% non condensing

60 kVA

Storage temperature

-20°C ÷ 50 °C (excluding batteries)

Noise level at 1 metre

58 ÷ 62 dBA

Pollution degree

PD2

Environmental category (EN 60721-3-3)

3K2

Protection index

IP 20

Operating height

up to 1000 metres above sea level without derating

80 kVA

Trimod HE 3 108 51 battery charger module (BCM) technical specifications Nominal input voltage

230 Vac + 15% - 20%

Nominal input voltage

19.3 A

Input power factor

PF > 0.99

Total harmonic distortion of the input current

THDi < 3%

Nominal output voltage

240/252 Vdc

Output voltage in maintenance phase

13.75 Vdc per battery

Nominal input voltage

15 Adc max

AC/DC performance

>93% at max rated output current

Functioning status indications

Yellow LED, fast flashing: recharge phase f1

(signalled by multicoloured LED on module and indications on UPS display)

Green LED, slow flashing: recharge phase and maintenance f2 Green LED steady: standby Red LED: fault status

Reference directive and standards Marchi

CE, EAC, CMIM

Safety

2014/35/EU Directive EN 62040-1

EMC

2014/30/EU Directive EN 62040-2

Performance and test requirements

EN 62040-3

53

User manual

Trimod HE

54

55

User manual

Trimod HE

LEGRAND Pro and Consumer Service BP 30076 - 87002 LIMOGES CEDEX FRANCE www.legrand.com

Installer stamp